3R110 Plus User Manual

szruitech.com

9

(2) Set the function of the digital input and output port according to the application requirements and
the actual wiring terminals;

(3) Set the motion parameters:

Address

Unit

Parameter Description

70

R/S^2

Acceleration of point motion

72

RPM

Speed of point motion

73

Command

pulse

The number of command pulses for point motion is lower
than the 16-bit register

74

Command

pulse

The number of command pulses for point motion is high
16-bit register

78

R/S^2

Emergency stop deceleration

84

-

Set position operation mode:
0: incremental 1: Absolute

(4) Communication given operation command: start the point movement by writing the values

1

(fixed length forward rotation) and

2

(fixed length reverse rotation) to register 18.(For details on

this register, please see "Driver Control Mode" Set register 18 in [17~23]";

(5)

During operation, if need to stop, please write value

6

(deceleration to stop, deceleration is

the setting value of register 71) and value

5

(emergency stop, deceleration is the setting value

of register 78) to register 18 .

Note:

When the motor is in operation, it only responds to the stop command (deceleration stop or
emergency stop). If it is necessary to change the running direction of the motor by command,
please send the stop command to wait for the motor to stop, and then send the start signal of the
other direction.

The acceleration (register 70), deceleration (register 71), and speed (register 72) are changed
during motor operation, but the driver will not respond to these set values immediately. It will not run
at the set values until the motor is stopped and restarted.

It is important to note that the emergency stop deceleration (Register 78) is responded to during the
current sport emergency stop, without waiting for the next stop of the emergency stop.

7.1.2 Jog control mode

3R110Plus has the function of controlling the jog operation of the motor through communication.The
specific modes and parameters to be set are as follows (register addresses are not specified or
specified as decimal numbers):

(1) Set the value of register address 20 (preset application selection in internal pulse mode) to
0(Communication control, respond to the command of register address 18)

(2) Set the function of the digital input and output port according to the application requirements and
the actual wiring terminals;

Содержание 3R110PLUS

Страница 1: ...3R110 Plus User Manual szruitech com Digital Stepper Driver 3R110PLUS User Manual Shenzhen Rtelligent Mechanical Electrical Technology Co ltd...

Страница 2: ...3 2 3 ALM OUT1 port 4 3 3 USB port 4 4 The setting of DIP switches and operating parameters 5 4 1 The setting of current 5 4 2 Standby current 5 4 3 The setting of pulse per revolution 5 4 4 Pulse com...

Страница 3: ...digital signal input high level can directly receive 24V DC level 1 photoelectric isolation digital signal output maximum withstand voltage 30V maximum input or pull out current 50mA 8 gears can be cu...

Страница 4: ...3 1 Power supply and motor port function description Function Grade Definition Remarks Power supply PE Single phase 220VAC power input AC AC Motor PE Motor PE earth wire Reversing any two wires of U...

Страница 5: ...le IN3 ENA ENA Alarm OUT1 ALM Optocoupler isolation open collector output ALM 3 2 1 PUL DIR port IN1 IN2 By default when operating in external pulse command mode 3R110 PLUS can receive two pulse comma...

Страница 6: ...e motor is in an error state it is automatically turned off The level logic of the enable signal can be set to the opposite At the same time this port can be reused as other functions like IN1 and IN2...

Страница 7: ...the driver is in the enabled state the current remains at the set current SW4 OFF After the driver stops receiving pulses for a certain time it enters the standby state and the current drops to a cert...

Страница 8: ...f 4 4 Pulse command filtering The driver has a built in pulse command smoothing function which can make the motor start more stable SW9 ON enable pulse command filtering SW9 OFF disable pulse command...

Страница 9: ...ase loss alarm function which can detect the phase loss state of the motor during stationary and movement During the operation of the stepper motor due to mechanical reasons the winding wire of the mo...

Страница 10: ...parameters In the absolute position mode the operation state is determined according to the current position and the absolute position set from 70 74 3 Speed mode continuous forward rotation According...

Страница 11: ...e motor is in operation it only responds to the stop command deceleration stop or emergency stop If it is necessary to change the running direction of the motor by command please send the stop command...

Страница 12: ...for the motor to stop and then send the start signal of the other direction The acceleration register 75 and deceleration register 76 are changed during motor operation but the driver will not respond...

Страница 13: ...4 This mode is for the speed defined by the speed table selected by SW5 6 7 8 5 Set the motion parameters you can modify the acceleration deceleration 7 3 IO Control Forward Reverse Same as 7 2 only n...

Страница 14: ...wer supply The position or speed is wrong The signal is disturbed Eliminate interference for reliable grounding The command input is incorrect Check the upper computer instructions to ensure the outpu...

Страница 15: ...ts please follow the procedures shown below 1 Contact our customer service staff to get the rework permission 2 The written document of the Driver failure phenomenon is attached to the goods as well a...