45
English
FUNCTIONS FOR THE FACTORY
> 3 sec.
This menu allows you to modify the operating parameters of the thermostat,
the electronic motor and other parameters (pump cycle, RESET).
With the control in
"OFF"
press the
M
and
Fan
buttons simultaneously
for 3 seconds.
Select the parameter to be changed by pressing the "+" or "-" buttons and
confirm with the "M" buttons.
Once the parameter has been selected, the display will show the value.
The value can be changed using the "+" or "-" buttons.
Press the "M" buttons once to return to parameter selection; to exit the
menu press the "M" button for more than 5 sec.
THERMOSTAT PARAMETERS - T-MB version only
Function
Description
Range
Default
OFS
Thermostat NTC probe offset variation
± 3 °C
0 °C
IrL
Relay hysteresis
0.5 ÷ 2.0 °C
0.7 °C
T2 probe PARAMETERS, CHANGEOVER
Function
Description
Range
Default
T2-1
Change of status from ventilation to cooling
15 ÷ 25 °C
< 22 °C
T2-2
Change of status from ventilation to heating
25 ÷ 35 °C
> 32 °C
T3 probe PARAMETERS, TME minimum probe
Function
Description
Range
Default
T3-1
Fan ON in heating mode
> 30 ÷ 40 °C
> 36 °C
T3-2
Fan ON in cooling mode
< 10 ÷ 25 °C
< 22 °C
I-T3
T3 probe hysteresis
2 ÷ 6 °C
4 °C
Anti-stratification cycle PARAMETERS
Function
Description
Range
Default
t1ds
T1 Air probe decompensation - winter cycle (only for set)
0.5 ÷ 2.0 °C
1.5 °C
F-t1
Fan OFF time
5 ÷ 13 min.
10 min.
F-t2
ON time of RL2
30 ÷ 120 sec.
40 sec.
F-t3
Post-ventilation time
5 ÷ 240 sec.
60 sec.
THERMOSTAT PARAMETERS - T-MB-ECM version only
Function
Description
Range
Default
Slu1
Min. speed voltage
1 ÷ 6
1 V
SCu2
Med. speed voltage
3 ÷ 8
5 V
SHu3
Max. speed voltage
6 ÷ 10
10 V
LLSI
Min. speed voltage for autom. fan - winter
1 ÷ 6
1 V
HLSI
Max. speed voltage for autom. fan - winter
5 ÷ 10
10 V
LLSE
Min. speed voltage for autom. fan - summer
1 ÷ 6
1 V
HLSE
Max. speed voltage for autom. fan - summer
5 ÷ 10
10 V
PFC
Proportional band in cooling mode
2.0 ÷ 6.0
3.5 °C
PFH
Proportional band in heating mode
2.0 ÷ 6.0
3.5 °C
OTHER POSITIONS
Function
Description
Operation
rE-t
General reset and restore default values
Confirm with the O/I and
Fan buttons
NOTE:
The
Deds, Dedr, Pt1, Pt2, Pt3
functions in the control cannot be applied
Содержание UP-ECO
Страница 4: ...4 Italiano Montaggio del comando CB E A B A B CTRL CTRL C ...
Страница 8: ...8 Italiano Montaggio del comando CB Touch A B CTRL C CTRL B CTRL C CTRL A B ...
Страница 27: ...27 English Installation of the CB E control A B A B CTRL CTRL C ...
Страница 31: ...31 English Installation of the CB Touch control A B CTRL C CTRL B CTRL C CTRL A B ...
Страница 50: ...50 Français Montage de la commande CB E A B A B CTRL CTRL C ...
Страница 54: ...54 Français Montage de la commande CB Touch A B CTRL C CTRL B CTRL C CTRL A B ...
Страница 73: ...73 Deutsch Montage der CB E Steuerung A B A B CTRL CTRL C ...
Страница 77: ...77 Deutsch Montage der CB Touch Steuerung A B CTRL C CTRL B CTRL C CTRL A B ...
Страница 96: ...96 Español Montaje del mando CB E A B A B CTRL CTRL C ...
Страница 100: ...100 Español Montaje del mando CB Touch A B CTRL C CTRL B CTRL C CTRL A B ...