Ruijie RG-NBS5200 Series Switches Hardware Installation and Reference Guide
Product Installation
24
Place the switch on the table, as shown in Figure 3-5.
Figure 3-5 Mounting the Switch on the Table
The device must be installed and operated in the place that can restrict its movement.
3.4 Grounding the Switch
RG-NBS5200 has a PGND on the back panel. First connect the PGND to the grounding lug of the rack and then
connect the grounding lug to the grounding bar of the equipment room.
Precautions
The sectional area of the grounding wire should be determined according to the possible maximum current.
Cables of good conductor should be used.
Do not use bare wire.
The grounding electric resistance should be less than
1Ω.