2.2 FRONT PANEL LEDS
Five Leds used to indicate the operating mode.
Seven input Leds used to indicate the status of the inputs.
2.3 DETECTED AND SIGNALED FAULTS
2.3.1 GENSET STATUSES
Status
Display
Abbreviation
Standby ( Not ready)
Standby
Standby
Ready
Ready
Ready
Counting Response delay to give start order
Response
RSP
Start order is given (ST.Gx engaged)
Starting
Starting
Gx OK signal active with No AC signals from genset
OK-WaitingAC
OK-NoAC
Counting Warm-up delay to engage load
Warm Up
WUp
Engaging load (CGx Engaged) with No CGx F/B detected yet
Engaging
Engaging
Load engaged (CGx Engaged with CGx F/B detected) with No CG F/B
detected yet
Engaged
Engaged
Feeding the load (CGx Engaged with CGx F/B & CG F/B detected )
Feeding Load
Feeding
Disengaging the load (CGx Disengaged) with CGx and/or CG F/B still
detected
Disengaging
Diseng.
Counting Cooling delay to disengage start order
Cooling
COL
Shutting down ( Start order released)
Shutting
SDN
2.3.2 GENSET FAULTS
Fault
Display
Abbreviation
Start Fail caused by absence of Gx OK signal
StFail-NoOK
StF.NoOK
Start Fail caused by Failure of G contactor
StFail-CG-F
StF.CG-F
Start Fail caused by Failure of Gx contactor
StFailCGx-F
StF.CGxF
Start Fail caused by Absence of AC signals
StFail-NoAC
StF.NoAC
Start Fail caused by High voltage
StFail-HiV.
StF.HiV
Start Fail caused by Low voltage
StFail-LoV.
StF.LoV
Start Fail caused by High frequency
StFail-HiF.
StF.HiF
Start Fail caused by Low frequency
StFail-LoF.
StF.LoF
Start Fail caused by wrong phase sequence
StFail-Seq-F
StF.Seq
Start Fail caused by G contactor jam
StFail-CGJam
StF.CG-J
Start Fail caused by Mains contactor jam
StFail-CMJam
StF.CM-J
Start Fail caused by the other generator contactor jam
StFail-CGyJam
StF.CGyJ
Start Fail caused by the expire of start failure delay
StFail-Time
StF.Time
Gx OK Signal lost after generator has turned on
OK Failure
OK Fail
Global contactor failure
CG Fail
CG Fail
CGx Contactor failure
CGx Fail
CGx Fail
One of the three-phase voltages goes above the over voltage limits set
by OVolt(L-N) for a delay of OVolt del.
Hi Voltage
Hi Volt.
One of the three-phase voltages goes below the under voltage limits
set by UVolt(L-N) for a delay of UVolt del.
Lo Voltage
Lo Volt.
The frequency goes above the value set in Over Freq. for a delay of
OFreq del.
Hi Freq.
Hi Freq.
The frequency goes below the value set in Under Freq. for a delay of
UFreq del.
Lo Freq.
Lo Freq.
The phases are reversed
Wrong Seq.
Seq.Fail
The load exceeds the value set by Overload % for a delay of Overld del Over Load
Over Ld.
2. FRONT
PANEL
DESCRIPTION