![S+S Regeltechnik 1301-1157-0130-200 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/s-s-regeltechnik/1301-1157-0130-200/1301-1157-0130-200_operating-instructions-mounting-and-installation_794010006.webp)
6
G
PREMASGARD
®
ALD
Rev. 2020 - V21
Conversion table for pressure values:
Unit =
bar
mbar
Pa
kPa
mH
2
O
1 Pa
0.00001 bar
0.01 mbar
1 Pa
0.001 kPa
0.000101971 mH
2
O
1 kPa
0.01 bar
10 mbar
1000 Pa
1 kPa
0.101971 mH
2
O
1 bar
1 bar
1000 mbar
100000 Pa
100 kPa
10.1971 mH
2
O
1 mbar
0.001 bar
1 mbar
100 Pa
0.1 kPa
0.0101971 mH
2
O
1 mH
2
O
0.0980665 bar
98.0665 mbar
9806.65 Pa
9.80665 kPa
1 mH
2
O
Calibratable barometer
PREMASGARD
®
ALD
with active output (U/I switchable) and 4 measuring ranges (max. 600...1100 hPa, switchable), in a
compact plastic housing with quick-locking screws, optionally with/without display. The pressure sensor is used for measuring atmospheric air
pressure in clean air (non-precipitating) or other non-aggressive, non-combustible gases. It is used in various applications such as ventilation and air
conditioning technology, in meteorological measurement stations and air-pressure-dependent control systems. The piezoresistive measuring element
is temperature-compensated and guarantees a high degree of reliability and accuracy. The sensor is factory-calibrated; an environmental precision
adjustment by an expert is possible.
TECHNICAL DATA
Power supply:
24 V AC/DC (± 10 %)
Working resistance:
R
a
(Ohm) = 25 ...450 Ohm for I-output
Load resistance:
R
L
> 25 kOhm for U-output
Power consumption:
< 1 W at 24 V DC;
< 2 VA at 24 V AC
Current consumption:
< 45 mA
Measuring ranges:
multi-range switching with
4 switchable measuring ranges
(see table)
Output:
switchable 0 -10 V ⁄ 4...20 mA
(via DIP switches)
Connection type:
3-wire connection
Ambient temperature:
storage –35...+85 °C; operation – 30...+75 °C, non-precipitating
Type of pressure:
atmospheric air pressure ⁄ absolute pressure
Medium:
clean air and non-aggressive, non-combustible gases
Accuracy:
typically ± 0.4 kPa compared to calibrated reference device
Zero point offset:
± 50 hPa
Positive pressure:
200 kPa
Signal filtering:
switchable 1 s ⁄ 10 s
(via DIP switches)
Temperature drift:
± 0.1 % of final value per °C
Housing:
plastic, UV-stabilised, polyamide material, 30 % glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), housing cover for display is transparent!
Housing dimensions:
72 x 64 x 37.8 mm (Tyr 1 without display)
72 x 64 x 43.3 mm (Tyr 1 with display)
Cable connection:
cable gland
, plastic (M 16 x 1.5; with strain relief, exchangeable,
inner diameter 10.4 mm)
or
M12 plug-in connector
(flush-type connector, 5-pin, A-coding)
according to DIN EN 61076-2-101 (optional, available upon request)
Electrical connection:
0.14 - 1.5mm², via screw terminals
Air humidity:
< 95 % r. H., non-precipitating air
Protection class:
III (according to EN 60 730)
Protection type:
IP 67
(according to EN 60 529)
housing tested, TÜV SÜD, report no. 713139052 (Tyr 1)
Standards:
CE conformity, electromagnetic compatibility according to EN 61 326, EMC Directive 2014 ⁄ 30 ⁄ EU
Equipment:
display,
one-line, cutout approx. 36 x15 mm (W x H),
for displaying the atmospheric air pressure ⁄ absolute pressure
ACCESSOIRES
WS-04
weather and sun protection hood
, 130 x 180 x 135 mm, stainless steel
V2A
(1.4301)
PREMASGARD
®
ALD
Measuring transducer for atmospheric pressure
Pressure range
(adjustable)
Type ⁄ WG01
Output display
(switchable)
Item no.
600...1100 hPa
700...1100 hPa
800...1100 hPa
900...1100 hPa
ALD
0 -10 V / 4...20 mA
1301-1157-0130-200
ALD LCD
0 -10 V / 4...20 mA
■
1301-1157-2130-200
Multi-range switching:
The
pressure ranges
can be set via DIP switches.
Output:
0 -10 V or 4...20 mA
(selectable via DIP switches)
Optional:
Cable connection with
M12 connector
according to DIN EN 61076-2-101 (on request)