background image

GOLD LOUVERS (FD-LD) 

The standard black louvers above and below the doors can
be replaced with a gold plated set.  You may order these
from your dealer.  

Dismantling and assembling louvers

For the following refer to (Figure 22):

1. The louvers are held in place by springs underneath.
Therefore,  to  remove,  push  down  from  the  top  and  pull
the top of the louvers forward.

2. Take the assembly apart by removing the top nuts from
the rods. Leave the bottom nuts and spring assemblies
on the ready rod.

3. Assemble  the  louvers  the  same  way  the  black  ones
came  apart,  reusing  the  original  rods,  spacers  and
springs. There should be about 1/4" of the rod protruding
above the top nut. 

4. Put the reassembled louvers back into the fireplace by
inserting the rods into the lower holes, and pushing the
louvers into place.

Warning:

Be sure to replace the heat shield behind the

top centre louvers the same way it was removed. Failure
to do this may result in a fire hazard (see Figure 22).

IMPORTANT!

Before  you  light  the  first  fire  after  you

have installed the new louvers, you must wipe all finger-
prints and dirt off the gold plating.  The gold louvers have
been coated with a silicone substance that will seal to the
gold louvers during the first fire.  If you do not wipe off the
gold plating, the acid from your fingerprints or other sub-
stances will permanently etch the gold plating.

NOTE:  Although the gold plating will not tarnish, care
must be taken not to scratch the surface.

DELTA ROCK RETAINER KIT (FD-KD) 

Facing

Facing  material  may  only  be  non-combustible  such  as
metal, brick, rock, concrete board, or ceramic tile.  Gypsum
board is NOT an acceptable facing material.

Warning:    DO  NOT

restrict  air  flow  through  the  inlet  and

outlet louvers of the fireplace.

If you desire to fully face the fireplace with soldiering brick,
it is recommended that you purchase the rock retainer kit
(part FD-KD-1) to help keep the facing in place.  It is NOT
recommended for brick or other self-supporting materials.
Follow these steps:

NOTE:  Remove the fireplace doors and louvers, and store
them  in  a  safe  place  until  the  masonry  work  is  finished.
Acid from the cleaning operation will permanently damage
the  gold  plating.  Ensure  that  the  cover  remains  over  the
right door.

NOTE: The louvers have two sets of mounting holes. Use
the rear set when there is no facing added to the fireplace
and use the front set when a facing has been added. This
is a cosmetic recommendation only.

Installation

1.  Start  by  installing  the  top  centre  expanded  metal  flush
and centred with the top centre louver opening. (It is rec-
ommended  that  you  just  clamp  the  centre  piece  in  place
until the sides are lined up)  Next install the right and left
expanded metal by aligning the edging and the mesh to the
centre piece and the side louver openings. Now install the
lower  arch  centre  above  the  door  aligning  it  to  the  side
pieces (see Figure 23). 

NOTE: When using wider lintel bar for heavier rock, make
sure that you have enough room to open the door wide.

2. Cover any remaining area which you wish to put facing
material on with wire mesh, or metal lath, overlapping the
heavy  expanded  metal.    Make  sure  nails  or  staples  used
for fastening mesh penetrate the studs at least 1".

3.  Mortar  must  be  "thin  set"  or  "thin  bed"  type,  inherently
polymer  modified.  Do  not  add  water  to  the  mixture  (this
applies to the grout as well). If the mortar is not modified,
you  should  add  a  synthetic  latex  additive.  Mix  to  a  firm,
moist consistency.  

4.  Using  a  plasterer’s  or  mason’s  trowel,  apply  a  scratch
coat that covers the wire mesh.  Let the mortar set before
adding  another  coat.    This  will  take  several  hours.
Afterwards,  apply  a  thinner  coat  and  the  facing.    Do  not

Page 17

DELTA

rod

top nut

louver

heat shield
(center top louver
set only)

spacer

bottom nut

spring assembly

Figure 22  :  Louver assembly

Содержание DELTA

Страница 1: ...Keep these instructions for future use Owner s Manual Residential Factory Built Fireplace Operation Maintenance Installation Delta 01 03 The DELTA ...

Страница 2: ...it 19 Remote Venting 19 The Gravity Vent System 21 The Central Heat System 24 Zone Heating WIRING DIAGRAMS 26 Zone Heat System 27 Thermostat 27 Circulating Blower 27 Central Heat System 27 All Systems Combined REPLACEMENT PARTS LIST 28 Replacement Parts List LABEL 29 Label WARRANTY 30 Warranty Page 2 Dear Customer The Delta incorporates technology with elegance to give you a beautiful view of the ...

Страница 3: ... fire The chimney must be inspected periodically during the heating season to see if a creosote buildup has occurred If a significant layer of creosote has accumulated 1 4 or more it should be removed to reduce the risk of chimney fire Warning burn seasoned wood only Do not burn driftwood treated wood coal garbage plastic Do not use construction scraps e g 2x4 or plywood scraps as your only supply...

Страница 4: ...it takes air from the room the Delta is in draws it around the fireplace and distributes it see Options Central Heating System parts FD HC6 FD HB6 NOTE The blower part FD HB6 can push warm air either up or down and can also be zone controlled see Options Zone Heating and diagrams HINT If some evening you would like to enjoy the ambi ence of the wood flame but you are a little too warm turn up the ...

Страница 5: ...ver the pins can be turned so that the doors seal well and fit with each other After adjustment tighten the Allen screws holding the hinge pins in place with the screwdriver and replace the door If the left side door fits correctly and the front door does not pass the paper test then the angle bracket needs to be adjusted Loosen the four screws that are attached to the centre door and slightly adj...

Страница 6: ...pipe This can be done by removing the cotter pin from the top right side of the secondary air pipe and sliding the pipe as far as it goes to the left Then when the right side drops out of its hole slide it to the right until the other side drops To remove the baffle push up and slide it off the brackets Replace both as you removed them and be sure the holes on the secondary air pipe are facing tow...

Страница 7: ...onents for gravity system central heat blower framing guide standoff gravity vent damper handle Hearth extension radiation shield ceiling clearance 39 min 84 from base to the ceilling fresh air hood at floor level For other installation options see figure 7 electrical knockouts Figure 2 General assembly ...

Страница 8: ...between the two forks before using STANDOFF INSTALLATION Before installing your Delta the side nailing strips need to be assembled as follows 1 Remove the nailing strips from the top of the unit 2 Remove the four 4 metal screws on each side of the Delta facing 3 Attach the nailing strip to the side of the Delta using the metal screws that you removed in Step 2 Figure 4 NOTE When using the optional...

Страница 9: ...lexible pipe must be used 1 Use the side or back outside air outlet 2 Find a convenient location for the combustion air duct and intake air hood The location of the intake air hood may be above or below floor level see Figure 7 Under no circumstances should the combustion air inlet be placed in attic spaces 3 Make a 4 1 4 5 1 4 if using a 5 diameter duct hole in the outside wall of the house Mount...

Страница 10: ...r above the radiation shield as shown in Figure 8 3 Place the first chimney length on the fireplace Secure the chimney length to the fireplace with the three screws provided The chimney must extend at least 3 ft above its point of contact with the roof and at least 2 ft higher than any wall roof or building within 10 ft of it Refer to the Excel instruc tion installation flue height requirements fo...

Страница 11: ...heat loss If the climate in your area is mild insulate the chase at least to the first firestop If the climate in your area is very cold insulate the chase to the top to keep the flue warmer to increase the draft and reduce creosote buildup If required by local codes make certain that the walls have been properly insulated vapour sealed and sheathed with a fire rated gypsum board see Figure 9 10 R...

Страница 12: ...must NOT go closer to the fireplace than the stand offs top back and sides You may also completely cover the top of the Delta as long as you main tain top standoff clearances and the 2 clearances around the chased chimney The 2 clearance around the chimney must be open to the fireplace up to the first fire stop 39 min SPARK GUARD Install a 5 piece of sheet metal centred under the joint between the...

Страница 13: ...rk guard 16 min 8 min 44 Figure 16 Clearance to combustibles mantle is 50 1 2 mini mum from the base of the fireplace 10 1 2 min no limit to side surround as long as 11 side clearance is observed MANTEL A masonry or other non combustible mantle may be placed directly above the top louvers If a wood or other com bustible mantle is desired then it must be at least 10 1 2 inches above the top louver ...

Страница 14: ...17 Installation of mantles and crown moulding backing 2x4 corner moulding hides mounting screws bolts screw bolt attaches crown moulding to backing 2x4 counter sink and fill crown moulding 11 6 12 25 4 12 24 47 12 12 8 6 16 2 5 5 35 3 29 19 44 2 framing guide 5 Figure 18 Unit dimensions 47 ...

Страница 15: ...re will be some increase in warm air movement to the room serviced by the gravity vent If you desire even heat throughout your home strictly from your fireplace or if you want to move heat to a remote area of your home it is recommended that you incorpo rate the central heat option parts FD HC6 and FD HB6 A thermostatically controlled blower takes heat from the fireplace and distributes the warm a...

Страница 16: ... blower with the outlet facing up from the back Fit the blower through the louver opening 3 Slide the blower into the two blower mounts being sure that it is pushed all the way down 4 Mount the thermo disc as shown in Figure 21 The front face of the fireplace is bent into a flange just above the lower opening The thermo disc mounts just above the centre louvers Push the clips on to the flange as f...

Страница 17: ... it is recommended that you purchase the rock retainer kit part FD KD 1 to help keep the facing in place It is NOT recommended for brick or other self supporting materials Follow these steps NOTE Remove the fireplace doors and louvers and store them in a safe place until the masonry work is finished Acid from the cleaning operation will permanently damage the gold plating Ensure that the cover rem...

Страница 18: ... must be removed for this option optional soldiering brick over louver openings Figure 25 Facing with soldiering brick Note when using a thicker facing be sure to leave enough room for the door to swing wide top framing guide use only the pre drilled holes in the rock retainer kit for screwing to the face spread plaster over more than a workable area so that the mortar will not set before the faci...

Страница 19: ...rts is allowed These genuine RSF Woodburning Fireplaces parts have the correct clearances These clearances must be maintained for your safety exept that B vent components can be replace by ICC double wall black pipe ULTRABlack UBF use only UBF black pipe The FD VD system incorporates standard 8 B vent com ponents for installation Single wall pipe is not allowed due to the high temperature of the a...

Страница 20: ...ur hand up inside and underneath bend up at least two of the four tabs at the base of the starter section to hold it in place 6 Install the shut off damper in the B vent starter sec tion through the left side louvers The shut off damper enables the manual control of hot air flowing through the gravity vent pipe With the top left louver removed and the angular portion of the rod in hand insert the ...

Страница 21: ...be run at a 0 clear ance to combustibles Warning If you are ducting out of the top of the fireplace and the backdraft damper is not installed the central heat ducting will become too hot for the surrounding com bustible materials Any substitute for any RSF kit will void all liability and warranty coverage by RSF Woodburning Fireplaces Installation 1 Remove the cover to the left on the top of the D...

Страница 22: ... ducting rigid or flex Any other size will not work properly Use only metal ducting between the fireplace and the blower You may use plastic ducting after the blower provided the temperature rating of the ducting is at least 250 F Do not use plastic ducting in a chase 7 To install the blower for the FD HB6 blower only attach the noise reduction collars to either side of the blower using 1 2 self t...

Страница 23: ...is is the most pop ular use of the central heat blower Do not install it in the room where the fireplace is installed We recommend an electrician wire the following There are yellow black and red wires coming out of the relay as shown in the wiring diagram Connect the wire from 4 of the terminal block to the yellow relay wire and the black transformer wire with a wire marrette Connect the black re...

Страница 24: ...ading if it is tested with a meter 2 If the blower still fails to operate consult your local RSF Woodburning Fireplaces authorized dealer for repair or replacement instructions ZONE HEATING FD HCZ 1 AND FD HCZ 2 For more regional heat control the Delta is ideally suited for zone heating Figure 38 shows an example of a three zone system The thermostat simultaneously opens the desired valve and star...

Страница 25: ...heat plenum for circulation throughout all rooms example 2 tie in to part of the duct system Figure 36 examples of air circulation when tying in to existing ducting zone dampers zone thermostats Figure 37 Zone heating example of 3 zones ...

Страница 26: ...ft damper motor internal blower thermal switch terminal block draft damper thermostat internal blower speed control black white black bare 110V relay yellow white black external blower control external central heat blower 24V 18ga LVT white Figure 38 Wiring for all systems with zone heat system zone thermostats heat only transformer ...

Страница 27: ...iring for the central system 110V draft damper motor draft damper thermostat internal bower speed control blower control thermostat variable speed switch external central heat blower 110V black black black white yellow 1 2 internal blower thermal switch bare white white 18 ga LVT transformer Figure 42 Wiring for all systems combined For a warming thermostat 1 should be the red wire and 2 should be...

Страница 28: ...31B 14 14 7 Thermostat RSF T822D2501 14 14 9 Controller 00100201 14 14 10 Control Centre 001 00204 14 14 11 Electric Blower Speed Control 5 14 14 13 Electric Blower c w Thermal Switch 11 1 D Refractory Back Right 11 2 D Refractory Back Left 11 3 D Refractory Side Right 11 4 D Refractory Side Left 11 5 D Refractory Bottom Right 11 6 D Refractory Bottom Left 11 7 D Refractory Front Right 11 8 D Refr...

Страница 29: ... OPERATE ONLY WITH VIEWING DOOR CLOSED AND LATCHED OPEN TO FEED FIRE ONLY FOR USE WITH SOLID WOOD FUELS ONLY OPERATE ONLY WITH FIREBRICK IN PLACE WARNOCK HERSEY 00000 UN PLANCHER COMBUSTIBLE DOIT ÊTRE PROTÉGÉ PAR UN MATÉRIAU NON COMBUSTIBLE S ÉTENDANT AU MOINS 16 405 MM AU DEVANT ET 8 205MM SUR LES CÔTÉS DE L OUVERTURE DE LA PORTE DU FOYER PIÈCES REQUISES POUR L INSTALLATION TUYAU FLEXIBLE DE 4 ou...

Страница 30: ... components Repairs or replacements necessitated by vandalism neglect abuse over firing improper fuel or fuel loads or failure to ade quately service the unit as stated in the owner s manual Repairs or replacements particularly charges for travel and labor not authorized by RSF Woodburning Fireplaces in advance LIMITATIONS All items found to be defective will be replaced or repaired upon return of...

Отзывы: