Flashing Red (Empty Scan List) - One or more enabled Modbus TCP servers have no scan lines
configured.
6)
Flashing Red (Communication not attempted yet)
–
(Specific server only) No reads are configured
and data needed for writes isn’t valid yet.
7)
Flashing Red (Dependency Error) - The dependent protocol is missing causing the communication to
go to inactive.
a)
The other protocol must be
Connected
.
8)
Off
–
The Ethernet cable is not connected to the gateway or there is no power to the gateway.
Variables
- These are the values for
All Servers,
or the specific server selected.
1)
Network Bitmap Status (Displayed in Hex):
a)
Each bit corresponds to a server. If the bit is set, the server is connected, otherwise the bit is 0.
b)
Bit 0 corresponds to server 1 and Bit 4 is for server 5 and so on.
2)
FC01 Read Coil Status:
a)
Function Code 1: Number of read Coil Status requests sent
b)
Point Type Used: 0x Coil Status
c)
# of Points: Any
3)
FC02 Read Input Status:
a)
Function Code 2: Number of read Input Status requests sent
b)
Point Type Used: 1x Input Status
c)
# of Points: Any
4)
FC03 Read Holding Registers:
a)
Function Code 3: Number of read Holding Register requests sent
b)
Point Type Used: 4x Hold Reg
c)
# of Points: Any
5)
FC04 Read Input Registers:
a)
Function Code 4: Number of read Input Register requests sent