19
4
5
6
1 2 3
SET REL.
OFFSET
ZERO
CO² CO²
VOC
VOC
r.H.
°C
12
11
13
1 2 3 4 5 6 7 8 9
ON
DIP
ON
ON
VOC
CO² Mode
NC
= Normally Closed
COM
= Common
NO
= Normally Open
Plug for
display
humidity in % r.H.
air quality (VOC)
Outputs
temperature in °C
–UB GND
+UB 24
V A
C/DC
Output CO
²
in ppm
VOC
sensor
Reset
button
NC
COM
NO
relay
switch
point
4
5
6
1 2 3
ZERO
CO²
free
free
Outputs
temperature in °C
–UB GND
+UB 2
4V A
C/DC
Output CO
²
in ppm
Reset
button
F
AERASGARD
®
RCO2 - W ⁄ RLQ - CO2 - W ⁄ RFTM - LQ - CO2 - W ⁄ RTM - CO2 - SD
Rev. 2021 - V31
Schéma de raccordement
RFTM - LQ
- CO2 - W
Schéma de raccordement
RTM - CO2 - SD
Interrupteur DIP (Baldur 2)
RFTM - LQ
- CO2 - W
Sensibilité COV
DIP 1 DIP 2
LOW
OFF
OFF
MEDIUM (default)
O N
OFF
HIGH
OFF
O N
IAQ
(Indoor Air Quality)
O N
O N
Teneur en CO2
DIP 4
0...2000 ppm (default)
OFF
0...5000 ppm
O N
Étalonnage automatique CO2
DIP 6
désactivé
OFF
activé (default)
O N
Affectation relais
DIP 7 DIP 8
CO2 (default) : 600...1900 ppm / 900...4700 ppm
OFF
OFF
COV :
10...95 %
O N
OFF
Température : +5...+48 °C
OFF
O N
Humidité :
10...95% r.H.
O N
O N
Sortie
DIP 9
Tension 0 -10 V (default)
OFF
Courant 4...20 mA
O N
Remarque :
DIP 3
e
DIP 5
ne sont pas affectés !
Niveau IAQ
(Indoor Air Quality)
COV
1
Très bonne
0
...
19
%
aucune mesure nécessaire
2
bonne
20
...
39
%
aération recommandée prochainement
3
moyenne
40
...
59
%
aération recommandée
4
mauvaise
60
...
79
%
aération prolongée nécessaire
5
Très mauvaise
80
...
100
%
aération intensive indispensable
Tableau conforme aux directives COVT du Ministère fédéral de
l’Environnement pour l’évaluation du niveau de contamination de
l’air intérieur
(Journal du Ministère fédéral de la santé - Recherche en santé -
Protection de la santé 2007, 50: 990–1005)