Chapter 6
Certification
RUGGEDCOM RS900L
Installation Guide
26
EMI and Environmental Type Tests
Section 6.4
EMI and Environmental Type Tests
The RS900L has passed the following EMI and environmental tests.
IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity Levels
Enclosure
Contact
+/- 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
+/- 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure ports
20 V/m
x
Signal ports
+/- 4 kV @ 2.5 kHz
x
DC Power ports
+/- 4 kV
4
AC Power ports
+/- 4 kV
4
IEC 61000-4-4
Burst (Fast Transient)
Earth
ground ports
+/- 4 kV
4
Signal ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
DC Power ports
+/- 2 kV line-to-earth,
+/- 1 kV line-to-line
3
IEC 61000-4-5
Surge
AC Power ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
Signal ports
10 V
3
DC Power ports
10 V
3
AC Power ports
10 V
3
IEC 61000-4-6
Induced (Conducted) RFI
Earth
ground ports
10 V
3
IEC 61000-4-8
Magnetic Field
Enclosure ports
40 A/m continuous, 1000 A/m for 1 s
DC Power ports
30% for 0.1 s, 60% for
0.1 s, 100% for 0.05 s
IEC 61000-4-29
30% for 1 period, 60% for 50 periods
IEC 61000-4-11
Voltage Dips and Interrupts
AC Power ports
100% for 5 periods,
100% for 50 periods
Signal ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
DC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
IEC 61000-4-12
Damped Oscillatory
AC Power ports
2.5 kV common, 1 kV
differential mode @ 1 MHz
3
Signal ports
30 V Continuous, 300 V for 1 s
4
IEC 61000-4-16
Mains Frequency Voltage
DC Power ports
30 V Continuous, 300 V for 1 s
4
IEC 61000-4-17
Ripple on DC Power Supply
DC Power ports
10%
3