Operation Parameters 

 

Floating/equalizing charge voltage 

  Floating (25

): 2.25V/cell 

  Equalizing (25

): 2.40V/cell 

  Temperature compensation coefficient: -3.5mv/cell/

 

 
 

Charge current-limiting valve: charge current-limiting valve range is 0.1C

10

-0.4C

10

 

According to the grid condition of the BTS, we divided the grid conditions into five types,   

see the table 3-1 below: 

Table 3-1 Grid conditions definition 

               

 

 

 

 

For the Type I and Type II, the charge current-limiting value is 0.10C

10

, for Type III and Type IV, 

the charge current-limiting value is 0.2C

10

 and the maximum charge current shall not exceed 

0.4C

10

, in case the grid condition is type V, contact our technical team for assistance. 

 
 

Factors Influencing Capacity 

Quantity of electricity battery discharge under certain condition is called battery capacity, symbol is 

“C”,  normal  unit  is  Ampere  Hour,  in  short  is  Ah.  Usually  discharge  rate  is  indicated  through  the 

suffix  of  “C”,  such  as  C10  means  capacity  at  10  hours  discharge  rate.  C3  means  capacity  at  3 

hours discharge rate. 

Battery capacity consists both of nominal capacity  and actual capacity, for nominal capacities of 

the FTC series battery please refer to Table 1-1. Actual capacity is the real quantity of electricity 

battery  discharge  under  certain  condition,  it  equals  to  discharge  current  multiplied  by  discharge 

time, the unit is Ah. 

Battery capacity is directly related to discharge current, end voltage and discharge temperature. In 

general, the smaller discharge current, the lower end voltage, the higher temperature  will cause 

larger discharge capacity. 

 

Type I: Total power failure time per month <10 hours 

Type II: Total power failure time per week <10 hours 

Type III: Power failure time every day ≥2hours, but <4 hours 

Type IV: Power failure time every day ≥4hours, but <8 hours 

Type V: (Including no grid): Power failure time every day ≥8hours 

Operati

on 

and

 m

ai

ntenan

ce

 

 

08

 

Содержание DCS Series

Страница 1: ...DCS Series Deep Cycle Solar Battery Technical Manual SHANDONG SACRED SUN POWER SOURCES CO LTD...

Страница 2: ...stic Curve 04 2 Charging Characteristic Curve 05 3 Cycle Performance Curve 05 4 Performance Data 06 Chapter III Operation and Maintenance 1 Safety Instructions 07 2 Operation Parameters 08 3 Factors I...

Страница 3: ...tive plates Negative plates Separators Container and Lid Posts sealing Terminal posts Electrolyte Vents Plates suspension Inter cell connectors Terminal hardware Product Introduction 01 Thick flat pas...

Страница 4: ...age V Nominal Capacity Ah 25 Dimensions mm Weight kg Short Circuit Current A Internal Resistance m 25 Terminal Type Terminal Layout C10 1 80V cell Length Width Height Total Height DCS12 50 12 50 350 1...

Страница 5: ...negative plate has not reached fully charged stage the process of active substance in negative plate transformed to spongy lead is not finished oxygen gas generated in positive plate reaches the nega...

Страница 6: ...1 describes the discharge curves of DCS Series at different discharge rate at ambient temperature 25 Table 2 1 describes the end voltage at different discharge rate Figure 2 1 Discharge characteristic...

Страница 7: ...arged the charge capacity can be as high as the 104 of the discharged capacity Figure 2 2 Charge characteristic curve Cycle Performance Curve At different depth of discharge the battery cycle life is...

Страница 8: ...16 0 12 0 9 60 5 60 2 28 1 200 1 056 0 562 1 90V 48 0 34 4 21 8 14 4 10 9 8 72 5 10 2 08 1 126 0 982 0 516 Constant power discharge data Table 2 3 DCS Series Battery Constant Power Discharge Data Shee...

Страница 9: ...ed by skilled personnel only Used batteries must be recycled and disposed properly as improper disposal of batteries is harmful to the environment and health Used batteries shall be properly disposed...

Страница 10: ...Hour in short is Ah Usually discharge rate is indicated through the suffix of C such as C10 means capacity at 10 hours discharge rate C3 means capacity at 3 hours discharge rate Battery capacity consi...

Страница 11: ...rted to C25 according to the following formula In the formula T Discharge temperature CT Capacity at temperature of T k Temperature coefficient k 0 006 at C10 discharge k 0 008 at C3 discharge k 0 01...

Страница 12: ...2 35 2 50V When battery float equalizing charge voltage according to the temperature compensation coefficient calculated values over the range according to the corresponding upper limit or lower limi...

Страница 13: ...orage temperature Maximum storage times Freshening charge intervals Recommended freshening charge method 20 25 Every 6 months Using constant current 0 1C10A 0 2C10A to charge battery bank till battery...

Страница 14: ...tainer temperature by using infrared thermometer 2 Use infrared thermometer to measure ambient temperature 1 Ambient Temp 20 45 2 Recommended Temperature 25 5 1 Check that the battery temperature comp...

Страница 15: ...Item Content Standard Maintenance 1 Measurement of each battery s floating voltage Measure each battery s floating voltage by using multimeter Battery floating voltage differential pressure must meet...

Страница 16: ...capacity to be maintained must be more than 80 and in energy storage use more than 60 of the reference capacity Recovery test measure and record various parameters specified in the monthly quarterly...

Страница 17: ...No 1 Shengyang Road Qufu City Shandong Province 273100 P R China Tel 0086 537 4422313 Fax 0086 537 4411980 E mail sales sacredsun cn...

Отзывы: