background image

16

G  

General notes

–  This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor 

 element. 

–  On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure.  

In case of pollution  ⁄  contamination, this filter should be cleaned on a regular basis.

–  Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by using compressed air. 
–  Touching the humidity element is under any circumstances to be avoided, as that would result in considerable mismeasurements.
–  In case of pollution, we recommend cleaning and recalibration in the factory.
–  In any case, the sensor must not get in contact with chemicals or other cleaning agents.
–  The relative humidity of 0 ...100 % is indicated by an output signal of 0 -10 V or 4 ... 20 mA. The device operating range covers 10.0 ... 99.9 % r. H. 

Outside of that range, mismeasurements or increased deviations may occur.

–  When several sensors (0  -10 V) are connected to one voltage supply of 24 V  AC, correct polarity must be regarded as otherwise the  alternating 

 voltage source may be short-circuited. 

–  The voltage outputs are short-circuit proof. Applying overvoltage or voltage supply to the voltage output will destroy the device.
–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
 Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by 

voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be 
observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities,  

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to 
prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

 Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous  
improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation 

by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing 
an initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel!  
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

Содержание HYGRASGARD RFF Series

Страница 1: ...er 2 Aufputz kalibrierf hig mit aktivem passivem Ausgang G Operating Instructions Mounting Installation Room humidity and temperature sensors 2 on wall calibratable with active passive output F Notice...

Страница 2: ...2 HYGRASGARD RFF HYGRASGARD RFTF D G F r Ma zeichnung Dimensional drawing Plan cot RFF RFTF T K 6 0 85 85 27 2...

Страница 3: ...hm Ub 14 V 0 02 A bei I Variante Lastwiderstand RL 5 kOhm bei U Variante Leistungsaufnahme 1 1 VA 24 V DC 2 2 VA 24 V AC Sensoren digitaler Feuchtesensor mit integriertem Temperatursensor kleine Hyste...

Страница 4: ...41A1 1200 000 HYGRASGARD RFTF U xx Raum Feuchte und Temperaturf hler Typ WG01 Messbereich Anzeige Feuchte Temperatur Ausgang Feuchte Temperatur Art Nr Baldur 1 RFTF U xx Pt Ni LM235Z aktiv passiv RFTF...

Страница 5: ...4 0 5 0 5 4 8 10 1 0 5 6 15 1 5 6 4 20 2 0 7 2 25 2 5 8 0 30 3 0 8 8 35 3 5 9 6 40 4 0 10 4 45 4 5 11 2 50 5 0 12 0 55 5 5 12 8 60 6 0 13 6 65 6 5 14 4 70 7 0 15 2 75 7 5 16 0 80 8 0 16 8 85 8 5 17 6...

Страница 6: ...sgang Feuchte 0 10V in r H UB 24V AC DC 1 2 3 4 UB GND optional f r Hintergrundbeleuchtung frei Ausgang Feuchte 4 20mA in r H UB 24V DC 1 2 3 4 Ausgang Temperatur 4 20mA in C Ausgang Feuchte 4 20mA in...

Страница 7: ...ohne Display 0 10 V Anschlussbild RFTF I Ausgang mit ohne Display 4 20 mA D HYGRASGARD RFF RFTF Rev 2020 V23 1 2 3 4 230V AC 24V AC DC SPS PC UB 24V AC DC Ausgang Feuchte 0 10V in r H Ausgang Tempera...

Страница 8: ...gsspannung ge messen Wird dieses Ger t mit DC Versorgungsspannung betrieben ist der Be triebsspannungseingang UB f r 15 36 V DC Einspeisung und UB bzw GND als Masseleitung zu verwenden Werden mehrere...

Страница 9: ...Dieses Ger t ist nur f r den angegebenen Verwendungszweck zu nutzen dabei sind die entsprechenden Sicherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des T V und der rtlichen EVU zu bea...

Страница 10: ...kOhm for U variant Power consumption 1 1 VA 24 V DC 2 2 VA 24 V AC Sensors digital humidity sensor with integrated temperature sensor small hysteresis high long term stability HUMIDITY Measuring rang...

Страница 11: ...1A1 1200 000 HYGRASGARD RFTF U xx Room humidity and temperature sensors Type WG01 Measuring Range Readout Humidity Temperature Output Humidity Temperature Item No Baldur 1 RFTF U xx Pt Ni LM235Z activ...

Страница 12: ...5 2 75 7 5 16 0 80 8 0 16 8 85 8 5 17 6 90 9 0 18 4 95 9 5 19 2 100 10 0 20 0 Temperature table MR 0 50 C C UA in V IA in mA 0 0 0 4 0 5 1 0 5 6 10 2 0 7 2 15 3 0 8 8 20 4 0 10 4 25 5 0 12 0 30 6 0 13...

Страница 13: ...n C 0 10V Output humidity in r H 0 10V UB 24V AC DC 1 2 3 4 UB GND optional for backlighting Free Output humidity in r H 4 20mA UB 24V DC 1 2 3 4 Output temperature in C 4 20mA Output humidity in r H...

Страница 14: ...diagram RFTF U Output with without Display 0 10 V Connecting diagram RFTF I Output with without Display 4 20 mA 1 2 3 4 230V AC 24V AC DC PLC PC UB 24V AC DC Output humidity in r H 0 10V Output temper...

Страница 15: ...llows operating 0 10 V devices on AC supply voltage The output signal is to be tapped by a measuring instrument Output voltage is measured her against zero potential O V of the input voltage When this...

Страница 16: ...avoided and EMC directives are to be observed This device shall only be used for its intended purpose Respective safety regulations issued by the VDE the states their control authorities the T V and t...

Страница 17: ...tabilis es 0 3 V Charge Ra Ohm Ub 14 V 0 02 A pour variante I R sistance de charge RL 5 kOhm pour variante U Consommation lectrique 1 1 VA 24 V cc 2 2 VA 24 V ca Capteurs capteur d humidit num rique a...

Страница 18: ...1200 000 HYGRASGARD RFTF U xx Sonde d humidit et de temp rature d ambiance Type WG01 plage de mesure affichage humidit temp rature sortie humidit temp rature r f rence Baldur 1 RFTF U xx Pt Ni LM235Z...

Страница 19: ...85 8 5 17 6 90 9 0 18 4 95 9 5 19 2 100 10 0 20 0 Tableau de temp rature plage de mesure 0 50 C C UA en V IA en mA 0 0 0 4 0 5 1 0 5 6 10 2 0 7 2 15 3 0 8 8 20 4 0 10 4 25 5 0 12 0 30 6 0 13 6 35 7 0...

Страница 20: ...put humidity in r H 0 10V UB 24V AC DC 1 2 3 4 UB GND optional for backlighting Free Output humidity in r H 4 20mA UB 24V DC 1 2 3 4 Output temperature in C 4 20mA Output humidity in r H 4 20mA UB 24V...

Страница 21: ...accordement RFTF U Sortie avec sans cran 0 10 V Sch ma de raccordement RFTF I Sortie avec sans cran 4 20 mA 1 2 3 4 230V AC 24V AC DC PLC PC UB 24V AC DC Output humidity in r H 0 10V Output temperatur...

Страница 22: ...esur e par rapport au potentiel z ro O V de la tension d entr e Si cet appareil est aliment en courant continu il faut utiliser l entr e de tension de service UB pour l alimentation en 15 36 V cc et U...

Страница 23: ...l le avec des c bles de puissance les directives CEM sont respecter Cet appareil ne doit tre utilis que pour l usage qui est indiqu en respectant les r gles de s curit correspondantes de la VDE des L...

Страница 24: ...0 3 Ra Ub 14 0 02 I RL 5 U 1 1 24 2 2 24 0 100 0 10 B 4 20 0 95 2 0 20 80 25 C 3 0 0 10 B U 4 20 I 800 0 50 C 0 10 B 4 20 0 50 C 0 2 K 25 C 0 10 B 4 20 25 50 C 5 55 C 0 14 1 5 ABS RAL 9010 85 x 85 x 2...

Страница 25: ...LAY 0 100 0 50 C 0 10 0 10 1201 41A1 1200 000 HYGRASGARD RFTF U xx WG01 Baldur 1 RFTF U xx Pt Ni LM235Z RFTF U PT100 0 100 0 50 C 0 10 0 10 Pt100 1201 41A1 2001 000 RFTF U PT1000 0 100 0 50 C 0 10 0 1...

Страница 26: ...8 35 3 5 9 6 40 4 0 10 4 45 4 5 11 2 50 5 0 12 0 55 5 5 12 8 60 6 0 13 6 65 6 5 14 4 70 7 0 15 2 75 7 5 16 0 80 8 0 16 8 85 8 5 17 6 90 9 0 18 4 95 9 5 19 2 100 10 0 20 0 0 50 C C UA B IA A 0 0 0 4 0...

Страница 27: ...midity in r H 0 10V UB 24V AC DC 1 2 3 4 UB GND optional for backlighting Free Output humidity in r H 4 20mA UB 24V DC 1 2 3 4 Output temperature in C 4 20mA Output humidity in r H 4 20mA UB 24V DC UB...

Страница 28: ...RFTF I 4 20 A 1 2 3 4 230V AC 24V AC DC PLC PC UB 24V AC DC Output humidity in r H 0 10V Output temperature in C 0 10V UB GND 1 2 3 4 230V AC 24V DC UB 24V DC Output humidity in r H 4 20mA Output tem...

Страница 29: ...5 20 25 30 35 36 40 Load resistance diagram Working resistance Ohm Operating voltage V DC Admissible range 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0...

Страница 30: ...30 r 0 100 0 10 4 20 10 0 99 9 0 10 24 ZVEI VDE EMV...

Страница 31: ...control their particular suitability must be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated i...

Страница 32: ...orne ziehen und halten To open the housing set a screwdriver 2 0 in the groove at centre press down and lift up the bottom frame slightly Pull top cover for ward and hold it Pour ouvrir le bo tier pla...

Отзывы: