Chapter 6
Certification
RUGGEDCOM RSG2300
Installation Guide
42
EMC and Environmental Type Tests
Description
Test Levels
Signal Ports
4 kV @ 2.5 kHz
DC Power Ports
4 kV
AC Power Ports
4 kV
Fast Transient
Earth Ground Ports
4 kV
Signal Ports
2.5 kV Common Mode @ 1 MHz
DC Power Ports
2.5 kV Common
1 kV differential mode @ 1 MHz
Oscillatory
AC Power Ports
2.5 kV Common
1 kV differential mode @ 1 MHz
Signal Ports
5 kV (Fail-Safe Relay Output)
DC Power Ports
5 kV
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV
DC Power Ports
2 kV
Dielectric Strength
AC Power Ports
2 kV
Damped Oscillatory
Magnetic Field
Enclosure Ports
100 A/m
Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp Heat, Cyclic)
Test Db
95% (Non-Condensing),
55 °C (131 °F), 6 Cycles
IEC 60068-21-1
Vibration
2g @ 10-150 Hz
IEC 60068-21-2
Shock
30 g @ 11 ms
Содержание RuggedSwitch RSG2300
Страница 4: ...RUGGEDCOM RSG2300 Installation Guide iv...
Страница 10: ...Preface RUGGEDCOM RSG2300 Installation Guide x Customer Support...
Страница 16: ...Chapter 1 Introduction RUGGEDCOM RSG2300 Installation Guide 6 Supported Fiber Optic Cables...
Страница 28: ...Chapter 2 Installing Device RUGGEDCOM RSG2300 Installation Guide 18 Wiring Examples...
Страница 38: ...Chapter 4 Communication Ports RUGGEDCOM RSG2300 Installation Guide 28 Removing a GBIC Optical Port...