General notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical 
and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to 
be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, 

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to 
prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed by authorised specialists only.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively 

valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous 
improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat 

 irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

THERMASGARD

® 

9111  (fieldbus input modules)

THERMASGARD

® 

9112  (fieldbus output modules)

Type ⁄ WG1 

Item No. 

Inputs 

Features

FB -16E - L 

1905-9111-1000-400 

16 digital 

with LEDs 

  

 

FB - 8AE 

1905-9111-2000-500 

8 analog 

for passive sensors 

 

 

 

Pt100,   Pt1000,   Ni1000,   Ni100TK5000

FB - 8AE - U 

1905-9111-2010-500 

8 analog 

active    0 -10 V 

  

 

FB - 8AE - I 

1905-9111-2020-500 

8 analog 

active  4...20 mA 

  

 

Type ⁄ WG1 

Item No. 

Outputs ⁄ Inputs 

Features

FB - 8AA - U 

1905-9112-0200-100 

8 analog out   

active    0 -10 V

FB - 8AA - U - H 

1905-9112-0201 -100 

8 analog out   

active    0 -10 V     

 

 

 

with manual operating level

FB - 8RA  

1905-9112-0300-100 

8 relay out   

normally open contacts

FB - 8RA - H 

1905-9112-0301 -100 

8 relay out    

normally open contacts 

 

 

 

with manual operating level

FB - 8RA - 4AE 

1905-9112-2300-300 

8 relay out  ⁄  

normally open contacts  ⁄ 

 

 

4 passive in 

Pt100,   Pt1000,   Ni1000,   Ni100TK5000

FB - 8RA - 4AE - H 

1905-9112-2301 -300 

8 relay out  ⁄ 

normally open contacts  ⁄ 

 

 

4 passive in 

Pt100,   Pt1000,   Ni1000,   Ni100TK5000 

 

 

 

with manual operating level

FB - 8RA - 4AE - U 

1905-9112-2310-300 

8 relay out  ⁄  

normally open contacts  ⁄ 

 

 

4 active in 

0 -10 V

FB - 8RA - 4AE - U - H 

1905-9112-2311 -300 

8 relay out  ⁄ 

normally open contacts  ⁄ 

 

 

4 active in 

0 -10 V 

  

 

with manual operating level

Содержание THERMASGARD 9112

Страница 1: ...ons Mounting Installation Fieldbus input modules and fieldbus output modules F Notice d instruction Modules d entr e bus de champ et modules de sortie bus de champ r Fieldbus THERMASGARD 9111 mit 8 an...

Страница 2: ...ncy operating level avec 8 sorties analogiques 0 10V commande manuelle et commande de secours 8 0 10B THERMASGARD 9112 mit 8 Relais Ausg ngen und Handbetrieb with 8 relay outputs and manual mode avec...

Страница 3: ...A Digital Ausgang Relais max 250 V AC 6A AC1 2A AC3 Analog Eingang passiv Pt100 Pt1000 Ni1000 Ni1000 LG 0 5 mA Analog Eingang aktiv 0 10V Ri 10k 0 20mA B rde 200 Analog Ausgang U 0 10V max 10mA je Aus...

Страница 4: ...egebenen Verwendungszweck zu nutzen dabei sind die entsprechenden Sicherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des T V und der rtlichen EVU zu beachten Der K ufer hat die Einhalt...

Страница 5: ...auf die Busleitung sendet ON ON 1 1 8 8 Rx Tx 0V sorgung 24V DC RS485 Busabschluss Bus adresse Busparameter Baudrate Datenbits RS485 Bus Konfiguration Die Position der DIP Schalter ist oben mittig Der...

Страница 6: ...s 1 bis 8 eingestellt werden ON ON 1 1 8 8 Rx Tx 0V orgung 24V DC RS485 Busabschluss Bus adresse Busparameter Baudrate Datenbits RS485 Bus ON ON 1 1 8 8 Rx Tx 0V orgung 24V DC RS485 Busabschluss Bus a...

Страница 7: ...bei ist es egal ob nur ein oder mehrere Eing nge gleichzeitig gelesen werden Digital Eingang read Discrete Inputs 0x02 Digital Ausgang Digitale Ausg nge werden als einzelne Bits im FB II Feldbussystem...

Страница 8: ...Ausgang Digitale Ausg nge werden als einzelne OUTPUT Bits im FB II Feldbussystem behandelt Dabei ist es egal ob nur ein oder mehrere Ausg nge gleichzeitig geschrieben oder gelesen werden Notbedienung...

Страница 9: ...ss Startadresse mit der das Beschreiben beginnen soll Die Anzahl der zu schreibenden Outputs wird durch ausziehen der F Box erreicht S Bus Output lesen Output lesen mit F Box Empfang Bin r Einstellung...

Страница 10: ...ister R 10 E 11 Holding Reg 11 Register R 11 E 12 Holding Reg 12 Register R 12 E 13 Holding Reg 13 Register R 13 E 14 Holding Reg 14 Register R 14 E 15 Holding Reg 15 Register R 15 16x digitaler Einga...

Страница 11: ...Register R 17 Ni1000 WI 2 Holding Reg 18 Register R 18 Ni1000 WI 3 Holding Reg 19 Register R 19 Ni1000 WI 4 Holding Reg 20 Register R 20 Ni1000 WI 5 Holding Reg 21 Register R 21 Ni1000 WI 6 Holding Re...

Страница 12: ...Register R 11 Ni1000 E 12 Holding Reg 12 Register R 12 Ni1000TK5000 E 13 Holding Reg 13 Register R 13 Ni1000TK5000 E 14 Holding Reg 14 Register R 14 Ni1000TK5000 E 15 Holding Reg 15 Register R 15 Ni1...

Страница 13: ...100 der Einheit angegeben z B Wert 250 im Ausgangsregister entspricht 2 5 V am Ausgang Lesezugriff Sollwert Modbus RTU SAIA S Bus Potentiometer read Register analog Holding Register read WO 0 Holding...

Страница 14: ...AC3 Analog input passive Pt100 Pt1000 Ni1000 Ni1000 LG 0 5 mA Analog input active 0 10V Ri 10k 0 20mA working resistance 200 Analog output U 0 10V max 10mA per each output Bus interface RS485 active g...

Страница 15: ...their heat flow Direct sun irradiation or heat irradiation by similar sources powerful lamps halogen spotlights must absolutely be avoided Operating this device close to other devices that do not comp...

Страница 16: ...g data to the bus line ON ON 1 1 8 8 Rx Tx 0V sorgung 24V DC RS485 Busabschluss Bus adresse Busparameter Baudrate Datenbits RS485 Bus Configuration The position of DIP switches is at the top centred T...

Страница 17: ...ght DIP switch positions 1 through 8 ON ON 1 1 8 8 Rx Tx 0V orgung 24V DC RS485 Busabschluss Bus adresse Busparameter Baudrate Datenbits RS485 Bus ON ON 1 1 8 8 Rx Tx 0V orgung 24V DC RS485 Busabschlu...

Страница 18: ...several inputs are read at the same time Digital input read Discrete Inputs 0x02 Digital output Digital outputs are treated as individual bits in the FB II fieldbus system Here it is immaterial whethe...

Страница 19: ...s are treated as individual OUTPUT bits in the FB II fieldbus system Here it is immaterial whether only one or several outputs are written or read at the same time Emergency operation switches Switche...

Страница 20: ...tination address Starting address writing should start wit The number of outputs to be written is obtained by extracting the FBox Reading S Bus Output Read Output using FBox Receive Binary Settings in...

Страница 21: ...10 Register R 10 E 11 Holding Reg 11 Register R 11 E 12 Holding Reg 12 Register R 12 E 13 Holding Reg 13 Register R 13 E 14 Holding Reg 14 Register R 14 E 15 Holding Reg 15 Register R 15 16x digital i...

Страница 22: ...gister R 17 Ni1000 WI 2 Holding Reg 18 Register R 18 Ni1000 WI 3 Holding Reg 19 Register R 19 Ni1000 WI 4 Holding Reg 20 Register R 20 Ni1000 WI 5 Holding Reg 21 Register R 21 Ni1000 WI 6 Holding Reg...

Страница 23: ...gister R 11 Ni1000 E 12 Holding Reg 12 Register R 12 Ni1000TK5000 E 13 Holding Reg 13 Register R 13 Ni1000TK5000 E 14 Holding Reg 14 Register R 14 Ni1000TK5000 E 15 Holding Reg 15 Register R 15 Ni1000...

Страница 24: ...indicated in 1 100 of a unit e g value 250 in the output register corresponds to 2 5V at the output Read access Setpoint Modbus RTU SAIA S Bus Potentiometer read Register Analog Holding Register read...

Страница 25: ...4V DC 500mA Sortie num rique relais max 250 V AC 6A AC1 2A AC3 Entr e analogique passive Pt100 Pt1000 Ni1000 Ni1000 LG 0 5 mA Entr e analogique active 0 10V Ri 10k 0 20mA charge 200 Sortie analogique...

Страница 26: ...s tre utilis proximit des sources de chaleur par ex radiateurs ou de leurs flux de chaleur il faut imp rativement viter un ensoleillement direct ou un rayonnement thermique provenant de sources simila...

Страница 27: ...des donn es sur la ligne de bus ON ON 1 1 8 8 Rx Tx 0V sorgung 24V DC RS485 Busabschluss Bus adresse Busparameter Baudrate Datenbits RS485 Bus Configuration Les interrupteurs DIP sont plac s en haut...

Страница 28: ...r DIP droit pos 1 8 ON ON 1 1 8 8 Rx Tx 0V orgung 24V DC RS485 Busabschluss Bus adresse Busparameter Baudrate Datenbits RS485 Bus ON ON 1 1 8 8 Rx Tx 0V orgung 24V DC RS485 Busabschluss Bus adresse Bu...

Страница 29: ...FB II Il est gal qu une seule ou plusieurs entr es soient lues en m me temps Entr e num rique read Discrete Inputs 0x02 Sortie num rique Les sorties num riques sont trait es comme des bits individuel...

Страница 30: ...e temps Sortie num rique Les sorties num riques sont trait es comme des SORTIES OUTPUT individuelles bits dans le syst me de bus de terrain FB II Ici il est gal qu une seule ou plusieurs sorties soien...

Страница 31: ...se de d part d o l criture doit commencer Le nombre des sorties crire est atteint par une extension de la F Box Lire sortie S Bus Lire sortie avec F Box R ception binaire R glages dans la F Box Initia...

Страница 32: ...0 Holding Reg 10 Register R 10 E 11 Holding Reg 11 Register R 11 E 12 Holding Reg 12 Register R 12 E 13 Holding Reg 13 Register R 13 E 14 Holding Reg 14 Register R 14 E 15 Holding Reg 15 Register R 15...

Страница 33: ...ing Reg 17 Register R 17 Ni1000 WI 2 Holding Reg 18 Register R 18 Ni1000 WI 3 Holding Reg 19 Register R 19 Ni1000 WI 4 Holding Reg 20 Register R 20 Ni1000 WI 5 Holding Reg 21 Register R 21 Ni1000 WI 6...

Страница 34: ...eg 10 Register R 11 Ni1000 E 12 Holding Reg 12 Register R 12 Ni1000TK5000 E 13 Holding Reg 13 Register R 13 Ni1000TK5000 E 14 Holding Reg 14 Register R 14 Ni1000TK5000 E 15 Holding Reg 15 Register R 1...

Страница 35: ...helle de 1 100 par ex valeur 250 dans le registrede sortie correspond 2 5V la sortie Acc s lecture Potentiom tre Modbus RTU SAIA S Bus valeur prescrite read Register analogique Holding Register read W...

Страница 36: ...9112 S Bus ModBus 24 24 5 24 V DC 24 500 250 6A AC1 2A AC3 Pt100 Pt1000 Ni1000 Ni1000 LG 0 5 0 10 Ri 10 0 20 200 O U 0 10 10 RS485 32 RS485 1200 YstY 2x08 CAT5 SAIA S Bus Parity Mode Data Mode 0 127 M...

Страница 37: ...8 0 10 FB 8AE I 1905 9111 2020 500 8 4 20 1 FB 8AA U 1905 9112 0200 100 8 0 10 FB 8AA U H 1905 9112 0201 100 8 0 10 FB 8RA 1905 9112 0300 100 8 FB 8RA H 1905 9112 0301 100 8 FB 8RA 4AE 1905 9112 2300...

Страница 38: ...drate Datenbits RS485 Bus DIP DIP RS485 Busabschluss offen Busabschluss geschlossen aktiviert Busabschluss offen Busabschluss geschlossen aktiviert DIP 8 ON ON 1 1 8 8 Rx Tx 0V orgung 24V DC RS485 Bus...

Страница 39: ...N 1 1 8 8 Rx Tx 0V orgung 24V DC RS485 Busabschluss Bus adresse Busparameter Baudrate Datenbits RS485 Bus ON ON 1 1 8 8 Rx Tx 0V orgung 24V DC RS485 Busabschluss Bus adresse Busparameter Baudrate Date...

Страница 40: ...Register 0x03 read Holding Register 0x03 write Single Register 0x06 write Multiple Register 0x17 FB II read Discrete Inputs 0x02 FB II write Single Coil 0x05 write Multiple Coil 0x0F read Coils 0x01 F...

Страница 41: ...0 10 0 20 1 100 6 7 670 11 25 1125 FB II FLAGS FB II OUTPUTS FB II FLAGS 0 10 ng 1 100 U 67 670 6 7 I 50 1000 10 SASI S Bus SASI S Bus Fupla F Box SASI F Box SASI S Bus Master F Box Cannel TS Delay 0...

Страница 42: ...on NO IP Node Profi S Bus Address 0 Destination station S Bus Destination element Output Destination address F Box S Bus F Box Empfang Bin r F Box Initialisation NO IP Node Profi S Bus Address 0 Sourc...

Страница 43: ...13 Register R 13 E 14 Holding Reg 14 Register R 14 E 15 Holding Reg 15 Register R 15 16 0 Modbus RTU SAIA S Bus read write Register Holding Register read write E 0 Holding Reg 16 Register R 16 E 1 Ho...

Страница 44: ...lding Reg 18 Register R 18 Ni1000 WI 3 Holding Reg 19 Register R 19 Ni1000 WI 4 Holding Reg 20 Register R 20 Ni1000 WI 5 Holding Reg 21 Register R 21 Ni1000 WI 6 Holding Reg 22 Register R 22 Ni1000 WI...

Страница 45: ...R 11 Ni1000 E 12 Holding Reg 12 Register R 12 Ni1000TK5000 E 13 Holding Reg 13 Register R 13 Ni1000TK5000 E 14 Holding Reg 14 Register R 14 Ni1000TK5000 E 15 Holding Reg 15 Register R 15 Ni1000TK5000...

Страница 46: ...ter Holding Register read WO 0 Holding Reg 8 Register R 8 WO 1 Holding Reg 9 Register R 9 WO 2 Holding Reg 10 Register R 10 WO 3 Holding Reg 11 Register R 11 WO 4 Holding Reg 12 Register R 12 WO 5 Hol...

Страница 47: ...V W0 4 0 10 V GND 0 V W0 5 0 10 V GND 0 V W0 6 0 10 V GND 0 V W0 7 0 10 V GND 0 V Rx Tx Pwr A0 A1 A2 A3 A4 A5 A6 A7 WI 0 WI 1 WI 2 WI 3 WI 4 WI 5 WI 6 WI 7 Rx Tx Pwr A0 A1 A2 A3 A4 A5 A6 A7 A0 A1 A2...

Страница 48: ...E05 E06 E07 E08 E09 E10 E11 E12 E13 E14 E15 24V DC 0 V E00 E01 E02 E03 E04 E05 E06 E07 E08 E09 E10 E11 E12 E13 E14 E15 Rx Tx Pwr A0 A1 A2 A3 A4 A5 A6 A7 A0 A1 A2 A3 A4 A5 A6 A7 W0 3 W0 2 W0 1 W0 0 Pt...

Отзывы: