LFS-PM Series Live Focus System Operating Manual
26
displayed. There may be the following reasons:
Do not do a calibration for a long time or the humidity and temperature has
changed a lot. Do a calibration again to clear this fault.
Part of the sensor has been replaced and installed again. Do a calibration again
to clear this fault.
There are bad connections of the wire. Check the wire connections.
Work piece do not have a good conduction with the shield of the amplifier. Check
the wire to the earth and the wire on the amplifier shield.
Parts of the laser spot are located on the capacity sensor and cause the
temperature rising. Please check the optical path and the optical devices.
5.1.5 Crash Alarm
When the laser head has touched the metal work piece for a certain time, the crash
alarm will be displayed on the displayer. If the laser head do not touch the metal sheet,
there is still crash alarm displayed. There may be the following reasons:
There is a short between the nozzle and the shield of the amplifier.
The axial cable between the amplifier and the capacity sensor is damaged or the
amplifier does not work.
The capacity value of the sensor has been out of the detecting range of the
distance controller.
5.1.6 Emergency Stop
When a low level signal is input to the emergency port, system will stop all the motion
immediately. If the input is keep high level and there is still a emergency triggered, the
following reasons may cause that.
Wrong wiring.
Machine electrical interference. Please check the wiring connection to the
EARTH.
5.1.7 Too Large Following Error
There is big error between the referenced distance and the actual distance of the
laser head. Please modify the filter factor parameters or increase the limit value.
5.1.8 Multiple Error
When there are several alarm triggered at the same time, the multi-alarm information
will be displayed on the displayer. User can go to “Alarm info” to check the alarm
information in detail.