Real Time Automation, Inc.
63
1-800-249-1612
LED Status
1)
Solid Green (Connected): The gateway is connected to an EtherNet/IP scanner and communicating
as expected.
2)
Flashing Green (Not Connected): The EtherNet/IP scanner has never attempted to initiate
communication to the gateway.
3)
Flashing Red (I/O Timeout): The gateway has lost a connection to the EtherNet/IP scanner.
4)
Solid Red: N/A
5)
Off:
a.
No power.
b.
No Ethernet cable plugged in.
Variables
1)
I/O Connections: Number of Class 1 Implicit Connections open
Note:
This does not include Listen Only
2)
I/O Input Msgs Sent: Number of messages sent to the scanner
Note:
Sum of all connections
3)
I/O Output Msgs Received: Number of messages received from the scanner
Note:
Sum of all connections
4)
I/O Heartbeat Msgs Sent: Number of heartbeat messages sent to the scanner (Used with Output
Only)
Note:
Sum of all connections
5)
I/O Heartbeat Msgs Received: Number of heartbeat messages received from the scanner (Used with
Input Only and Listen Only)
Note:
Sum of all connections
6)
EIP Sessions: Number of Encapsulation Sessions open (used with UCMM and Explicit)
7)
UCMM Messages: Number of UCMM Messages received (it is assumed we always respond, the log
can detect dropped packets)
Note:
Sum of all connections
8)
EM Connection: Number of Class 3 Output Connections open