background image

26

DIRECT SPARK IGNITION
LIGHTING INSTRUCTIONS

This appliance is equipped with a
direct spark ignition device. This device
lights the main burners each time the
room thermostat (closes) calls for heat.
See lighting instructions on the
furnace.

TO START FURNACE

1.

BE SURE THAT THE MANUAL
GAS CONTROL HAS BEEN IN
THE “OFF” POSITION FOR AT
LEAST FIVE MINUTES. DO NOT
ATTEMPT TO MANUALLY LIGHT
THE MAIN BURNERS. FAILURE
TO FOLLOW THIS WARNING CAN
CAUSE A FIRE OR AN
EXPLOSION RESULTING IN
PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.

2. Set the room thermostat to the

lowest setting.

3. Turn the gas control knob to the

“On” position, or move the gas
control lever to the “On” position.

4. Replace the control access door.

5. Turn on the electrical power.

6. Set the room thermostat to a point

above room temperature to light the
main burners. After the burners are
lit, set room thermostat to a desired
temperature.

TO SHUT DOWN FURNACE

1. Set the room thermostat to its

lowest setting.

2. Shut off the gas to main burners by

turning the gas control knob to the
“Off” position, or by depressing the
gas control lever and moving it to
the “Off” position.

SHOULD OVERHEATING OCCUR
OR THE GAS SUPPLY FAIL TO
SHUT OFF, SHUT OFF THE
MANUAL GAS VALVE TO THE
APPLIANCE BEFORE SHUTTING
OFF THE ELECTRICAL SUPPLY.
FAILURE TO DO SO CAN CAUSE AN
EXPLOSION OR FIRE RESULTING
IN PROPERTY DAMAGE,
PERSONAL INJURY OR DEATH.

Sequence of operation with a single
stage thermostat

a. Connect the “W” terminal on the

thermostat to the W2 terminal on the
control board.

b. When there is a call for heat, the “R”

and “W2” contacts close and the
IFC runs a self check routine to
verify that the pressure switch
contacts are open. The limit switch
contacts are constantly monitored.

START-UP PROCEDURES

WARNING

!

WARNING

!

c. The induced draft motor starts on

high until the low pressure switch
contacts close (a maximum of 60
seconds), and then changes to low
speed. After a 30 second pre-purge,
the spark ignitor energizes and the
low stage of the gas valve opens,
lighting the burners.

d. After the gas valve opens, the

remote flame sensor must prove
ignition for one second using the
process of flame rectification. If the
burners do not light, the system
goes through another ignition
sequence. It does this up to 4 times.
(2 tries on low fire and 2 tries on
high fire.)

e. The main blower starts on low

speed 20 seconds after the burners
light. The furnace operates on low
fire for 12 minutes and then, if the
thermostat is not satisfied, shifts to
high fire, causing the draft inducer to
go to high speed, the gas valve to
100% and the main blower goes to
heat speed.

f. When the thermostat cycle ends, the

gas valve closes, and the burners
go out.

g. The draft inducer will continue

running for a 10 second (low speed)
or 5 second (high speed) post
purge.

h. The main blower will run for 90

seconds on high speed or 120
seconds on low speed. (This timing
is field adjustable, for 60, 90, 120 or
150 seconds). See Figure 21 for
switch settings.

Sequence if the system doesn’t light
or doesn’t sense flame:

a. If flame is not sensed within 8

seconds after the gas valve opens,
the valve closes and the ignitor is
de-energized. The induced draft
motor will run for 60 seconds on low,
stop momentarily, and then restart.

b. The ignition process goes through

one more try on low fire. If this fails,
there are two tries on high fire with a
30 second interpurge between trials.
During high fire ignition attempts,
the inducer steps to high speed, the
high pressure switch closes (both
pressure switches are now closed),
and the gas valve steps to 100%.

c. If there is no ignition after the 2nd

trial on high fire, the furnace goes
into soft lockout for one hour.

d. The sequence repeats after a one

hour delay and continues repeating
until ignition is successful or the call
for heat is terminated.

e. To reset the lockout, make and

break power either at the thermostat
or at the unit disconnect switch for 5
to 10 seconds. The furnace will then
go through another set of trials for
ignition.

f. If flame is established and

maintained during the trial for
ignition period and flame is lost, the
gas valve is de-energized, the draft
inducer completes a post-purge of
10 seconds. The indoor blower
motor will be energized and/or
remain energized on low speed for
low fire and heat speed for high fire
for the selected delay off time.

When the inter-purge delay is over,
the control verifies the pressure
switch has opened and then initiates
another ignition trial period. The
control will recycle up to 5 flame
losses (4 re-cycles) within a single
call for heat before going into
lockout.

Sequence of operation with two
stage thermostat

Connect W1 and W2 terminals on the
thermostat to W and W2 terminals on
the control board.

Call for 1st stage heat

a. R and W thermostat contacts close

and the control module runs a self-
check routine. After the control
module verifies that both sets of
pressure switch contacts are open,
the induced draft motor starts on
high until the low pressure switch
contacts close (a maximum of 60
seconds), then changes to low
speed.

b. After a 30 second pre-purge, the

spark igniter energizes and the gas
valve (low stage) opens, lighting the
burners.

c. After the burners light, the remote

flame sensor must prove ignition. If
the burners do not light, the system
goes through another ignition
sequence. It does this up to 4 times
(2 tries on low fire and 2 tries on
high fire).

d. The main blower starts on low

speed 20 seconds after the gas
valve opens. The furnace continues
to run on low until the call for heat is
satisfied or the 2nd stage contacts
close. If the 1st stage call for heat is
satisfied the gas valve closes and
the induced draft motor continues
running for a 10 second post purge
time. the main blower runs for 120
seconds (this timing is field
adjustable). See Figure 23 for switch
settings.

Call for 2nd stage heat after 1st

stage

R and W2 thermostat contacts close,
calling for 2 stage heat. The induced
draft motor then switches to high
speed and the high pressure switch
contacts will close. The gas valve
switches to high fire and the main
blower switches to heating speed.

Содержание (-)GLL Series

Страница 1: ...92 24161 24 09 SUPERSEDES 92 24161 24 08 INSTALLATION INSTRUCTIONS FOR UPFLOW HORIZONTAL GPL AND DOWNFLOW GLL TWO STAGE INDUCED DRAFT GAS FURNACES...

Страница 2: ...furnace ground to electrical panel DC microamp A flame signal hot surface ignition units Correct control voltage Measure and set heat anticipator amperage Air conditioning low voltage wires connected...

Страница 3: ...e cancer or birth defects such as fiberglass insulation lead in brass and combustion products from natural gas All new equipment shipped for sale in California will have labels stating that the produc...

Страница 4: ...RATING PLATE MARKING MEANS FOR PROVIDING OUTDOOR AIR REQUIRED FOR COMBUSTION RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55 F 13 C AND 80 F 27 C AND CLEAN FURNACE DUCT WORK AND COMPONENTS UPON SUBSTANTI...

Страница 5: ...is unit when installed For attic or crawl space installation horizontal furnaces may be installed on combustible wood flooring or by using support brackets See Figure 1 6 IMPORTANT If installing in a...

Страница 6: ...BOTTOM 24 1 2 26 13 16 26 5 8 24 11 32 24 11 32 19 32 9 16 24 7 16 28 1 16 26 5 8 14 3 8 11 1 2 34 1 5 8 DIA 23 15 20 D 7 8 DIA 7 8 DIA 19 32 19 32 3 4 14 3 8 11 1 2 1 1 4 23 17 32 C GAS CONNECTION EL...

Страница 7: ...15 5 8 23 5 8 0 0 0 1 3 6 140 lbs TOP BOTTOM 24 1 2 19 3 4 C A B D LOW VOLTAGE GAS CONNECTION ELECTRIC CONNECTION E 26 5 8 26 13 16 6 3 16 20 3 8 23 3 8 5 8 5 8 3 4 5 8 34 23 3 8 20 3 8 6 3 16 24 7 16...

Страница 8: ...tor coil if used of the entire system should not exceed 0 5 w c Be sure to have adequate space for unit filter IMPORTANT Some high efficiency filters have a greater than normal resistance to air flow...

Страница 9: ...CE AND CREATE POTENTIALLY HAZARDOUS CONDITIONS INCLUDING CARBON MONOXIDE POISONING OR DEATH 2 If summer air conditioning is desired position the indoor coil on the top of the unit Insure that no air c...

Страница 10: ...a closet the door must be closed when making this check of the installation DO NOT reset the overtemperature switch without taking corrective action to assure that an adequate supply of combustion ai...

Страница 11: ...temporary construction outside air may still be required for the furnace to operate and vent properly Outside air openings should be sized the same as for a confined space FIGURE 7 AIR FROM ATTIC CRAW...

Страница 12: ...minimum free area of 1 square inch for each 2000 BTUH of total input rating for all equipment in the enclosure see Figure 8 Here are typical duct sizes FIGURE 8 OUTSIDE AIR USING A HORIZONTAL INLET O...

Страница 13: ...ible construction that carries a U L listing Common venting is allowed with vertical B 1 vent systems and lined masonry chimneys Follow the National Fuel Gas Code ANSI Z223 1 and or the Natural Gas In...

Страница 14: ...ight above the highest connected equipment draft hood or flue collar 3 Must rise 1 4 per foot away from the furnace on horizontal runs and be supported with straps or hangers so it has no sags or dips...

Страница 15: ...remains connected to the common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous co...

Страница 16: ...event undue pressure drop and never smaller than the pipe size to the combination gas valve on the furnace Refer to Table 2 for the recom mended pipe size for natural gas and Table 3 for LP gas pipe s...

Страница 17: ...d to use liquefied petroleum LP gas by replacing the pressure regulator spring with the conversion kit spring This LP kit spring allows the regulator to maintain the proper adjusted manifold pressure...

Страница 18: ...clockwise to decrease pressure 7 Securely replace the regulator cap for high fire 8 Operate the furnace in low speed 9 Note or adjust the manifold pressure to give A 1 7 w c for natural gas low fire B...

Страница 19: ...aking the pressure adjustment TO CHANGE ORIFICE SPUDS 1 Shut off the manual main gas valve and remove the gas manifold 2 Replace the orifice spuds 3 Reassemble in reverse order 4 Turn the gas supply b...

Страница 20: ...l Electric Code ANSI NFPA No 70 latest edition or Canadian Electrical Code Part 1 CSA Standard C22 1 and local building codes This can be obtained from National Fire Protection Association Batterymarc...

Страница 21: ...eaner whenever the circulating air blower is in operation RXGW B01 CHIMNEY ADAPTER This appliance is CSA certified for use with RXGW B01 chimney adapter Refer to Kit Installation Instructions 92 10168...

Страница 22: ...TO BE CHANGED THE FOLLOWING EXAMPLES SHOW HOW TO DETERMINE IF AN ORIFICE CHANGE WILL BE NECESSARY AND HOW TO DETERMINE THE NEW ORIFICE SIZE IN CANADA AS AN ALTERNATE TO ADJUSTING THE BURNER ORIFICE SI...

Страница 23: ...YSTEMS Furnace installation with Rheem Ruud ARA or ARL outdoor condensing units can provide high efficiency up to 16 SEER cooling operation Using Tables 9 and 10 and literature provided with the cooli...

Страница 24: ...8 48 25 000 24 000 23 000 22 000 21 000 20 000 19 000 18 000 17 000 16 000 All calculations are performed by using the first three columns of information only Before beginning any calculations determi...

Страница 25: ...thermostat connections since low speed cooling is not wired to the same control board as all other thermostat terminals UP TO 16 SEER COOLING OPERATION SINGLE STAGE COOLING All IFC part numbers and re...

Страница 26: ...ttings Sequence if the system doesn t light or doesn t sense flame a If flame is not sensed within 8 seconds after the gas valve opens the valve closes and the ignitor is de energized The induced draf...

Страница 27: ...d voltage variations The installer is given the option of three air flow options in the heating mode as shown in Table 12 Switches 1 and 2 on the interface control regulate the steady state heating mo...

Страница 28: ...inputs The B terminal input is provided for heat pump applications This signal comes from a heat pump thermostat and tells the heat pump to switch its reversing valve to TABLE 14 COOLING AIR FLOW SWI...

Страница 29: ...29 FIGURE 23 COOLING HEAT PUMP OFF DELAY PROFILES ST A0827 01...

Страница 30: ...30 FIGURE 24 COOLING HEAT PUMP ON DELAY PROFILES ST A0828 01...

Страница 31: ...31 FIGURE 25 LOW HEAT OFF DELAY PROFILES ST A0829 01...

Страница 32: ...32 FIGURE 26 HIGH HEAT OFF DELAY PROFILES ST A0830 01...

Страница 33: ...ne from the heat exchanger See Figure 27 2 Insert a thermometer in the return air duct as close to the furnace as possible 3 Operate the furnace 4 When the thermometer in the supply air duct stops ris...

Страница 34: ...wer wheel E Wrong motor rotation F Blower wheel slipping on the motor shaft 6 Overfiring the furnace with too much gas pressure 7 Ventilation problems FLAME ROLL OUT SAFETY SWITCHES Furnaces are equip...

Страница 35: ...tch is located in the upper position on the furnace LUBRICATION The blower motor and induced draft motor are permanently lubricated by the manufacturer and do not require further attention The motor m...

Страница 36: ...s are used in the system it is important that the airflow is not reduced to maximize system performance and life Always verify that the system s airflow is not impaired by the filtering system that ha...

Страница 37: ...37 FIGURE 32 FILTER RETAINING RODS SIDE RETURN FIGURE 33 DOWNFLOW FILTER INSTALLATION...

Страница 38: ...DS PLACEMENT OF COMBUSTIBLE MATERIALS ON AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE PERSONAL INJURY OR DEATH THE FURNACE OWNER SHOULD BE CAUTIONED...

Страница 39: ...39 FIGURE 34 INTEGRATED FURNACE CONTROL IFC TROUBLESHOOTING GUIDE FOR UTEC 1095 101...

Страница 40: ...40...

Страница 41: ...41 FIGURE 35 FOR MODELS WITH UT ELECTRONIC CONTROLS 1095 101 INTEGRATED FURNACE CONTROL AND ECM BLOWER MOTOR...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...44 CM 1105...

Отзывы: