8.  Under the 

Status

 tab, check to make sure the parameters are correct and 

that the logger is either 

logging 

or there is a 

log pending

 under the 

Sampling

 

section. 

9.  Click 

Disconnect

 button to terminate logger connection. 

10. Exit the software and disconnect the communication cable. 

11. The data logger should now be taking readings. Return to the logger to 

download the data. Check the remaining battery life every time you connect. 
The battery state is an approximate value based on recent battery use. 

4.4 

D

OWNLOADING 

D

ATA

 

1.  Connect the communication cable to your computer and the DT2485 and 

launch the software. If the connection is successful, the port and status 
indicators turn green and the 

Status

 screen should display logger 

information. 

2.  Press the 

Collect Data

 button on the 

Status 

tab to download the data. A data 

file (*.csv) will automatically be created in the data directory. The default data 
directory is: 

My Documents\Multichannel\

 

3.  Before downloading, the program will ask whether you would like to erase 

the existing data on the logger or keep appending to existing records. To 
erase the old data and continue logging with the same parameters, select 
the 

Logging 

tab and press 

Apply Settings.

 

4.  To keep the old data on the logger and continue logging, exit the program, 

and disconnect the communication cable. 

5.  To change any logging parameters, do so under the 

Logging

 tab and press 

Apply Settings 

to save the changes. 

6.  Disconnect the communication cable when finished. 

4.5 

H

ELP 

S

YSTEM

 

An extensive help system in DT Logger Host can be activated anytime by pressing 
F1 or the RST icon. Answers to common problems and troubleshooting tips can be 
found by browsing help topics or searching using keywords. 

 

C

AMPBELL 

L

OGGER 

Q

UICK 

S

TART 

U

I

NSTRUCTIONS 

 

The following is a brief outline to update the Modbus addresses of IPI sensors in a 
string with a CR6 or CR310 Campbell logger. Before  

5.1 

H

ARDWARE 

R

EQUIREMENTS

 

  Campbell Logger 

o

  CR6 

Содержание MEMS IPI 4

Страница 1: ...his document RST Instruments Ltd reserves the right to change the information at any time and assumes no liability for its accuracy Copyright 2020 RST Instruments Ltd All rights reserved Document Numb...

Страница 2: ...ICM0095B RST Instruments Ltd Page i REVISION HISTORY Rev Revision History Date Prepared By Approved By A Initial release 2020 Nov 13 MP BN B Added instructions for Campbell CR6 and CR310 loggers DT L...

Страница 3: ...R QUICK START UP INSTRUCTIONS 9 5 1 Hardware Requirements 9 5 2 CR6 Wiring 10 5 2 1 Updating the Modbus Addresses With a CR6 10 5 2 2 Code for CR6 12 5 3 CR310 Wiring 14 5 3 1 Updating the Modbus Addr...

Страница 4: ...ger using C1 and C2 14 Figure 5 10 Select CRBasic editor under the Program menu 15 Figure 5 11 CR300 Series Program icon 15 Figure 5 12 Compiling and saving the code in the CRBasic editor 16 Figure 5...

Страница 5: ...To ensure that all components are working together correctly and able to communicate RST recommends that initial set up and configuration take place in the office or warehouse prior to final installa...

Страница 6: ...of each sensor and its order in the string from the top to the bottom of the string Connect the IPI string to the desired data logger following the wiring scheme outlined in Table 2 1 CAUTION IT IS C...

Страница 7: ...ehouse installation in the field will be straightforward See ICM0062 for detailed instructions 2 2 1 Cleaning Connectors Keep caps on connectors Figure 2 3 until mated to the next sensor to prevent co...

Страница 8: ...RE DT2485 logger or Campbell Logger o PC with LoggerNet and o RST ELGL4000 Interface if using CR310 3 2 PC HARDWARE Desktop or laptop with Intel or AMD processor USB port 3 3 WINDOWS HOST OPERATING SY...

Страница 9: ...sion The current version can be downloaded from https rstinstruments com resources software Navigate to the site and select the appropriate data logger 2 Follow the on screen instructions to install t...

Страница 10: ...Once the software connects to the logger the port and status indicators will turn green and the Status screen should display logger information 3 Navigate to the DTBus tab to configure the IPI sensors...

Страница 11: ...o the string Insert a sensor to the current position in the string Change communication between ASCII and Modbus Remove the currently displayed sensor from the string or remove all sensors Add specifi...

Страница 12: ...the Upload to Logger button to apply the changes Click Yes when asked to update Modbus Addresses 6 Wait for update process to finish The logger is now logging data 7 If desired real time sensor readi...

Страница 13: ...ile csv will automatically be created in the data directory The default data directory is My Documents Multichannel 3 Before downloading the program will ask whether you would like to erase the existi...

Страница 14: ...ses on the IPI string ensure that all settings have been saved on the logger unit Modbus addresses for sensors connected to a Campbell CR6 logger can be updated via a CRBasic code Once the user has de...

Страница 15: ...will depend on the type of logger that will be used 6 Update the number of IPIs and the serial number of each IPI in the code in order of installation or planned installation 7 Compile the code and th...

Страница 16: ...l LoggerNet instructions for ensuring current settings have been saved 12 Select Send New on the right hand side of the screen and open the saved CRBasic code from Step 7 13 Click on Start Running 14...

Страница 17: ...nsors per string EndTable Main Program BeginProg Open serial port SerialOpen ComC1 9600 0 0 128 4 SerialFlush ComC1 Guard against serial number error causing incorrect data SerialOut ComC1 65534 MBA 2...

Страница 18: ...gure 5 9 FIGURE 5 9 WIRING SCHEMATIC FOR AN IPI SYSTEM TO THE CR310 LOGGER USING C1 AND C2 5 3 1 Updating the Modbus Addresses With a CR310 Before updating the Modbus addresses on the IPI string ensur...

Страница 19: ...Ensure that any existing settings have been saved 5 Remove the template code and paste the code see Section 5 3 2 into the editor The appropriate code will depend on the type of logger that will be u...

Страница 20: ...COMPILING AND SAVING THE CODE IN THE CRBASIC EDITOR 8 If the compilation was successful the following message will appear at the bottom of the window FIGURE 5 13 SUCCESSFUL COMPILATION MESSAGE 9 Close...

Страница 21: ...ct Send New on the right hand side of the screen and open the saved CRBasic code from Step 7 13 Click on Start Running 14 The Modbus addresses for the sensors on the IPI string will now be updated 5 3...

Страница 22: ...in interface banner set mode on program run continuous reading mode SerialOut Com1 MODE 0 CHR 13 1 0 SerialIn interface_banner Com1 200 CHR 13 100 Delay 0 1 Sec SerialFlush Com1 Guard against serial n...

Страница 23: ...nts Ltd 19 6 INSTALLATION Refer to the MEMS Digital In Place Inclinometer System Instruction Manual ICM0062 for detailed installation instructions 7 SERVICE AND REPAIR This product contains no user se...

Отзывы: