6) 

OVERCURRENT AND SHORT CIRCUIT PROTECTION 

Remote  overload  protection  is  required.  (see  Fig.  7).  [

Integral  solid  state  short  circuit  protection  does  not  provide 

branch  circuit  protection.  Branch  circuit  protection  must  be  provided  in  accordance  with  the  Manufacturer 
Instructions, National Electrical Code and any additional local code

]. 

The protection devices shown infigure 7a and figure 7b must include a branch fuse type: LP-CC-8 by COOPER 
BUSSMAN LCC or equivalent. [

Suitable for Use On A Circuit Capable Of Delivering Not More Than 5000 Arms 

Symmetrical Amperes, 79 Vdc Maximum for all models when protected by semiconductor fuses model LP-CC-8 by 
COOPER BUSSMAN LCC.

7) 

ELECTRO-MAGNETIC INTERFERENCE 

Drive  and  all  related  cabling  are  source  of  E.M.  interference  (conducted  and  radiated).  In  order  to  comply  to  directive 
2004/108/CE  and  related  standards  (EN  61800-3)  installation  has  to  be  done  according  to  schematics  in  Fig  7  and 
following indications: 

 

 

Locate drives, power supply, transformer and related cables inside the same enclosure, which has to be hermetic 
to electromagnetic fields. 

 

Interpose a filter between the transformer primary and the main (CORCOM mod. 6VDK1). Locate the filter near 
the supply entrance. Use only shielded cable (outside the enclosure) for connecting motor and drive. 

 

Connection made to Protective Earth terminal (PE), shown in Fig.7, must be short and have the lowest possible 
inductance. 

 

Use a supply transformer with a metal shield between primary and secondary winding and connect this shield to 
earth. 

8) 

FORCED COOLING 

According to operating conditions (ambient temperature, current setting, duty-cycle) forced cooling can be necessary. The 
most sure method to evaluate if this need exists or not is to measure temperature of the drive heatsink; if this temperature 
is greater than 65 - 70 °C in the most unfavourable working conditions, you need a forced cooling to obtain a reasonable 
long life from drive. 
 

 

Содержание A-NDC 04

Страница 1: ...inimum and maximum value of nominal phase current setting 2 LOGIC INPUT AND OUTPUT SIGNALS connectors AM3 or C2 see Fig 1 7 9 and 10 All inputs and outputs are optically insulated mutually and respect...

Страница 2: ...y common They can be used to connect the shield of logic signal cable if that is mandatory or useful depending on type of control system STEP DIRECTION and CURRENT OFF simplified input structure DRIVE...

Страница 3: ...terminal B 16 Motor winding terminal A 17 Motor winding terminal A 18 Connection point for shield of motor shielded cable 4 MAIN SETTINGS Dip switches and jumpers Main setting must be done by the user...

Страница 4: ...ations Smoothing effect of B type depends on resolution setting the more resolution is low the more smoothing is effective C type current profile performs higher motor torque D type current profile is...

Страница 5: ...der to comply to directive 2004 108 CE and related standards EN 61800 3 installation has to be done according to schematics in Fig 7 and following indications Locate drives power supply transformer an...

Страница 6: ...e right of the drive Do not obstruct air gratings The maximum surrounding air temperature must be lower than 40 C Maximum surrounding air temperature 40 C Installation is allowed in local environment...

Страница 7: ...nsformer power 4 Fuse F2 type LP CC 8 by COOPER BUSSMAN LCC or equivalent Fuse F2 is mandatory for UL compliance 5 Rectifier bridge type according transformer power 6 Terminals 1 10 12 13 and 18 are i...

Страница 8: ...ACKET sold separately L bracket suitable for vertical rail mounting of A NDC 04 A NDC 04 V A NDC 06 and A NDC 06 V KSM01 DIN A KIT BRACKET sold separately L bracket with plastic elements PHOENIX UM SE...

Страница 9: ...from components side without heatsink Dimensions in millimeters CONNECTORS FOR A NDC 04 and A NDC 06 AM1 AMP MODU1 male 6 pole connector mod 280611 2 AM2 AMP MODU1 male 2 pole connector mod 280609 2 A...

Отзывы: