Installation and Commissioning

FUNCTION 

The supplied probe with the electronic sensor is firmly connected (see also connection diagram on housing side) to the top-hat rail 
housing via a connection cable (KL = approx. 2.4 m).
The measuring transducer compares the air velocity at the sensor with the set threshold at the potentiometer (0.1…20 m/s).  
The changeover contact closes when the threshold is reached or exceeded.  
The integrated start-up override ensures trouble-free start-up (e.g. of the fan) and thus avoids unwanted fault messages (BMS).

START-UP OVERRIDE 

There are application scenarios in which fan motors and measuring instruments are switched off and on again.  
When switched on, the fans take a few seconds to build up a flow.  
During this start-up time, the BMS could switch to fault mode (lack of flow). 
For this reason, a start-up override of 60 s is permanently programmed into all unit types.
After the supply voltage is switched on, a flow of 20 m/s or greater than the set switching threshold during this 
start-up time is assumed and the output signal is increased to 10 V or the relay is switched, depending on the type. 
After the start-up time has elapsed, the unit switches to normal measuring mode.  

SWITCHING POINT 

The switching point (0.1…20 m/s) for the changeover contact is set  
via a potentiometer on the front of the housing.

LED STATUS INDICATOR

The current switching status of the changeover contact/relay and the operating 
status of the unit is indicated via two LEDs on the front of the housing.

YELLOW LED  

“Relay” (switching status):

 

Off

 

= Switching point not reached → Contact 5-6 open 

Continuous light

  = Switching point reached → Contact 5-6 closed 

Flashing

 

= Start-up override active 

GREEN LED  

“On ⁄Off” (operating status):

 

Continuous light

  = Readiness for operation of the measuring transducer 

Flashing

 

= Error in sensor or sensor line

Connecting diagram  

KHSSF-W 

Connecting diagram  

KHSSW-W24 

Connecting diagram  

KHSSW-W230

Содержание RHEASGARD KHSSF

Страница 1: ...ternal flow probe incl mounting flange with active switching output F Notice d instruction Capteur de d bit d air sur profil s chapeau pour montage en gaine contr leur de d bit d air lectronique sonde...

Страница 2: ...Ma zeichnung Dimensional drawing Plan cot mm 44 45 65 25 max 155 12 20 KL 5 8 44 max 155 12 20 KL 5 8 Relay On Off 1 10 5 15 20 m s 1 2 3 4 5 6 7 8 9 10 11 12 48 33 58 90 2 36 5 Relay On Off 1 10 5 15...

Страница 3: ...W24 Wechselkontakt 24 V max 5 A cos 1 Schalthysterese 2 EW Schwellwert ber Potentiometer einstellbar KHSSW W230 Wechselkontakt 230V AC max 10 A cos 1 Schalthysterese 2 EW Schwellwert ber Potentiometer...

Страница 4: ...g aktiv Ausgang schaltend Art Nr KHSSF AOS KHSSF W 24 V AC DC 0 10 V 4 20 mA 1 Wechsler 1701 5118 0102 001 KHSSW KHSSW W24 24 V AC DC 1 Wechsler 1701 5113 0102 001 KHSSW W230 230V AC 1 Wechsler 1701 5...

Страница 5: ...tetypen eine Anlauf berbr ckung von 60 s fest einprogrammiert Nach Zuschalten der Versorgungsspannung wird w hrend dieser Anlaufzeit eine Str mung von 20 m s bzw gr er als die eingestellte Schaltschwe...

Страница 6: ...ollte nicht mehr als 100 m betragen eine Verpolung der Anschl sse kann zu Besch digungen am Ger t und oder anderen Ger ten am Leitungsstrang f hren Der Einbau hat unter Beachtung der bereinstimmung de...

Страница 7: ...darf nicht f r berwachungszwecke welche dem Schutz von Personen gegen Gef hrdung oder Verletzung dienen und nicht als Not Aus Schalter an Anlagen und Maschinen oder vergleichbare sicherheitsrelevante...

Страница 8: ...W230 230 V AC changeover contact max 10 A cos 1 a switching hysteresis of 2 final value threshold can be adjusted via potentiometer Data point flow velocity m s Sensor calorimetric temperature compens...

Страница 9: ...A 1 changeover contact 1701 5118 0102 001 KHSSW KHSSW W24 24 V AC DC 1 changeover contact 1701 5113 0102 001 KHSSW W230 230V AC 1 changeover contact 1701 5133 0102 001 Note Changeover contact with aut...

Страница 10: ...nently programmed into all unit types After the supply voltage is switched on a flow of 20 m s or greater than the set switching threshold during this start up time is assumed and the output signal is...

Страница 11: ...nd BMS should not exceed 100 m Reversing the polarity of the connections can cause damage to the unit and or other units on the wiring harness Before installation make sure that the existing technical...

Страница 12: ...monitoring applications which serve the purpose of protecting persons against hazards or injury or as an EMERGENCY STOP switch for systems or machinery or for any other similar safety relevant purpos...

Страница 13: ...glable par potentiom tre KHSSW W24 Contact inverseur 24 V max 5 A cos 1 hyst r sis de commutation 2 Vf valeur seuil r glable par potentiom tre KHSSW W230 Contact inverseur 230 V CA max 10 A cos 1 hys...

Страница 14: ...ce KHSSF AOS KHSSF W 24 V CA CC 0 10 V 4 20 mA 1 inverseur 1701 5118 0102 001 KHSSW KHSSW W24 24 V CA CC 1 inverseur 1701 5113 0102 001 KHSSW W230 230V CA 1 inverseur 1701 5133 0102 001 Remarque Conta...

Страница 15: ...quelle un pontage au d marrage de 60 s est programm de mani re fixe dans tous les types d appareils Apr s la mise en marche de la tension d alimentation un d bit de 20 m s ou sup rieur au seuil de com...

Страница 16: ...ble entre la sonde et la gestion technique de b timent ne doit pas d passer 100 m L inversion de la polarit des connexions peut endommager l appareil et ou d autres appareils sur le faisceau de c bles...

Страница 17: ...mode de fonctionnement Cet appareil ne devra pas tre utilis des fins de surveillance qui visent la protection des personnes contre les dangers ou les blessures ni comme interrupteur d arr t d urgence...

Страница 18: ...3 KHSSF W 0 10 4 20 Automatic Output Switching U I 24 5 cos 1 2 KHSSW W24 24 5 cos 1 2 KHSSW W230 230 10 cos 1 2 0 1 20 0 5 3 0 5 1 0 2 0 2 60 60 c 10 20 5 6 5 6 PC ABS UL94 V0 36 2TE 35 90 36 58 PA6...

Страница 19: ...RD KHSSF RHEASREG KHSSW WG01 KHSSF AOS KHSSF W 24 0 10 4 20 1 1701 5118 0102 001 KHSSW KHSSW W24 24 1 1701 5113 0102 001 KHSSW W230 230 1 1701 5133 0102 001 AOS Automatic Output Switching DE 10 2015 0...

Страница 20: ...20 r 2 4 0 1 20 60 20 10 0 1 20 5 6 5 6 KHSSF W KHSSW W24 KHSSW W230...

Страница 21: ...21 r 5x d 3x d d KHSSF xx KHSSW xx VDE VDI 100 0 5 5 d 3 d DIN 43763 S S...

Страница 22: ...22 ZVEI VDE EMV r 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND...

Страница 23: ...the faultless quality of our products as stated in our General Terms and Conditions Sous r serve d erreurs et de modifications techniques Toutes les informations correspondent l tat de nos connaissanc...

Страница 24: ...KHSSF W GND UB OUT Schaltbild Schematic diagram Sch ma de connexion KHSSW W230 Schaltbild Schematic diagram Sch ma de connexion KHSSW W24 1 2 3 4 5 6 7 8 9 10 11 12 Sensor GND black IN green UB red Re...

Отзывы: