Installation and Commissioning

ATTENTION!   

The minimum CO2

  

concentration of outdoor air amounts to approx. 350  ppm (output voltage = 1.75 V

 

at  MR  =  0...2000  ppm or 0.7 V at MR = 

0...5000  ppm) in leafy, hardly industrialised areas. Gas inter-exchange in the sensor element happens by diffusion.

 

Depending on the changes to the 

concentration and the flow velocity of the air surrounding the sensor, the reaction of the device to the change of concentration may take place with 
a delay. It is absolutely necessary to choose the device mounting position to ensure that the air stream “presses” into the duct tube. Otherwise, 
below-atmospheric pressure will develop in the duct tube that may cause a substantial deceleration of gas exchange or even prevent it.  

General information on air quality 

The service life of the sensor depends on its functional principle  and the type and concentration of pollutant gas burden. The sensitive layer of the 
sensor element reacts with all volatile organic compounds and is therefore modified in its electrical properties. This procedure leads to an offset of 
the characteristic line. When measuring the air quality, the general condition of the air quality is recorded. Whether the air quality is “good” or “bad” 
depends on the individual interpretation of each individual. Different pollution burdens and concentrations influence the air quality signal (0  - 10  V) in 
different ways. Examples are cigarette smoke, deodorant sprays, cleaning agents and various adhesive materials for floor and wall coverings, as well 
as dyes. Increased levels of solvents, nicotine, hydrocarbons, aerosol propellants, etc. intensify the wear/ageing of the sensor element. Especially at 
high pollutant  gas burdens, even when the devices are idle (transport and storage) the zero point is adjusted. This must be corrected on-site depending 
on the specific conditions or basic burdens. Air quality measuring instruments from various manufacturers cannot be compared directly with each 
other because of the different functional principles, the pre-set basic burden (zero point) and the permitted burden (amplification/sensitivity). The 
devices are set or calibrated according to the specifications of the sensor manufacturer. Here, a zero point and end value, and therefore a maximum 
load, are established. In special circumstances, there is an overrun of the measuring range or an excessively high basic burden on the devices (out-
gassing carpets, wall paint, etc.) In order to enable a measurement or distinction of different air qualities, the devices must be configured by the client 
in accordance with the on-site conditions which do not correspond to the function domain and thus the factory calibration. Here, it should be noted 
that the factory calibration will be lost and technical data compliance can no longer be guaranteed. 

Schematic diagram 

KTM - CO2 - SD

 

DIP switch

 

KTM - CO2 - SD

CO2

 

 content  

DIP 4

0...2000 ppm  (default)

OFF

0...5000 ppm

O N

4
5

6

OFFSET

CO²  

°C

1 2 3

4

ON

ZERO  CO²

DIP  CO²

+U

B 2

4V A

C/

DC

–UB GND Output CO

²  in ppm

free
Output temperature  in °C
free

Содержание AERASGARD KFTM-CO2-W

Страница 1: ...incl mounting flange for humidity temperature CO2 content and air quality VOC calibratable with active switching output F Notice d instruction Sonde transmetteur de gaine multifonctionnelle y compris...

Страница 2: ...202 5 126 112 90 50 20 112 20 4 32 3 13 4 M16x1 5 60 87 30 32 62 M4 5 2 20 M16x1 5 MFT 20 K Montageflansch aus Kunststoff Mounting flange plastic Bride de montage en mati re plastique SF K Kunststoff...

Страница 3: ...eingestellt Kxx CO2 W 0 10 V oder 4 20 mA B rde 800 ber DIP Schalter w hlbar gew hlte Variante gilt einheitlich f r alle Ausg nge mit Offset Potentiometer 10 vom Messbereich Relais Ausgang KTM CO2 SD...

Страница 4: ...er Ist Feuchte Ist Temperatur Luftqualit t und oder des Ist CO2 Gehaltes ZUBEH R SF M Metall Sinterfilter 16 mm L 32 mm austauschbar aus Edelstahl V4A 1 4404 7000 0050 2200 100 AERASGARD KTM CO2 SD Ka...

Страница 5: ...C 1 ausgezeichnet 0 19 keine Ma nahmen erforderlich 2 gut 20 39 baldige Bel ftung empfohlen 3 m ig 40 59 Bel ftung empfohlen 4 schlecht 60 79 verst rkte Bel ftung erforderlich 5 ungesund 80 100 intens...

Страница 6: ...andbel ge sowie Farbstoffe Erh hte Belastungen von z B L sungsmittel Nikotin Kohlenwasser stoffe Treibgase verst rken den Verbrauch die Alterung des Sensorelementes Ins be sondere bei hohen Schadgasbe...

Страница 7: ...assen 4 Nach 10 Minuten ist die Kalibrierung abgeschlossen Status LED erloschen Countdown abgelaufen und das Ger t sollte eine CO2 Konzentration zwischen 350 500 ppm anzeigen bzw bermitteln Automatisc...

Страница 8: ...s f hren Achten Sie daher auf die korrekte Verdrahtung Schaltung Schaltung 0 10V 0V GND 0 10V 0V GND Versorgung mit AC 24V 0V DC 15 36V GND AC 24V 0V DC 15 36V GND Schaltung 0 10V 0V GND V Versorgung...

Страница 9: ...d Sicherungsbestimmung zu gew hrleisten und Gef hrdungen aller Art zu vermeiden F r M ngel und Sch den die durch unsachgem e Verwendung dieses Ger tes entstehen werden keinerlei Gew hrleistungen und H...

Страница 10: ...VA 24 V AC typical peak current 200 mA Outputs KTM CO2 SD 0 10 V fixed Kxx CO2 W 0 10 V or 4 20 mA working resistance 800 selectable via DIP switches selected variant applies for all outputs with off...

Страница 11: ...ng actual humidity actual temperature air quality and or the actual CO2 content ACCESSORIES SF M Metal sinter filter 16 mm L 32 mm exchangeable stainless steel V4A 1 4404 7000 0050 2200 100 AERASGARD...

Страница 12: ...IAQ Indoor Air Quality VOC 1 excellent 0 19 no action required 2 good 20 39 prompt airing recommended 3 moderate 40 59 airing recommended 4 poor 60 79 increased airing required 5 unhealthy 80 100 inte...

Страница 13: ...Examples are cigarette smoke deodorant sprays cleaning agents and various adhesive materials for floor and wall coverings as well as dyes Increased levels of solvents nicotine hydrocarbons aerosol pr...

Страница 14: ...now leave the room 4 After 10 minutes the calibration is complete status LED has gone out the countdown is complete and the device should indicate or transmit a CO2 concentration of between 350 500 p...

Страница 15: ...ield device a supply voltage short circuit would be caused by that device The consequential short circuit current flowing through this field device may cause damage to it Therefore pay attention to co...

Страница 16: ...to adhere to the building and safety regulations and has to prevent perils of any kind No warranties or liabilities will be assumed for defects and damages arising from improper use of this device Con...

Страница 17: ...cc 10 Puissance absorb e 4 8 W 24 V cc typique 6 8 VA 24 V ca typique Pointe de courant 200 mA Sorties KTM CO2 SD 0 10 V r glage fixe Kxx CO2 W 0 10 V ou 4 20 mA charge 800 s lectionnable via interrup...

Страница 18: ...r la temp rature effective la qualit de l air et ou la teneur en CO2 ACCESSOIRES SF M filtre fritt en m tal 16 mm L 32 mm rempla able en acier inox V4A 1 4404 7000 0050 2200 100 AERASGARD KTM CO2 SD S...

Страница 19: ...int rieur Bundesgesundheitsbl Gesundheitsforsch Gesundheitsschutz 2007 50 990 1005 Journal du Minist re f d ral de la sant Recherche en sant Protection de la sant 2007 50 990 1005 Tableau d humidit pl...

Страница 20: ...les produits de nettoyage ou aussi divers mat riaux adh sifs pour rev tement de sol et de mur ainsi que les colorants Les charges polluantes comme les solvants la nicotine les hydro carbures les gaz c...

Страница 21: ...le faire sortir toutes les personnes de la pi ce 4 L talonnage est termin apr s 10 minutes LED d tat teintes compte rebours coul et l appareil doit indiquer une concentration en CO2 comprise entre 350...

Страница 22: ...ppareil Veillez donc au raccordement correct des fils Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND R...

Страница 23: ...entreprises d approvisionnement en nergie locales L acheteur doit respecter les dispositions relatives la construction et la s curit et doit viter toutes sortes de risques Nous d clinons toute respon...

Страница 24: ...10 Kxx CO2 W 0 10 4 20 800 DIP 10 KTM CO2 SD Kxx CO2 W 24 1 A DIP 16 L 35 16 L 32 0 100 0 95 2 0 20 80 25 C 3 0 0 10 4 20 A DIP 35 80 C 10 60 C 0 2 K 25 C KTM CO2 SD 0 10 Kxx CO2 W 0 10 4 20 DIP VOC...

Страница 25: ...CO2 W CO2 Deluxe AERASGARD KFTM LQ CO2 W VOC CO2 Deluxe WG02 CO2 VOC KTM CO2 SD KTM CO2 SD U 35 80 C 0 2000 5000 1 1501 8112 1001 200 KLQ CO2 W KLQ CO2 W 0 2000 5000 1 0 100 W 1501 8111 7301 500 KLQ...

Страница 26: ...2 15 1 5 6 4 75 7 5 16 0 20 2 0 7 2 80 8 0 16 8 25 2 5 8 0 85 8 5 17 6 30 3 0 8 8 90 9 0 18 4 35 3 5 9 6 95 9 5 19 2 40 4 0 10 4 100 10 0 20 0 45 4 5 11 2 50 5 0 12 0 55 5 5 12 8 35 80 C C UA in V IA...

Страница 27: ...ev 2021 V33 r CO2 350 1 1 75 0 2000 1 0 7 0 5000 1 0 10 KTM CO2 SD DIP KTM CO2 SD DIP4 0 2000 1 OFF 0 5000 1 ON 4 5 6 OFFSET CO C 1 2 3 4 ON ZERO CO DIP CO UB 24V AC DC UB GND Output CO in ppm free Ou...

Страница 28: ...28 r 30 50 1 2 3 50 CO2 350 500 1 15 20 CO2 350 500 1 1 2 ZERO CO2 5 AUTO 0 5 600 3 4 10 350 500 1 15 20 7 VOC 1 15 2 ZERO VOC 5 AUTO 0 5 60 3 60 VOC...

Страница 29: ...GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND 10 95 SET CO2 10 400 1 600 1900 1 0 2000 1 900 4700 1 0 5000 1 VOC 10 95 23 74 C 10...

Страница 30: ...30 r VOC 0 10 4 20 10 95 35 80 C 24 CO2 VOC CO2 VOC ZVEI VDE EMV VDE VDI 0 5 g DIN 43763 S S...

Страница 31: ...tatements and data herein represent our best knowledge at date of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certa...

Страница 32: ...32 AERASGARD KLQ CO2 W AERASGARD KFTM LQ CO2 W KTM CO2 SD D G F r Einbauschema Mounting diagram Sch ma de montage KLQ CO2 W KFTM LQ CO2 W KFTM CO2 W KTM CO2 SD 250 mm 115 mm P P...

Отзывы: