background image

10

THERMASGARD

®

  RTF xx   (diverse versions) 

Rev.  2020 - V24

Room temperature sensor 

THERMASGARD

®

  RTF xx

 with passive output, in an elegant housing made of plastic, with snap-on lid, base with 4-hole 

attachment for installation on vertically or horizontally installed in-wall flush boxes, with predetermined breaking point for on-wall cable entry, or in 
enclosures made of stainless steel (top and bottom part are of stainless steel, the lid is screwed on), vandal-proof version e.g. for schools, military 
barracks, and public buildings. This residential room temperature sensor is used to detect ⁄ display temperatures in closed dry rooms, in  
apartments, in cinemas, supermarkets, storage rooms, office and business facilities.  

TECHNICAL DATA

Measuring ranges: 

–30...+70 °C  (passive sensors) and 
   0...+50 °C  (for U-variant)

Sensor: 

for types, see table

Potentiometer: 

standard 1kΩ, max. 0.1 W  other ratings optional on request,  
e. g. 100 Ω, 2.5 kΩ, 5 kΩ, 10 kΩ, (optional potentiometer 0…10 V, linear),with angle of rotation limiter 

Turn switch: 

max. 24 V AC ⁄ DC, max. 130 mA, up to 5 steps (0, Auto, I, II, III),  with angle of rotation limiter 

Rocker switch:  

max. 24 V AC ⁄ DC, max. 130 mA

Push-buttons:  

normally open contact, max. 24 V DC, max. 10 mA

LEDs:  

max. 24 V DC (optional max. 24 V AC), 
standard green (optional red, yellow, or two-colour)

Housing: 

plastic, ABS, pure white (similar to RAL 9010),  
(optional stainless steel 

V2A

 (1.4301)

Dimensions: 

85  x  85 x  27 mm    (Baldur 1)    Standard 
98  x  98 x  33 mm    (Baldur 2) 
75  x  75 x  25 mm    (stainless  steel 

V2A

 (1.4301)

Installation: 

wall mounting or on in-wall flush box  Ø 55 mm, base with 4-hole for mounting on vertically or  
horizontally installed in-wall flush boxes for cable entry from the back, with predetermined breaking  
point for on-wall cable entry from top ⁄  bottom in case of plain on-wall installation 

Electrical connection: 

0.14 - 1.5 mm²  via terminal screws, on safety extra-low voltage max. 24 V DC only

Humidity: 

max. 90 % r. H., non-precipitating air

Protection class: 

III   (according to EN 60 730)

Protection type: 

IP 30  (according to EN 60 529)

Lettering: 

standard is swelling arrow with centre position, unfilled (optional special printing) 

THERMASGARD

®

 RTF 1       

Room temperature sensors 

Type ⁄ WG03

Sensor ⁄ Output

RTF1 xx

passive

IP 30   

(–30...+70 °C)

RTF PT100 ...

*

Pt100    (according to DIN EN 60 751, class B)

RTF PT1000 ...

*

Pt1000  (according to DIN EN 60 751, class B)

RTF NI1000 ...

*

Ni1000   (according to DIN EN 43 760, class B, TCR = 6180 ppm ⁄ K)

RTF NI1000TK5000 ...

*

Ni1000 TK5000  (TCR = 5000 ppm ⁄ K),  LG - Ni1000

RTF LM235Z ...

*

LM235Z  (TCR = 10 mV ⁄ K; 2.73 V at O °C),  KP10

RTF NTC1,8K ...

*

NTC  1.8 K

RTF NTC10K ...

*

NTC 10K

RTF NTC20K ...

*

NTC 20K

RTF - U  xx

passive ⁄ active

IP 30   

(0...+50 °C)

RTF-U PT1000 ...

*

Pt1000 / 0 - 10 V  (potentiometer)

RTM  P U

aktive  

Display IP 30   

(0...+50 °C)

RTM-U 

P

0 - 10 V  (temperature and potentiometer)

RTM-U U 

P

_DISPLAY

0 - 10 V  (temperature and potentiometer)

 

...

 =   Version

RTF xx T 

 

Version with sensor  

and pushbutton (max. 24 V DC, max. 10 mA)

RTF xx LT 

  Version with sensor,  

LED (green), and pushbutton (max. 24 V DC, max. 10 mA)

RTF xx PT

  Version with sensor, potentiometer (1 kOhm, max. 0.1 W),   

and pushbutton (max. 24 V DC, max. 10 mA)

RTF xx PLT

  Version with sensor, potentiometer (1 kOhm, max. 0.1 W),  

LED (green), and pushbutton (max. 24 V DC, max. 10 mA)

RTF xx PW

  Version with sensor, potentiometer (1 kOhm, max. 0.1 W),  

and rocker switch (max. 24 V AC/DC, max. 130 mA)

RTF xx PD

  Version with sensor, potentiometer (1 kOhm, max. 0.1 W),  

and turn switch (max. 24 V AC/DC, max. 130 mA)

RTF xx P

 

Version with sensor and potentiometer (1 kOhm, max. 0.1 W)

Содержание THERMASGARD RTF LM235Z Series

Страница 1: ...er und messumformer Aufputz G Operating Instructions Mounting Installation Room temperature sensors and measuring transducers on wall F Notice d instruction Sonde et convertisseur de temp rature d amb...

Страница 2: ...g Geh use Baldur 1 Dimensional drawing Housing Baldur 1 Plan cot bo tier Baldur 1 Baldur 1 Ma zeichnung Geh use Baldur 2 Dimensional drawing Housing Baldur 2 Plan cot bo tier Baldur 2 Baldur 2 T K 6 0...

Страница 3: ...r waagerecht installierten UP Dosen f r Kabeleinf hrung hinten mit Sollbruchstelle f r Kabeleinf hrung oben unten bei AP elektr Anschluss 0 14 1 5 mm ber Schraubklemmen nur an Sicherheitskleinspannung...

Страница 4: ...15 14 13 12 11 10 9 8 7 6 T1 Sollwert Offset THERMASGARD RTFxxT Ausf hrung mit F hler und Taster max 24 V DC max 10 mA Baldur 1 THERMASGARD RTFxxLT Ausf hrung mit F hler Leuchtdiode gr n und Taster m...

Страница 5: ...W Leuchtdiode gr n und Taster max 24 V DC max 10 mA Baldur 1 THERMASGARD RTFxxPW Ausf hrung mit F hler Potentiometer 1 kOhm max 0 1 W und Wippschalter max 24 V AC DC max 130 mA Baldur 1 THERMASGARD R...

Страница 6: ...isplay 1 2 3 18 17 16 P1 P2 4 5 S1 15 14 13 12 11 10 9 8 7 6 Sollwert Offset THERMASGARD RTFxxP RTFxxPU RTM U PU Ausf hrung mit F hler und Potentiometer 1 kOhm max 0 1 W 1 2 3 4 5 6 min max Korrektur...

Страница 7: ...eratursensor in einem entsprechenden Geh use eingebettet wobei das Geh use verschieden aufgebaut sein kann z B mit einer externen F hlerh lse siehe Au entemperaturf hler ATF2 Bei den Geh usef hlern wi...

Страница 8: ...d zu ber cksichtigen VDE VDI Technische Temperaturmessungen Richtlinie Mess an ord nungen f r Temperaturmessungen die EMV Richtlinien diese sind einzuhalten eine Parallelverlegung mit stromf hrenden L...

Страница 9: ...ogdarstellung sind nicht zus tzlich aufgef hrt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfalle...

Страница 10: ...installed in wall flush boxes for cable entry from the back with predetermined breaking point for on wall cable entry from top bottom in case of plain on wall installation Electrical connection 0 14 1...

Страница 11: ...0 mA Baldur 1 THERMASGARD RTFxxLT Version with sensor LED green and pushbutton max 24 V DC max 10 mA Baldur 1 THERMASGARD RTFxxPT Version with sensor potentiometer 1 kOhm max 0 1 W and pushbutton max...

Страница 12: ...RD RTFxxPW Version with sensor potentiometer 1 kOhm max 0 1 W and rocker switch max 24 V AC DC max 130 mA Baldur 1 THERMASGARD RTFxxPD Version with sensor potentiometer 1 kOhm max 0 1 W and turn switc...

Страница 13: ...P RTFxxPU RTM U PU Version with sensor and potentiometer 1 kOhm max 0 1 W Baldur 1 Baldur 1 Baldur 1 3 4 5 6 Rx 1 2 Output temperature 0 10V UB supply voltage 24V AC DC UB GND Output potentiometer 0 1...

Страница 14: ...plication On housing type sensors the temperature sensor is embedded in a respective housing Different designs of enclosures are available e g with an external sensor sleeve see outside temperature se...

Страница 15: ...regarded VDE VDI directive technical temperature measurements measurement set up for temperature measurements The EMC directives must be adhered to It is imperative to avoid parallel laying of curren...

Страница 16: ...re exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products In case of any...

Страница 17: ...r bo tes d encastrement mont es verticalement ou horizontalement pour passage de c ble par l arri re avec point de rupture pour passage de c ble par le haut bas pour montage en saillie Raccordement le...

Страница 18: ...Baldur 1 THERMASGARD RTFxxLT Mod le avec sonde diode lectroluminescente verte et bouton poussoir max 24 V cc max 10 mA Baldur 1 THERMASGARD RTFxxPT Mod le avec sonde potentiom tre 1 kOhm max 0 1 W et...

Страница 19: ...ur 1 THERMASGARD RTFxxPW Mod le avec sonde potentiom tre 1 kOhm max 0 1 W et interrupteur bascule max 24 V ca cc max 130 mA Baldur 1 THERMASGARD RTFxxPD Mod le avec sonde potentiom tre 1 kOhm max 0 1...

Страница 20: ...le avec sonde et potentiom tre 1 kOhm max 0 1 W Baldur 1 Baldur 1 Sch ma de raccordement RTM U PU Display 3 4 5 6 Rx 1 2 Output temperature 0 10V UB supply voltage 24V AC DC UB GND Output potentiomete...

Страница 21: ...un bo tier correspondant Mais il est possible que ce bo tier soit construit diff remment par ex avec une sonde chemis e externe voir sonde de temp rature ext rieure ATF2 Dans le cas des sondes sous f...

Страница 22: ...igueur pour le lieu de mesure par ex r gles de soudage etc Sont notamment consid rer Mesure technique de temp ratures selon VDE VDI directives ordonnances sur les instruments de mesure pour la mesure...

Страница 23: ...il sont applicables des diff rences par rapport la pr sentation dans le catalogue ne sont pas mentionn es explicitement et sont possibles suite au progr s technique et l am lioration continue de nos p...

Страница 24: ...70 C RTF PT100 Pt100 DIN EN 60 751 RTF PT1000 Pt1000 DIN EN 60 751 RTF NI1000 Ni1000 DIN EN 43 760 TCR 6180 1 K RTF NI1000TK5000 Ni1000 TK5000 TCR 5000 1 K LG Ni1000 RTF LM235Z LM235Z TCR 10 K 2 73 O...

Страница 25: ...FxxT 24 10 Baldur 1 THERMASGARD RTFxxLT 24 10 Baldur 1 THERMASGARD RTFxxPT 1 0 1 24 10 Baldur 1 1 2 3 18 17 16 4 5 S1 15 14 13 12 11 10 9 8 7 6 T1 1 2 3 18 17 16 4 5 S1 15 14 13 12 11 10 9 8 7 6 T1 LD...

Страница 26: ...ARD RTFxxPW 1 0 1 24 130 Baldur 1 THERMASGARD RTFxxPD 1 0 1 24 130 Baldur 2 1 2 3 18 17 16 P1 P2 4 5 S1 15 14 13 12 11 10 9 8 7 6 T1 LD1 setpoint offset 1 2 3 4 21 20 19 5 6 S1 1 2 3 0 15 16 17 18 14...

Страница 27: ...xPU RTM U PU 1 0 1 Baldur 1 Baldur 1 RTM U PU 3 4 5 6 Rx 1 2 Output temperature 0 10V UB supply voltage 24V AC DC UB GND Output potentiometer 0 10V 1 2 3 4 5 6 min max Korrektur T Potentio meter int S...

Страница 28: ...N EN 60 751 Pt 1000 DIN EN 60751 Ni 1000 DIN EN 43 760 TCR 6180 ppm K Ni 1000_TK5000 TCR 5000 ppm K LM235Z IC 10 K 2 73 C NTC DIN 44070 PTC KTY 0 100 C TK ATF2 FSTF RTF ATF G 10 x SS 02 r 70 C 105 C 1...

Страница 29: ...Imax Pt1000 0 6 A Pt100 1 0 A Ni1000 DIN Ni1000 TK5000 0 3 A NTC xx 2 LM235Z 400 A 5 A KTY 81 210 2 A 0 C Pt100 Pt1000 DIN EN 60751 0 3 K 1 3 DIN EN 60751 0 1 K NI1000 DIN EN 43760 0 4 K NI1000 1 2 D...

Страница 30: ...30 r ZVEI VDE EMV r...

Страница 31: ...date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are used und...

Страница 32: ...557 0 3431 3607 3830 110 120 146 1 1461 1760 1625 4 3552 3817 3930 120 130 149 8 1498 1833 3676 4008 130 140 153 6 1536 1909 3802 4166 140 150 157 3 1573 1987 3929 4280 150 NTC 1 8 kOhm NTC 2 2 kOhm N...

Отзывы: