Installation, Usage and Maintenance Instructions
6.3 WATER CONNECTION
6.3.1 PUMP
The boiler does not have a built in CH-pump. Therefore a CH-pump must be mounted separately . Select a pump that
matches the hydraulic resistance of the boiler and the installation. The graph below shows the resistance characteristics
for the different boiler models
For electrical connections see chapter 6.7.
6.3.2 MINIMUM FLOW
The minimum flows shown below must be guaranteed.
Type
Flow [m
3
/h] @ ΔT25 Full Load
Flow [m
3
/h] @ ΔT30 Start = 15%
Flow [m
3
/h] @ ΔT30 Part Load
340
11.7
3.1
1.9
425
14.6
3.9
2.4
510
17.5
4.7
2.9
600
20.5
5.5
3.4