background image

OPEL PLUS KEYSTONE Owner's Manual 

11 

RSF Woodburning Fireplaces 

stoves, there is no need to cure the fireplace itself by starting with small fires and progressively larger ones. Feel 

free to light a large fire from the very start.  
You will experience a slight odor during the first few fires. This odor comes from curing paint and oil burning off the 

metal. The odor may be strong enough to set off your smoke detector. Open the doors and windows to allow the 

room to properly ventilate. 

 

LIGHTING 

Ensure that the catalytic bypass is open (pulled all the way out) 

while starting a fire (see Figure 3).  Leave it open until the fire 

is hot (approx. 15-30 minutes). 
Ensure that the combustion air control lever is all the way to the 

right in the open position. You will want as much air as possible 

for the lighting process. 
Start  by  laying  your  fire  starter  and  kindling.  Traditional  fire 

starter is crumpled newspaper;  make sure to use  enough to 

light the kindling (5-6 pieces should do). Next lay the kindling 

crisscrossed  over  the  newspaper.  Using  plenty  of  kindling 

ensures that the chimney will heat up quickly and establish a 

strong  draft, 

never  use  any  flammable  liquids

.  Light  the 

paper  and  close  the  door  most  of  the  way,  but  don’t  shut  it 

completely. If the door is positioned correctly you will see air 

rushing into the fireplace, this will help the lighting process. 
Once the kindling is lit and sustaining fire, you can add some 

small pieces of seasoned cordwood. Use the andirons in front 

to help position the cordwood so as not to flatten and smother the fire you’ve just created. Always add at least 3 

pieces of cordwood. Position your cordwood in a manner that the fire will hit several pieces as it rises and has air 

gaps to flow through. Continue to leave the door slightly open until the cordwood is lit. Close the door completely 

when the fire is established, if the fire goes out you’ve shut the door too early. 

 

 WARNING: DO NOT USE A GRATE OR ELEVATE THE FIRE. 

 WARNING: MAKE SURE TO KEEP THE FIRE BEHIND THE ANDIRONS. REPOSITION THE LOGS IF THEY 

FALL AGAINST THE GLASS. 

ENGAGE THE CATALYST 

When the fire is hot, you should always engage the catalyst. To engage the catalyst, simply push the bypass handle 

all the way in so that the bypass damper is closed. Closing the bypass will force the smoke through the catalyst.  

When the catalyst is engaged you will receive more heat from your fireplace, and it will burn much more cleanly. 
The catalyst should not be engaged (bypass closed) unless the fireplace is hot. If the bypass is closed before the 

fireplace is hot, the catalyst will get dirty and no extra heat will be generated. The catalyst must be at least 175°C 

(350

°

F) before it will start to burn off the wood smoke. Typically, this requires the fire to be lit for 15 to 30 minutes. 

CATALYST TEMPERATURE PROBE 

For  an  exact  temperature  reading  at  your  catalyst,  your  fireplace  is  equipped  with  a  temperature  probe  which 

measures the temperature within 1" of the catalyst. A wire and connector have been dropped down on the left side 

of the fireplace, inside the casing. You can connect to the probe with our optional Digital Temperature Display (FO-

DTD) or any standard Type K Thermocouple/Sensor Thermometer. 
For an accurate temperature reading the bypass must be closed. Here are the important temperature ranges that 

you need to be aware of: 

  Below 175°C (350°F): not enough heat is generated from the fire, add more wood, open the air control and 

keep the bypass opened. 

  Between 175°C (350°F) and 700°C (1300°F): the temperature is just right for the catalyst, add more wood as 

necessary and keep the bypass closed except for reloading. 

 

Figure 3 Bypass Handle 

Содержание OPEL+ KEYSTONE

Страница 1: ...dential Factory Built Fireplace Operation Maintenance Installation OPEL PLUS KEYSTONE Keep these instructions for future use Industrial Chimney Company Inc 400 J F Kennedy St Jerome QC Canada J7Y 4B7 Telephone 450 565 6336 www icc rsf com ...

Страница 2: ...LYTIC COMBUSTOR 4 OPTIONS 4 UNIT DIMENSIONS AND CLEARANCES 7 OPERATION 9 AIR CONTROLS 9 IMPROVING EFFICIENCY 10 IMPORTANCE OF DRAFT 10 BURN TIME VS HEAT OUTPUT 10 FUEL 10 FIRST FIRES 10 LIGHTING 11 ENGAGE THE CATALYST 11 CATALYST TEMPERATURE PROBE 11 ADJUSTING THE BURN RATE 12 REFUELING 12 TROUBLESHOOTING PROBLEMS 12 MAINTENANCE 13 CATALYTIC COMBUSTOR 13 REPLACING THE CATALYST 13 CHIMNEY CLEANING ...

Страница 3: ... fireplace If you are unable to slow down the burning rate of the fire or if the chimney connector behind the top louver glows red you are overfiring the fireplace 10 DO NOT use a fireplace grate or other products not specified for use with this fireplace 11 The burn rates are set by the semi automatic air control at the factory DO NOT tamper with the air control DO NOT install a flue damper that ...

Страница 4: ...L KEYSTONE s draft control This control has a bimetal coil to allow more air when the unit is cold and less air when the unit is hot guarding against overheating It can be controlled either manually with the lever that is located on the right below the door or automatically with an optional electric wall thermostat For the first few days it is best to operate the fireplace with the manual control ...

Страница 5: ...automatic control of the Central Heat Blower via a wall thermostat and thermal switch The Zone Heat Control FO FDHCZ1 along with Zone Damper Kits FO FDHCZ2 will provide the same features as the Central Heat Control but for more than one heating zone If you wish to install the Central Heat Blower on a Clean Face OPEL KEYSTONE you will need the Central Heat T FO T that will enable you to connect the...

Страница 6: ...can also be obtained from our Internet Web Site www icc rsf com WARNING THIS FIREPLACE HAS NOT BEEN TESTED WITH AN UNVENTED GAS LOG SET TO REDUCE RISK OF FIRE OR INJURY DO NOT INSTALL AN UNVENTED GAS LOG SET INTO THIS FIREPLACE DO NOT INSTALL A GAS LOG LIGHTER BECAUSE THE HEAT PRODUCED BY THE FIREPLACE WILL PERMANENTLY DAMAGE THE GAS LOG LIGHTER ...

Страница 7: ... firebox opening 26 3 8 Without the Keystone top louver With Keystone top louver Figure 1 Unit Dimensions and Clearances Refer to Table 1 J for maximum mantel depth Refer to Table 1 K for minimum mantel height above the firebox opening Refer to Table 1 H for minimum width of hearth extension Refer to Table 1 G for minimum depth of hearth extension Non combustible hearth extension and spark guard r...

Страница 8: ... chimney height from fireplace top to below the chimney rain cap 12 3 66 m E Maximum chimney height maximum total chimney height from fireplace top to below the chimney rain cap 40 12 19 m F Maximum chimney height supported by the fireplace 18 5 47 m G Minimum depth of non combustible hearth extension from the front of the fireplace 18 457 mm H Minimum width of non combustible hearth extension tot...

Страница 9: ...S Unlike most open fireplaces RSF fireplaces don t have flue dampers Instead the system is sealed by closing the door and the amount of air entering the firebox is controlled by the combustion air control lever on the front of the fireplace on the right below the door see Figure 2 which can be moved up or down Setting the air control lever all the way open up will allow the maximum amount of air i...

Страница 10: ...on See Table 3 for minimum chimney height recommendations BURN TIME VS HEAT OUTPUT The faster your fireplace burns the more heat it will create however faster fires result in much more hot air flow up the chimney which means you are sacrificing efficiency Fast burning fires lots of air go through much more wood than slow burning fires To get the most out of your OPEL KEYSTONE fireplace adequately ...

Страница 11: ...s to flow through Continue to leave the door slightly open until the cordwood is lit Close the door completely when the fire is established if the fire goes out you ve shut the door too early WARNING DO NOT USE A GRATE OR ELEVATE THE FIRE WARNING MAKE SURE TO KEEP THE FIRE BEHIND THE ANDIRONS REPOSITION THE LOGS IF THEY FALL AGAINST THE GLASS ENGAGE THE CATALYST When the fire is hot you should alw...

Страница 12: ...urnt wood that is left in the firebox This will help revive the fire Place the new logs in the firebox Try to maintain a clear path in front of the pilot which is the metal tube centered between the two andiron posts The pilot brings an influx of air close to the coals that will help to keep the fire going Once the new wood has been loaded keep the door slightly ajar for about 3 10 minutes to get ...

Страница 13: ... Enough gasket is supplied to wrap the catalyst with two layers of the gasket material Carefully insert the catalyst into the opening and reinsert the screws that hold it in place The catalyst gasket expands as it is heated so it is normal for the gasket to have some small gaps after being inserted As the gasket expands the spaces will be filled CHIMNEY CLEANING Check the chimney for creosote buil...

Страница 14: ...ost of the deposits that have accumulated Remember the drier the wood and the hotter the fire the cleaner the glass A word of caution although heat will not break the glass impact can Be careful not to hit the glass WARNING NEVER CLEAN THE GLASS WITH AN ABRASIVE CLEANER USE ONLY A CLEANER RECOMMENDED BY YOUR DEALER NEVER CLEAN THE GLASS WHILE IT IS HOT A SERIOUS BURN CAN RESULT THERE ARE A NUMBER ...

Страница 15: ... available from your RSF dealer The OPEL KEYSTONE Door cannot be adjusted to tighten the door seal The gaskets must be replaced when necessary to resolve the issue NOTE An improper door seal can have a significant effect on the performance and durability of the fireplace An air leak can result in reduced efficiency over firing excessive wood consumption and premature catalyst and fireplace failure...

Страница 16: ...options before beginning the actual installation refer to Figure 7 and Figure 8 Dimensions of the fireplace along with clearances are shown in Figure 1 and Table 1 WARNING IF THIS FIREPLACE IS NOT PROPERLY INSTALLED A HOUSE FIRE CAN RESULT FOR YOUR SAFETY FOLLOW THE INSTALLATION INSTRUCTIONS AND CLEARANCES DO NOT PACK REQUIRED AIR SPACES WITH INSULATION OR OTHER MATERIALS 1 Note the location of ro...

Страница 17: ... framing dimensions are larger than required for ease of installation Examples shown here are for a Louvered OPEL KEYSTONE The Heat Dump Option will also require an extra 12 on the selected side Figure 6 Louvered OPEL KEYSTONE Framing Examples 53 1 4 39 24 82 38 58 18 ...

Страница 18: ... Shield with a Storm Collar in the Attic Ceiling Radiation Shield Hearth Extension and Beneath Hearth Extension refer to text for particulars Outside Air Inlet refer to text for particulars WARNING The wall surface directly above the fireplace must be non combustible grayed area see Table 1 L and text for particulars Cold air trap optional Electrical and Gas Knock Outs Flashing And Roof Radiation ...

Страница 19: ...ing Radiation Shield with a Storm Collar in the Attic Ceiling Radiation Shield Hearth Extension and Beneath Hearth Extension refer to text for particulars Outside Air Inlet refer to text for particulars Cold air trap optional Electrical and Gas Knock Outs WARNING The wall surface directly above the fireplace must be non combustible grayed area see Table 1 L and text for particulars Gravity Vent Op...

Страница 20: ...g the fireplace to the crate attach the casing or base of the fireplace to the floor Position the brackets all around the fireplace in the same fashion as they were on the crate If possible try to have at least one of the brackets screwed into the floor joist with 2 wood screws FRAMING The enclosure walls can be framed with any suitable materials 2x4 or 2x6 studs plywood gypsum board etc Because o...

Страница 21: ...level Every 15 30 or 45 offset one pair of elbows also increases the minimum height See Table 3 for more precise recommended flue heights For example if you are living 6015 above sea level your chimney should terminate at least 15 from the top of the fireplace if it is a straight chimney or at least 18 6 if one 30 offset is used as shown in Table 3 Table 3 Minimum Recommended Flue Height Elevation...

Страница 22: ...aside Install the flue adapter on the first chimney length and secure it with the screws provided Reinstall the flue adapter on the fireplace and secure it with the screws you have put aside earlier Assemble the rest of the chimney The chimney must extend at least 3 above its point of contact with the roof and at least 2 higher than any wall roof or building within 10 of it If the chimney is highe...

Страница 23: ...en it to the other section with 3 metal screws at the joints 2 Install enough lengths to obtain the desired offset Secure each joint with 3 metal screws 3 Use another elbow to return the chimney to the vertical direction 4 Install a wall support or an offset support above each offset to support the weight of the chimney elbows are not designed to support the chimney above an offset Refer to the te...

Страница 24: ...ront of the fireplace REMEMBER Check local codes concerning installation requirements and restrictions in your area MASONRY CHIMNEY Installing your OPEL KEYSTONE fireplace with a masonry chimney still requires using EXCEL chimney from the top of the fireplace to the wall where it will connect to a listed liner that will run up inside the masonry chimney see Figure 15 The stainless steel liner shou...

Страница 25: ...hind the brick because three sides of it must stay in place 3 Bring the stainless steel liner down from the top of the chimney If you are using a rigid liner you will need enough room to secure an elbow to it with at least two screws If it is difficult to install rigid stainless steel liner in the existing masonry chimney or for a masonry chimney with less than 10 x10 inside a listed stainless ste...

Страница 26: ...ENSION If the OPEL KEYSTONE is installed on a non combustible floor the spark guard specified below is not required Install the spark guard provided 5 x 36 piece of sheet metal halfway under the fireplace and halfway under the hearth extension and centered on the door opening The spark guard will extend 2 beneath the fireplace This will make certain that sparks cannot lodge in this area and start ...

Страница 27: ...e non combustible Combustible mantel posts are not permitted unless they meet the clearance required to a perpendicular sidewall see Table 1 B The only combustible material accepted below the minimum clearance for combustible materials above the fireplace see Table 1 L is for a mantel shelf REFRACTORY BRICKS INSTALLATION The refractory bricks come pre installed These instructions show the order fo...

Страница 28: ...is in its installation instructions and if the required clearances are met To convert the OPEL KEYSTONE please carefully follow the following steps 1 There is a 1 hole on both sides of the fireplace about 9 up from the bottom of the fireplace The gas line must come into the fireplace through one of these holes Choose the side of installation that is more convenient to you 2 There are a few parts t...

Страница 29: ...llation instructions Make sure also to respect all clearances stated by the gas log manufacturer WARNING THE MAXIMUM GAS OUTPUT ALLOWED IN THE OPEL KEYSTONE IS 35 000 BTU THE GAS LOG HAS TO BE LISTED TO ANSI Z21 60 CSA 2 26 THE COMBUSTION AIR CONTROL MUST BE FULLY OPEN WHEN THE GAS LOG IS FUNCTIONING When operating an OPEL KEYSTONE with a gas log installed make sure to follow the gas log manufactu...

Страница 30: ... PLUS KEYSTONE Owner s Manual 30 RSF Woodburning Fireplaces LISTING LABEL The listing label is glued to the bottom of the fireplace Just remove the bottom louver the listing label is below the floor shield ...

Страница 31: ...OPEL PLUS KEYSTONE Owner s Manual 31 RSF Woodburning Fireplaces COMPLETE OPTIONS LIST ...

Страница 32: ...OPEL PLUS KEYSTONE Owner s Manual 32 RSF Woodburning Fireplaces ...

Страница 33: ...at kit must be installed before facing and must be accessible for servicing FO FDHC4 Heat Dump Kit FO HD Rock Retainer Kit FO KK Central Heat T Option FO T Louvered OPEL KEYSTONE Required Optional Not available Opel Keystone Top Louver FO OPLK Ash Pan Kit FO AP Blower Internal FO FDHB5 N Blower Central Heat FO FDHB6 1 Thermostat kit FO FDHC4 Heat Dump Kit FO HD Rock Retainer Kit FO KK Gravity Vent...

Страница 34: ...OPEL PLUS KEYSTONE Owner s Manual 34 RSF Woodburning Fireplaces REPLACEMENT PARTS Will be available soon Contact your RSF dealer for information ...

Страница 35: ...l loads or failure to adequately service the unit as stated in the owner s manual Repairs or replacements particularly charges for travel and labor not authorized by RSF Woodburning Fireplaces in advance LIMITATIONS All items found to be defective will be replaced or repaired upon return of the defective part to an authorized RSF Woodburning Fireplaces dealer RSF Woodburning Fireplaces will not be...

Страница 36: ...dburning Fireplaces This warranty is expressly in lieu of all other warranties expressed or implied including the warranties of merchantability and fitness for use and all other obligations or liabilities on the part of RSF Woodburning Fireplaces ...

Отзывы: