Page 10
Victrix 24kW X Instructions
Example:
Flue system consists of 9m of 80mm air intake pipe with 3 x 90 bends and 6m of exhaust pipe with 2 x 90
bends.
Component Resistances:
Component
Resistance
Quantity Total
80mm Intake pipe
0.87
9
7.83
90˚ air intake bend
1.9
3
5.7
80mm Flue pipe
1.2
6
7.2
90˚ Flue bend
2.6
2
5.2
25.93
Total Flue Resistance
In this case the total resistance of the
system is less than 100. The flue de-
sign is acceptable. Care should be
taken to insulate the exhaust flue pipe
to ensure that condensation is not pos-
sible.