background image

Trademarks 

CompactLogix, ControlLogix, & PLC-5 are registered trademarks of Rockwell Automation, Inc. 
EtherNet/IP is a trademark of the Open DeviceNet Vendors Association (ODVA). 
MicroLogix, RSLogix 500, and SLC are trademarks of Rockwell Automation, Inc. 
Microsoft, Windows, and Internet Explorer are registered trademarks of Microsoft Corporation. 
All other trademarks and registered trademarks are the property of their holders. 

 
Limited Warranty 

Real Time Automation, Inc. warrants that this product is free from defects and functions properly. 
 
EXCEPT AS SPECIFICALLY SET FORTH ABOVE, REAL TIME AUTOMATION, INC. DIS-
CLAIMS ALL OTHER WARRANTIES, BOTH EXPRESSED AND IMPLIED, INCLUDING BUT 
NOT LIMITED TO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A 
PARTICULAR APPLICATION. THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL 
RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS, WHICH VARY FROM STATE TO STATE. 
 
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the 
many variables and requirements associated with any particular application, Real Time Automation, 
Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. Ex-
cept as specifically set forth above, Real Time Automation and its distributors and dealers will in no 
event be liable for any damages whatsoever, either direct or indirect, including but not limited to loss 
of business profits, income, or use of data. Some states do not allow exclusion or limitation of inciden-
tal or consequential damages; therefore, the limitations set forth in this agreement may not apply to 
you. 
 
No patent liability is assumed by Real Time Automation with respect to use of information, circuits, 
equipment, or software described in this manual. 
 
Government End-Users 
If this software is acquired by or on behalf of a unit or agency of the United States Government, this 
provision applies: The software (a) was developed at private expense, is existing computer software, 
and was not developed with government funds; (b) is a trade secret of Real Time Automation, Inc. for 
all purposes of the Freedom of Information Act; (c) is “restricted computer software” submitted with 
restricted rights in accordance with subparagraphs (a) through (d) of the Commercial “Computer Soft-
ware-Restricted Rights” clause at 52.227-19 and its successors; (d) in all respects is proprietary data 
belonging solely to Real Time Automation, Inc.; (e) is unpublished and all rights are reserved under 
copyright laws of the United States. For units of the Department of Defense (DoD), this software is 
licensed only with “Restricted Rights”: as that term is defined in the DoD Supplement of the Federal 
Acquisition Regulation 52.227-7013 (c) (1) (ii), rights in Technical Data and Computer Software and 
its successors, and: Use, duplication, or disclosures is subject to restrictions as set forth in subdivision 
(c) (1) (ii) of the Rights in Technical Data and Computer Software clause at 52.227-7013. If this soft-
ware was acquired under GSA schedule, the U.S. Government has agreed to refrain from changing or 
removing any insignia or lettering from the Software or documentation that is provided or from pro-
ducing copies of the manual or media. Real Time Automation, Inc., 150 S. Sunnyslope Rd. Suite 130, 
Brookfield, WI 53005. 
© 2008 Real Time Automation, Inc. All rights reserved. 

Содержание 460MXE

Страница 1: ...460MXE Gateway User Guide 460MXE Gateway User Guide...

Страница 2: ...forth in this agreement may not apply to you No patent liability is assumed by Real Time Automation with respect to use of information circuits equipment or software described in this manual Governmen...

Страница 3: ...a BACnet IP Client or Ethernet IP Client or DeviceNet Master By following this guide you will be able to configure the 460MXE gateway for basic operation You will set the device s network settings an...

Страница 4: ...Data You will need the following tools The 460MXE Gateway The provided CD ROM A Working PC Windows based The Supplied Ethernet crossover cable A 7 30 VDC power source T strip You will also need to ve...

Страница 5: ...60MXE gateway are for Port 0 T strip to be set for RS485 in cluding power Pin 5 Port 1 DB9 is set to RS232 by default If these default port are not compatible with your equipment they can be configure...

Страница 6: ...0MXE gateway are for Port 0 T strip to be set for CAN while Port 1 DB9 is set to RS485 by default If these default port are not compatible with your equipment they can be configured differently For sp...

Страница 7: ...e to the device 2 Using the crossover cable supplied connect the device to the PC NOTE If you are connecting to the device via a hub or a switch use a standard Ethernet cable 3 Insert the provided CD...

Страница 8: ...1 Open an MS DOS Command Prompt 2 Type ipconfig and press enter 3 Note the IP address The previous example was 192 168 0 1 4 To test the communication between the PC and the unit type ping in the prom...

Страница 9: ...2 Type the desired description into the text box 3 Click Save 4 From the Main Page Click the Edit button with the Application Parameters section 5 Enter a 0 to transfer data to BACnet IP 6 Enter a 1 t...

Страница 10: ...xt box 3 Click Save 4 In the Selected Communication Modules row click Edit 5 In the Modbus row click Edit 6 Verify that the Enabled box is checked 7 Response Timeout is set to 500 ms by default and sh...

Страница 11: ...Master Modules 1 From the Main page click Edit in the Client Module Configuration row 2 There are four options for external devices Eaton IQ 250 260 Power Meter Eaton IQ 130 140 150 Eaton Power Xpert...

Страница 12: ...d Generic Remote Modbus Slave Device button 5 Enter a name for the device in the Device Label field to help distinguish between multiple devices 6 In the Slave address enter the address that correspon...

Страница 13: ...e BACnet device to the Modbus slave 3 The Point Type Data Type values will match those of the Modbus slave device 4 Length is the number of data types to be read It is not the number of registers 5 Cl...

Страница 14: ...t corresponds with your Modbus Slave device s 3 In the Device Name field enter a unique name for the device 4 The Description and Locations fields are optional Filling in the fields is recommended to...

Страница 15: ...net IP Server 1 For the Data Out column do the same as Step 8 except use the correct Output Instance Number Length in bytes and Required Pack Interval in milliseconds 2 Click Save when configuration i...

Страница 16: ...ange the device description on the main page in the Description row click Edit Otherwise skip to step 4 2 Type the desired description into the text box 3 Click Save 4 In the Selected Communication Mo...

Страница 17: ...249 1612 460 Gateway Device Line 460MXE Application Parameters 1 Next Application Parameters click Edit 2 460MXE Mapping will display the connection between the tags file names in your PLC to the BAC...

Страница 18: ...The 460MXE Device Summary and Status page will be shown 3 The device drop down menu allows you to switch between the different devices and display their status 4 Under Show you can choose to show onl...

Страница 19: ...1612 460 Gateway Device Line 460MXE Validating Gateway Communication If the Timeout counter or the Error counter are incrementing or a status of Enabled Not Connected refer to the Troubleshooting Tops...

Страница 20: ...ollow these steps 1 From the Main Page click the Utilities button 2 Click Save Configuration to File 3 Click Save 4 Browse to the location you want to save the file 5 Click OK 6 Remove the first devic...

Страница 21: ...ded location 3 For Bacnet IP or Ethernet IP follow steps 4 6 For DeviceNet skip to step 7 4 Attach the Ethernet cable from the BACnet IP Client Ethernet IP Client to the network port on the 460MXE Gat...

Страница 22: ...ng side of the Gateway unit 3 Remove the green T Strip connector Slide the cover off towards the ports The jumpers are just behind the ports 4 Move the jumper shunts to reflect the desired settings 5...

Страница 23: ...3 4 5 Pin Setting GND CANL SHIELD CANH PWR Port 1 DB 9 RS485 1 2 3 4 5 6 7 8 9 Pin Setting NC TX NC NC GND NC TX NC NC Port 0 T Strip CAN 1 2 3 4 5 Pin Setting GND CANL SHIELD CANH PWR Port 1 DB 9 RS...

Страница 24: ...Real Time Automation Inc 150 South Sunny Slope Road Suite 130 Brookfield WI 53005 Toll free 1 800 249 1612 Local 262 439 4999 www rtaautomation com support rtaautomation com...

Отзывы: