Offset adjustment is done at a potentiometer on the circuit board within  
an adjustment range of ± 10 % of the device’s pressure range. 

Ex-factory this potentiometer is in center position and is lacquer sealed. 

All settings and adjustments that are made before must be done in this 
configuration. 

Offset adjustment is carried out using a tool called “screwdriver 2.5”  
(blade with in mm). 

Automatic offset setting

1.

  Before setting the zero point, the device must be in operation  

for at least 60 minutes.  

2.

  Connect pressure inputs P (+) and P (–) by means of a hose  

(pressure difference between both inputs = 0 Pa). 

3.

  For zero point setting press 

"key"

 (auto zero)

 pushbutton 

 

uninterruptedly for 5 seconds.   

A LED signalises prompting the calibration by short flashing,  
and after a short countdown the measured (current) offset value is  
added to the measurand and zero voltage safe stored. 

Correct calibration is confirmed by steady light of the LED for  
3 seconds respectively indicated in the display (optional) by switching  
from “AUTO 0” to “PROG 0”. 

Note: By releasing the button during the countdown (counter > 0),  
zero point setting is immediately terminated! 

Manual offset adjustment

At the potentiometer OFFSET ∆P can be balanced.  
The adjustment range is ca. ± 10  % of the pressure range.  
Here another reference point different from zero point can be used. 

Readout in the display

In the 1st line of the display, the 

ACTUAL pressure

 up to the measuring range  

limit is displayed. 

Switching between the units Pa and hPa (100 Pa = 1 hP) happens automatically.   

Pa

  =  Pascal 

hP

  =  Hektopascal

The following configurations can be preset via 

DIP switches. 

The DIP switch sliding blocks can be moved 

without using tools. DIP switch 6 is not assigned. 

Pressure ranges 

In each case four different pressure ranges 

depending on the type of device can be preset 

via DIP switches 

DIP 1

 and 

DIP 2

.

Measuring range mode

The measuring range is configured via DIP 

switch 

DIP 3

, either into the unidirectional range 

or into the bidirectional range. 

Therefore altogether eight pressure measuring 

ranges are configurable.

Characteristic line – analog output

The output characteristic line can be defined via 

DIP switch 

DIP 4

. Here is distinguished between 

a linear and a square root extracting output 

characteristic line. When square root extracting 

output characteristic line is selected, the 

measuring range setting at DIP switches 

DIP 1

 

and 

DIP 2

 is without function. 

In that case the maximum pressure range is 

used for computation.  

Measurement signal filtering

In order to stabilize the pressure measurement 

signal and the  output voltage, the measurement 

signal is filtered. 

The time interval for such averaging can be 

preset via DIP switch 

DIP 5

 to 1 or 10 seconds. 

By a longer filtering interval, the settling time of 

the sensor is automatically extended. 

G  

PREM

ASGARD

®

  211x 

 212x 

 212x - SD

  |  Configuration and zero point calibration

Содержание PREMASGARD 211 Series

Страница 1: ...g connection set compact form adjustable calibratable with multi range switching and active output F Notice d instruction Convertisseur de pression et de pression diff rentielle y compris kit de racco...

Страница 2: ...eichnung Dimensional drawing Plan cot ohne Display without display sin cran ohne Display without display sin cran mit Display with display avec cran mit Display with display avec cran 39 49 4 3 15 6 1...

Страница 3: ...ture 20 50 C temperature compensated 0 50 C Pressure connection with connection nozzles for pressure hose 6 mm Type of pressure differential pressure Medium clean air and other non aggressive non comb...

Страница 4: ...D 2125 LCD 0 10 V 4 20 mA 1301 11A7 2050 000 max 100 100 Pa PREMASGARD 2120 IP 67 0 50 Pa 50 50 Pa 0 100 Pa 100 100 Pa PREMASGARD 2120 0 10 V 4 20 mA 1301 11A7 0110 000 PREMASGARD 2120 LCD 0 10 V 4 20...

Страница 5: ...a 110 Pa TYPES OF MONITORING Pressure connections at the pressure switch are marked with P1 for higher pressure and P2 for lower pressure A Below atmospheric pressure P1 is not connected but open to t...

Страница 6: ...ecting diagram PREMASGARD 211x PREMASGARD 212x PREMASGARD 212x SD 1 2 3 230V AC 24V AC DC PLC PC UB 24 V AC DC UB AC DC GND Output pressure Pa DIP switches for pressure range setting output attenuatio...

Страница 7: ...t in the display In the 1st line of the display the ACTUAL pressure up to the measuring range limit is displayed Switching between the units Pa and hPa 100 Pa 1 hP happens automatically Pa Pascal hP H...

Страница 8: ...right stop Offset 10 Original characteristic line Offset 0 Control knob in central position default Displacement of characteristic line by control knob left stop Offset 10 zero point offset 100 of mea...

Страница 9: ...ing instructions delivered together with the device are exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and...

Страница 10: ...r control their particular suitability must be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated...

Страница 11: ...DAL 01 Dimensional drawing Plan cot ASD 06 Anschluss Set Connection set Kit de raccordement Ma zeichnung ASD 06 Dimensional drawing Plan cot ASD 07 Anschlussnippel Connection nipple Embouts de raccor...

Отзывы: