
2.3.3 UTILITY STATUSES
Status
Display
Abbreviation
Standby (not ready)
Standby
Standby
Ready
Ready
Ready
Utility Absent
Absent
Absent
Counting Restoring delay
Restoring
Rest.
Engaging load (CM engaged with No CM F/B detected yet)
Engaging
Engaging
Feeding the load (CM engaged with CM F/B detected )
Feeding Load
Feeding
Disengaging load CM Disengaged) with CM still detected
Disengaging
Diseng.
2.3.4 UTILITY FAULTS
Fault
Display
Abbreviation
Utility contactor failure
C-U Fail
CU Fail
One of the three-phase voltages goes above the over voltage limits set
by OVolt(L-N) for a delay of OVolt del.
Hi Voltage
Hi Volt.
One of the three-phase voltages goes below the under voltage limits
set by UVolt(L-N) for a delay of UVolt del.
Lo Voltage
Lo Volt.
The frequency goes above the value set in Over Freq. for a delay of
OFreq del.
Hi Freq.
Hi Freq.
The frequency goes below the value set in Under Freq. for a delay of
UFreq del.
Lo Freq.
Lo Freq.
The phases are reversed
Wrong Seq.
Seq.Fail
2. FRONT
PANEL
DESCRIPTION
Содержание OMEGA-ATS
Страница 2: ......
Страница 35: ...6 DIMENSIONS 6 DIMENSIONS...
Страница 37: ......
Страница 38: ......
Страница 39: ......
Страница 40: ...0 1 2 3 4 5 0 1 2 3 4 5 0 1 0 1 2...
Страница 41: ...6 6 6 6 6 6 6 6 6 6 6 6...
Страница 45: ......
Страница 46: ......