background image

18

SETTING GAS PRESSURE

The maximum gas supply pressure to
the furnace should be 10.5

” 

w.c.

natural gas, or 13

” 

w.c. LP gas. The

minimum supply gas pressure to the
gas valve should be 5" w.c. natural gas
or 11" w.c. LP gas. A properly
calibrated manometer is required for
accurate gas pressure measurements.

ELEVATIONS ABOVE 2000 FT
REQUIRE THAT THE FURNACE
INPUT RATING BE ADJUSTED AND
THAT THE SIZE OF THE BURNER
ORIFICES BE RE-CALCULATED
BASED ON ELEVATION AND GAS
HEATING VALUE. THE BURNER
ORIFICES MAY (OR MAY NOT)
NEED TO BE CHANGED. SEE THE
SECTION TITLED “HIGH ALTITUDE
INSTALLATIONS” OF THIS BOOK
FOR INSTRUCTIONS.

Manifold Gas Pressure
Measurement. Natural gas manifold
pressure should be 3.5" w.c.; LP gas
manifold pressure should be 10"
w.c. 

Only small variations on gas

pressure should be made by adjusting
the pressure regulator.

1. With the gas shut off at the manual

gas valve, remove the pressure
tap plug in the gas manifold or the
gas valve outlet. See Figure 26.

2. Connect a U-Tube manometer to

this pressure tap. See Figure 27.

3. Turn on the gas supply and

operate the furnace in high speed.

4. Note or adjust the manifold gas

pressure to give:

A. 3.5" w.c. for natural gas high fire.

B. 10" w.c. for LP gas high fire.

5. To adjust the pressure regulator

for high fire, remove the regulator
cap located on the 

side of the

regulator. See Figure 14.

6. Turn the adjustment screw

clockwise to increasre pressure or
counterclockwise to decrease
pressure.

7. Securely replace the regulator cap

for high fire.

8. Operate the furnace in low speed.

9. Note or adjust the manifold

pressure to give:

A. 1.7" w.c. for natural gas low fire.

B. 4.9" w.c. for LP gas low fire.

10. To adjust the pressure regulator

for low fire, remove the regulator
cap 

on the top of the regulator.

See Figure 14.

11. Turn the adjustment screw

clockwise to increase pressure or
counterclockwise to decrease
pressure.

12. Securely replace the regulator cap

for low fire.

TABLE 2

NATURAL GAS PIPE CAPACITY TABLE (CU. FT./HR.)

Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific
gravity of 0.60 (natural gas).

Nominal

Length of Pipe, Feet

Iron Pipe
Size, Inches

10

20

30

40

50

60

70

80

1/2

132

92

73

63

56

50

46

43

3/4

278

190

152

130

115

105

96

90

1

520

350

285

245

215

195

180

170

1-1/4

1,050

730

590

500

440

400

370

350

1-1/2

1,600

1,100

890

760

670

610

560

530

After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour
required for the gas input rating of the furnace. By formula:

Gas Input of Furnace (BTU/HR)

Cu. Ft. Per Hr. Required

=

Heating Value of Gas (BTU/FT3)

The gas input of the furnace is marked on the furnace rating plate. The heating value of the gas (BTU/FT3) may be
determined by consulting the local natural gas utility or the LP gas supplier.

FIGURE 14

TYPICAL GAS VALVE

INLET
PRESSURE
TAP

OUTLET
PRESSURE
TAP

HIGH FIRE
MANIFOLD
PRESSURE
ADJUSTMENT

LOW FIRE
PRESSURE
MANIFOLD
ADJUSTMENT

FIGURE 13

TYPICAL HOSE CONNECTION TO LINE PRESSURE TAP

!

CAUTION

Содержание (-)GLL Series

Страница 1: ...92 24161 24 09 SUPERSEDES 92 24161 24 08 INSTALLATION INSTRUCTIONS FOR UPFLOW HORIZONTAL GPL AND DOWNFLOW GLL TWO STAGE INDUCED DRAFT GAS FURNACES...

Страница 2: ...furnace ground to electrical panel DC microamp A flame signal hot surface ignition units Correct control voltage Measure and set heat anticipator amperage Air conditioning low voltage wires connected...

Страница 3: ...e cancer or birth defects such as fiberglass insulation lead in brass and combustion products from natural gas All new equipment shipped for sale in California will have labels stating that the produc...

Страница 4: ...RATING PLATE MARKING MEANS FOR PROVIDING OUTDOOR AIR REQUIRED FOR COMBUSTION RETURN AIR TEMPERATURE MAINTAINED BETWEEN 55 F 13 C AND 80 F 27 C AND CLEAN FURNACE DUCT WORK AND COMPONENTS UPON SUBSTANTI...

Страница 5: ...is unit when installed For attic or crawl space installation horizontal furnaces may be installed on combustible wood flooring or by using support brackets See Figure 1 6 IMPORTANT If installing in a...

Страница 6: ...BOTTOM 24 1 2 26 13 16 26 5 8 24 11 32 24 11 32 19 32 9 16 24 7 16 28 1 16 26 5 8 14 3 8 11 1 2 34 1 5 8 DIA 23 15 20 D 7 8 DIA 7 8 DIA 19 32 19 32 3 4 14 3 8 11 1 2 1 1 4 23 17 32 C GAS CONNECTION EL...

Страница 7: ...15 5 8 23 5 8 0 0 0 1 3 6 140 lbs TOP BOTTOM 24 1 2 19 3 4 C A B D LOW VOLTAGE GAS CONNECTION ELECTRIC CONNECTION E 26 5 8 26 13 16 6 3 16 20 3 8 23 3 8 5 8 5 8 3 4 5 8 34 23 3 8 20 3 8 6 3 16 24 7 16...

Страница 8: ...tor coil if used of the entire system should not exceed 0 5 w c Be sure to have adequate space for unit filter IMPORTANT Some high efficiency filters have a greater than normal resistance to air flow...

Страница 9: ...CE AND CREATE POTENTIALLY HAZARDOUS CONDITIONS INCLUDING CARBON MONOXIDE POISONING OR DEATH 2 If summer air conditioning is desired position the indoor coil on the top of the unit Insure that no air c...

Страница 10: ...a closet the door must be closed when making this check of the installation DO NOT reset the overtemperature switch without taking corrective action to assure that an adequate supply of combustion ai...

Страница 11: ...temporary construction outside air may still be required for the furnace to operate and vent properly Outside air openings should be sized the same as for a confined space FIGURE 7 AIR FROM ATTIC CRAW...

Страница 12: ...minimum free area of 1 square inch for each 2000 BTUH of total input rating for all equipment in the enclosure see Figure 8 Here are typical duct sizes FIGURE 8 OUTSIDE AIR USING A HORIZONTAL INLET O...

Страница 13: ...ible construction that carries a U L listing Common venting is allowed with vertical B 1 vent systems and lined masonry chimneys Follow the National Fuel Gas Code ANSI Z223 1 and or the Natural Gas In...

Страница 14: ...ight above the highest connected equipment draft hood or flue collar 3 Must rise 1 4 per foot away from the furnace on horizontal runs and be supported with straps or hangers so it has no sags or dips...

Страница 15: ...remains connected to the common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other gas burning appliance to their previous co...

Страница 16: ...event undue pressure drop and never smaller than the pipe size to the combination gas valve on the furnace Refer to Table 2 for the recom mended pipe size for natural gas and Table 3 for LP gas pipe s...

Страница 17: ...d to use liquefied petroleum LP gas by replacing the pressure regulator spring with the conversion kit spring This LP kit spring allows the regulator to maintain the proper adjusted manifold pressure...

Страница 18: ...clockwise to decrease pressure 7 Securely replace the regulator cap for high fire 8 Operate the furnace in low speed 9 Note or adjust the manifold pressure to give A 1 7 w c for natural gas low fire B...

Страница 19: ...aking the pressure adjustment TO CHANGE ORIFICE SPUDS 1 Shut off the manual main gas valve and remove the gas manifold 2 Replace the orifice spuds 3 Reassemble in reverse order 4 Turn the gas supply b...

Страница 20: ...l Electric Code ANSI NFPA No 70 latest edition or Canadian Electrical Code Part 1 CSA Standard C22 1 and local building codes This can be obtained from National Fire Protection Association Batterymarc...

Страница 21: ...eaner whenever the circulating air blower is in operation RXGW B01 CHIMNEY ADAPTER This appliance is CSA certified for use with RXGW B01 chimney adapter Refer to Kit Installation Instructions 92 10168...

Страница 22: ...TO BE CHANGED THE FOLLOWING EXAMPLES SHOW HOW TO DETERMINE IF AN ORIFICE CHANGE WILL BE NECESSARY AND HOW TO DETERMINE THE NEW ORIFICE SIZE IN CANADA AS AN ALTERNATE TO ADJUSTING THE BURNER ORIFICE SI...

Страница 23: ...YSTEMS Furnace installation with Rheem Ruud ARA or ARL outdoor condensing units can provide high efficiency up to 16 SEER cooling operation Using Tables 9 and 10 and literature provided with the cooli...

Страница 24: ...8 48 25 000 24 000 23 000 22 000 21 000 20 000 19 000 18 000 17 000 16 000 All calculations are performed by using the first three columns of information only Before beginning any calculations determi...

Страница 25: ...thermostat connections since low speed cooling is not wired to the same control board as all other thermostat terminals UP TO 16 SEER COOLING OPERATION SINGLE STAGE COOLING All IFC part numbers and re...

Страница 26: ...ttings Sequence if the system doesn t light or doesn t sense flame a If flame is not sensed within 8 seconds after the gas valve opens the valve closes and the ignitor is de energized The induced draf...

Страница 27: ...d voltage variations The installer is given the option of three air flow options in the heating mode as shown in Table 12 Switches 1 and 2 on the interface control regulate the steady state heating mo...

Страница 28: ...inputs The B terminal input is provided for heat pump applications This signal comes from a heat pump thermostat and tells the heat pump to switch its reversing valve to TABLE 14 COOLING AIR FLOW SWI...

Страница 29: ...29 FIGURE 23 COOLING HEAT PUMP OFF DELAY PROFILES ST A0827 01...

Страница 30: ...30 FIGURE 24 COOLING HEAT PUMP ON DELAY PROFILES ST A0828 01...

Страница 31: ...31 FIGURE 25 LOW HEAT OFF DELAY PROFILES ST A0829 01...

Страница 32: ...32 FIGURE 26 HIGH HEAT OFF DELAY PROFILES ST A0830 01...

Страница 33: ...ne from the heat exchanger See Figure 27 2 Insert a thermometer in the return air duct as close to the furnace as possible 3 Operate the furnace 4 When the thermometer in the supply air duct stops ris...

Страница 34: ...wer wheel E Wrong motor rotation F Blower wheel slipping on the motor shaft 6 Overfiring the furnace with too much gas pressure 7 Ventilation problems FLAME ROLL OUT SAFETY SWITCHES Furnaces are equip...

Страница 35: ...tch is located in the upper position on the furnace LUBRICATION The blower motor and induced draft motor are permanently lubricated by the manufacturer and do not require further attention The motor m...

Страница 36: ...s are used in the system it is important that the airflow is not reduced to maximize system performance and life Always verify that the system s airflow is not impaired by the filtering system that ha...

Страница 37: ...37 FIGURE 32 FILTER RETAINING RODS SIDE RETURN FIGURE 33 DOWNFLOW FILTER INSTALLATION...

Страница 38: ...DS PLACEMENT OF COMBUSTIBLE MATERIALS ON AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROPERTY DAMAGE PERSONAL INJURY OR DEATH THE FURNACE OWNER SHOULD BE CAUTIONED...

Страница 39: ...39 FIGURE 34 INTEGRATED FURNACE CONTROL IFC TROUBLESHOOTING GUIDE FOR UTEC 1095 101...

Страница 40: ...40...

Страница 41: ...41 FIGURE 35 FOR MODELS WITH UT ELECTRONIC CONTROLS 1095 101 INTEGRATED FURNACE CONTROL AND ECM BLOWER MOTOR...

Страница 42: ...42...

Страница 43: ...43...

Страница 44: ...44 CM 1105...

Отзывы: