Installation
2.6 Console Port Wiring
A RS232 console port for configuration and management of the device is located on the
LED display module shown in Figure 23. This port is intended to be a temporary
connection during initial configuration or troubleshooting and allows for direct access to
the serial-based management console. The connection is made using the DB9-Female
to RJ45 console cable included in the device packaging shown in Figure 24. Console
connection settings are: 57600 baud, no parity bits, 8 data bits, and 1 stop bit.
Figure 23: Console port location on display board
Figure 24: RSG200 Console cable
For user reference, the console cable pin-out is shown in Table 4.
RuggedCom RS232 over RJ45 pin-out specification
Signal Name (PC is DTE)
DB9- Female
RJ45 Male
DCD – Carrier detect
1
2
RxD – Receive data (to DTE)
2
5
TxD – Transmit data (from DTE)
3
6
DTR – Data terminal ready
4
3
Signal GND
5
4
DSR – Data set ready
6
1*
RTS – Ready to send
7
8
CTS – Clear to send
8
7
RI – Ring Indicator
9
1*
Table 4: RS232 over RJ45 console cable pin-out
After initial configuration, the RuggedSwitch device can be configured via a number of
new mechanisms such as Telnet, Secure Shell (SSH) and the built-in web server.
Consult the RuggedSwitch
®
ROS User Guide for further details.
NOTE:
This port is not intended to be a permanent connection and the cable shall be
less than 2m (6.5 ft) in length.