2.4.6 UTILITY SUBMENU
What you see on
the display
Description
Visibility Condition
Range
Default
Value
Mains Rest.
Mains Restoration
delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
10 sec
Over Freq
Over frequency
“Inst. Type” set to MGG or
MG
N, 10 Hz to 70 Hz
55 Hz
OFreq del
Over frequency delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
2 sec
Under Freq
Under frequency
“Inst. Type” set to MGG or
MG
N, 10 Hz to 70 Hz
45
UFreq del
Under frequency
delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
2 sec
OVolt(L-N)
Over voltage (Line-
Neutral)
“Inst. Type” set to MGG or
MG
N, 1 to 260 V
240 V
OVolt del
Over voltage delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
3 sec
UVolt(L-N)
Under voltage (Line-
Neutral)
“Inst. Type” set to MGG or
MG
N, 1 to 260 V
180 V
UVolt del
Under voltage delay
“Inst. Type” set to MGG or
MG
0 to 999 seconds
5 sec
U-Seq Test
Utility phase sequence
test
“Inst. Type” set to MGG or
MG
N: Phase sequence test disabled
Y: Phase sequence test enabled
N
NB Phases
Utility connection
“Inst. Type” set to MGG or
MG
1PH: 1 phase
3PH: 3 phases
3PH
What you see on
the display
Description
Visibility Condition
Range
Default
Value
G2 Overload %
G2 Overload % of the
current transformer
“Omega Type” set to
ATSO
0 to 100%
90
G2 Overld del
G2 Overload delay
“Omega Type” set to
ATSO
0 to 999 seconds
10
G1 Max Load %
G1 Maximum Load %
of the current
transformer
“Omega Type” set to
ATSO
0 to 100%
50
G1 Maxld del
G1 Maximum load
delay
“Omega Type” set to
ATSO
0 sec to 99 min
10sec
G2 Min Load %
G2 Minimum Load %
of the current
transformer
“Omega Type” set to
ATSO
0 to 100%
30
G2 Minld del
G2 Minimum load
delay
“Omega Type” set to
ATSO
0 sec to 99 min
10sec
Recycle reset
Recycle after Utility
reset
N/A
N: No automatic reset is done after
a genset fault
Y: Automatic reset is done on faulty
genset when Mains is established
Y
Gx Mode
G1/G2 Mode
N/A
OnWUAbs: On When Utility is
Absent
AlwaysOn: Always On
OnWUAbs
2. FRONT
PANEL
DESCRIPTION
Содержание OMEGA-ATS
Страница 2: ......
Страница 35: ...6 DIMENSIONS 6 DIMENSIONS...
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ...0 1 2 3 4 5 0 1 2 3 4 5 0 1 0 1 2...
Страница 41: ...6 6 6 6 6 6 6 6 6 6 6 6...
Страница 45: ......
Страница 46: ......