66
CompTrol Interface V4.0.x | Issue 21-05-2021 | 1000932
Program 7 – temperature setpoint definition without signal boundary value monitoring
Temperature
setpoint
Analog signal type
[°C]
0-10 V DC
[V DC]
0-5 V DC
[V DC]
0-20 mA
[mA]
4-20 mA
[mA]
18
0
0
0
4
18.5
0.6
0.3
1.2
5
19
1
0.5
2
5.6
19.5
1.4
0.7
2.8
6.2
20
1.8
0.9
3.6
6.9
20.5
2.2
1.1
4.4
7.5
21
2.6
1.3
5.2
8.2
21.5
3
1.5
6
8.8
22
3.4
1.7
6.8
9.4
22.5
3.8
1.9
7.6
10.1
23
4.2
2.1
8.4
10.7
23.5
4.6
2.3
9.2
11.4
24
5
2.5
10
12
24.5
5.4
2.7
10.8
12.6
25
5.8
2.9
11.6
13.3
25.5
6.2
3.1
12.4
13.9
26
6.6
3.3
13.2
14.6
26.5
7
3.5
14
15.2
27
7.4
3.7
14.8
15.8
27.5
7.8
3.9
15.6
16.5
28
8.2
4.1
16.4
17.1
28.5
8.6
4.3
17.2
17.8
29
9
4.5
18
18.4
29.5
9.4
4.7
18.8
19
30
10
5
20
20
Table 46: Value table for program 7 temperature setpoint
13.4 Digital input assignment in program 7
Input
Function
Description
X2a-D1
Remote ON/OFF
The indoor unit or group of indoor units can be switched on and off via
the digital input. Forced mode can be activated with DIP switch
S2-5
(see “5.2.2 Remote ON/OFF” on page 26).
X2a-D2
Cooling mode
The signal switches the indoor unit to Cooling mode. The mode can
then no longer be changed using the wired remote control.