Timers
While the UNISAB S-Control is waiting for
a timer to expire, the middle LED in the
Timer field will flash.
If a number in the timer row is selected, the
readings will apply to the first active timer
which causes the LED to flash.
The field
Timer No.
shows the number of
the active timer, and the field
Time
shows
the number of remaining seconds.
It is possible to select any timer. By pressing
the
SET
key momentarily in any of the timer
fields, you pass on to the next timer. Anoth-
er way of doing this is to select the field
Timer No.
and enter the required number. SP
can be used to display and change a timer
setpoint. The set point is the value from
which a timer starts counting down (except
for the hour counter).
The following table shows timer numbers
and indicates which timers will cause a LED
to flash, which timers can be edited, etc.
The timers are described in the following
section.
Timer
No.
Description
Unit
Flashing Change- Factory
Min.
Max.
setting
able
0
1
2
3
4
5
6
7
8
9
Hour counter
Start/start
Stop/start
Prelubrication
Oil flow
Motor feedback
Suction pressure ramp
function
Slide max.
Delay before start
Delay before stop
Hrs x 10
Sec.
Sec
Sec.
Sec.
Sec.
Sec./bar
Sec.
Sec.
Sec.
No
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
0
1200
300
60
600
15
0
300
300
300
0
600
60
60
--
5
0
300
0
60
1999
1999
1999
120
--
60
1999
600
1999
1998
*
*
* If
No prelubrication
has been selected in the configuration, factory and minimum settings
will be 0.
10
11
12
13
14
15
Motor feed back
Ext.start permission
(normal stop)
Ext. start permission
(Instant stop)
Set points No. 1/No. 2
Oil flow switch
Thermistor
No
Yes
Yes
No
No
No
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--