Real Time Automation, Inc.
66
1-800-249-1612
7)
Solid Red (Empty Scan List) - One or more enabled BACnet MS/TP slaves have no scan lines
configured.
a)
Verify there are scan lines configured for devices that are enabled.
8)
Solid Red (No Serial Port Configured)
–
Port configured in the BACnet MS/TP master configuration
page is not enabled in the Port Configuration page.
Variables
- These are the values for
All Slaves,
or the specific slave selected.
1)
Network Bitmap Status (Displayed in Hex):
a)
Each bit corresponds to a slave. If the bit is set, the slave is connected, otherwise the bit is 0.
b)
Bit 0 corresponds to slave 1 and Bit 4 is for slave 5 and so on.
2)
RD Prop Request
–
Number of Read Property Single requests sent to the BACnet MS/TP devices.
a)
NOTE
: Read Property Single Requests are only used if the BACnet MS/TP device does not
support Read Property Multiple (RPM).
3)
WR Prop Request
–
Number of Write Property Single requests sent to the BACnet MS/TP devices.
a)
NOTE
: Write Property Single Requests are only used if the BACnet MS/TP device does not
support Write Property Multiple (WPM).
4)
RD Prop Multiple Request
–
Number of Read Property Multiple requests sent to the BACnet MS/TP
devices.
5)
WR Prop Multiple Request
–
Number of Write Property Multiple requests sent to the BACnet MS/TP
devices.
6)
RD/WR Response Success
–
Number of successful read or write responses received. This value
should be equal to RD WR RD Mu WR Multiple Variable Counts.
7)
RD/WR Response Error
–
Number of read or write error responses received.
a)
NOTE
: If the gateway receives an error of Unsupported Service for a RPM or WPM request, then
RP/WR Single requests will be used for that device for the duration of that power up.
8)
RD/WR Timeout
–
Total number of read/write requests sent to the BACnet MS/TP device with no
reply received within the response timeout configured.
9)
# of Object Read Attempts
–
Total number of objects that the gateway attempted to read.
10)
# of Object Write Attempts
–
Total number of objects that the gateway attempted to write.
Status Strings
-
These are the values for
All Slaves,
or the specific slave selected.
1)
Last Error Code:
a)
Last read/write reply error that the gateway received
Error Code Breakdown
: