General notes

–  This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor  element. 
–  Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by using compressed air. 
–  In case of pollution, we recommend cleaning and recalibration in the factory.
–  In any case, the sensor must not get in contact with chemicals or other cleaning agents.
–  Extremely high concentrations of VOCs, aggressive cleaning agents or silicone-containing vapours can destroy the sensor element or  

reduce its service life drastically.

–  The air quality signal “good“...“bad“ is represented by the output signal 0 -10 V or 4...20 mA.
–  The device operating range covers 10 ... 95 % relative humidity respectively 0 ...+50 °C. 

Beyond that range, mismeasurements or increased deviations will occur. 

–  The chemical sensor is a consumable. The lifetime of the sensor depends on nature and concentration of the pollutant gas burden.
–  When several sensors are connected to one voltage supply of 24 V  AC, correct polarity must be regarded as otherwise the  alternating  voltage source 

may be short-circuited. 

–  The outputs are short-circuit proof. Applying overvoltage or voltage supply to the output will destroy the device.
–  If the automatic system (automatic balancing of CO2 / VOC measurand) is activated, a cyclical fresh air supply must be provided,  

as otherwise incorrect measurements can occur.

–  The device must be permanently energized to measure the CO2 and VOC concentration correctly.
–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV and 

the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations 

from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.  

Direct sun irradiation or heat  irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of housings or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an 
initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel!  
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

Notes regarding mechanical mounting and attachment:

Mounting shall take place while observing all relevant regulations and standards applicable for the place of measurement (e.g. such as welding instructions, 
etc.). Particularly the following shall be regarded:

–  VDE ⁄ VDI directive technical temperature measurements, measurement set - up for temperature measurements.
–  The EMC directives must be adhered to.
–  It is imperative to avoid parallel laying of current-carrying lines.
–  We recommend to use shielded cables with the shielding being attached at one side to the DDC ⁄ PLC. 

Before mounting, make sure that the measuring device technical parameters comply with the actual conditions at the place of utilization, in particular in 
respect of:
–  Measuring range
–  Permissible maximum temperature and humidity
–  Protection type and Protection class
–  Oscillations, vibrations, shocks are to be avoided (< 0.5 g)

Содержание AERASGARD RCO2-W

Страница 1: ...and CO2 content calibratable with active switching output F Notice d instruction Sonde d ambiance transmetteur multifonctionnelle pour l humidit la temp rature la qualit d air COV et de teneur en CO2...

Страница 2: ...CO2 SD D G F r Ma zeichnung Geh use Baldur2 Dimensional drawing Housing Baldur2 Plan cot bo tier Baldur2 Baldur2 Ma zeichnung Edelstahlgeh use Dimensional drawing Stainless steel housing Plan cot Bo t...

Страница 3: ...0 mA RLQ CO2 W RFTM LQ CO2 W 4 4 W 24 V DC typisch 6 4 VA 24 V AC typisch Peakstrom 200 mA Ausg nge RTM CO2 SD 0 10 V fest eingestellt Rxx CO2 W 0 10 V oder 4 20 mA B rde 800 ber DIP Schalter w hlbar...

Страница 4: ...CO2 W Raum Luftqualit ts VOC und CO2 F hler Premium AERASGARD RFTM CO2 W Multifunktionaler Raumf hler f r Feuchte Temperatur und CO2 Gehalt Deluxe AERASGARD RFTM LQ CO2 W Multifunktionaler Raumf hler...

Страница 5: ...oor Air Quality ON ON CO2 Gehalt DIP 4 0 2000 ppm default OFF 0 5000 ppm ON CO2 autom Kalibrierung DIP 6 deaktiviert OFF aktiviert default ON Relais Zuordnung DIP 7 DIP 8 CO2 default 600 1900 ppm 900...

Страница 6: ...icher Luft qualit ten zu erm glichen m ssen die Ger te entsprechend den Bedingungen vor Ort welche nicht dem Definitionsbereich und damit nicht der werksseitigen Kalibrierung entsprechen vom Kunden ei...

Страница 7: ...ganischen Substanzen so gut wie m glich unterbinden Fenster ffnen bzw L ftungsanlage auf Au enluft einstellen Geh usedeckel abnehmen und 15 Minuten warten 2 Den ZERO VOC Taster gedr ckt halten bis die...

Страница 8: ...er t abzugreifen Hierbei wird die Ausgangssignal gegen das Nullpotenial O V der Eingangsspannung ge messen Wird dieses Ger t mit DC Versorgungsspannung betrieben ist der Betriebsspannungseingang UB f...

Страница 9: ...rdungen aller Art zu vermeiden F r M ngel und Sch den die durch unsachgem e Verwendung dieses Ger tes entstehen werden keinerlei Gew hrleistungen und Haftungen bernommen Folgesch den welche durch Fehl...

Страница 10: ...V DC typical 6 4 VA 24 V AC typical peak current 200 mA Outputs RTM CO2 SD 0 10 V fixed Rxx CO2 W 0 10 V or 4 20 mA working resistance 800 selectable via DIP switches selected variant applies for all...

Страница 11: ...and CO2 sensor Standard AERASGARD RCO2 W Room CO2 sensor Premium AERASGARD RLQ CO2 W Room air quality VOC and CO2 sensor Premium AERASGARD RFTM CO2 W Multifunctional room sensor for humidity temperatu...

Страница 12: ...IAQ Indoor Air Quality ON ON CO2 content DIP 4 0 2000 ppm default OFF 0 5000 ppm ON CO2 autom calibration DIP 6 deactivated OFF activated default ON Relay assignment DIP 7 DIP 8 CO2 default 600 1900 p...

Страница 13: ...n of different air qualities the devices must be configured by the client in accordance with the on site conditions which do not correspond to the function domain and thus the factory calibration Here...

Страница 14: ...as possible open windows and set air conditioning system to use outdoor air remove the housing cover and wait 15 minutes 2 Press and hold the ZERO VOC button until the flashing LED row changes to a st...

Страница 15: ...reverse polarity protection diode is integrated in this device variant This internal one way rectifier on AC supply voltage The output signal is to be tapped by a measuring instrument The output sign...

Страница 16: ...event perils of any kind No warranties or liabilities will be assumed for defects and damages arising from improper use of this device Consequential damages caused by a fault in this device are exclud...

Страница 17: ...a typique Pointe de courant 200 mA RLQ CO2 W RFTM LQ CO2 W 4 4 W 24 V cc typique 6 4 VA 24 V ca typique Pointe de courant 200 mA Sorties RTM CO2 SD 0 10 V r glage fixe Rxx CO2 W 0 10 V ou 4 20 mA char...

Страница 18: ...RASGARD RCO2 W Sonde d ambiance de CO2 Premium AERASGARD RLQ CO2 W Sonde d ambiance de qualit d air COV et de CO2 Premium AERASGARD RFTM CO2 W Sonde d ambiance multifonctionnelle pour l humidit la tem...

Страница 19: ...ir Quality ON ON Teneur en CO2 DIP 4 0 2000 ppm default OFF 0 5000 ppm ON talonnage automatique CO2 DIP 6 d sactiv OFF activ default ON Affectation relais DIP 7 DIP 8 CO2 default 600 1900 ppm 900 4700...

Страница 20: ...Afin de permettre une mesure ou une diff renciation des diff rentes qualit s de l air les appareils doivent tre r gl s par le client selon les conditions sur place qui ne correspondent pas au champ d...

Страница 21: ...res ou r gler le syst me de ventilation sur air ext rieur retirer le couvercle du bo tier et attendre 15 minutes 2 Maintenir la touche ZERO VOC enfonc e jusqu ce que les LED d tat s allument en contin...

Страница 22: ...signal de sortie doit tre pr lev avec un appareil de mesure Ce faisant le signal de sortie est mesur e par rapport au potentiel z ro O V de la tension d entr e Si cet appareil est aliment en courant c...

Страница 23: ...ur doit respecter les dispositions relatives la construction et la s curit et doit viter toutes sortes de risques Nous d clinons toute responsabilit ou garantie pour les d fauts et dommages r sultant...

Страница 24: ...O2 W 0 10 4 20 800 DIP 10 RTM CO2 SD Rxx CO2 W 24 1 A DIP RH C RH 0 100 RH 0 10 4 20 A DIP RH 2 0 20 80 25 C 3 0 C 0 50 C C 0 2 K 25 C C RTM CO2 SD 0 10 Rxx CO2 W 0 10 4 20 A DIP VOC VOC VOC volatile...

Страница 25: ...CO2 VOC Baldur 2 RTM CO2 SD RTM CO2 SD U 0 50 C 0 2000 1 1501 61B2 1001 200 RCO2 W RCO2 W LCD 0 2000 5000 1 W 1501 61B0 7321 200 RLQ CO2 W RLQ CO2 W 0 2000 5000 1 0 100 W 1501 61B1 7301 500 RLQ CO2 W...

Страница 26: ...Output CO in ppm Reset button r AERASGARD RCO2 W RLQ CO2 W RFTM LQ CO2 W RTM CO2 SD Rev 2021 V31 RFTM LQ CO2 W RTM CO2 SD DIP Baldur2 RFTM LQ CO2 W VOC DIP 1 DIP 2 LOW OFF OFF MEDIUM default ON OFF H...

Страница 27: ...27 r CO2 350 1 1 75 0 2000 1 0 7 0 5000 1 0 10 30 50 1 2 3 50 CO2 350 500 1 15 20 CO2 350 500 1 1 2 ZERO CO2 5 AUTO 0 5 600 3 4 10 350 500 1...

Страница 28: ...8 r VOC 15 20 7 VOC 1 15 2 ZERO VOC 5 AUTO 0 5 60 3 60 VOC 10 95 SET CO2 10 400 1 600 1900 1 0 2000 1 900 4700 1 0 5000 1 VOC 10 95 5 48 C 10 95 DIP DIP 7 DIP 8 10 CO2 ppm VOC C r H C CO2 V VOC T H r...

Страница 29: ...6 85 8 5 17 6 40 4 0 10 4 90 9 0 18 4 45 4 5 11 2 95 9 5 19 2 100 10 0 20 0 0 50 C C UA IA A 0 0 0 4 0 5 1 0 5 6 10 2 0 7 2 15 3 0 8 8 20 4 0 10 4 25 5 0 12 0 30 6 0 13 6 35 7 0 15 2 40 8 0 16 8 45 9...