Smart Positioner
YT-2700
Product Manual
Ver. 1.18
46
ITEM
Description
FF / FS
YT-2700L
1’st row→FF: Fail Freeze / FS: Fail Safe.
2’nd row→Positioner model.
1.6.03
VERSION /
2017MR 8
1’st row→version number of firmware.
2’nd row→VERSION: Main software version / 2016MR 8: loading date
of software.
※
You can toggle them, pushing <ENTER>
HART REV
HART protocol version
POL AddR
HART protocol channel address.
※
You can change it, pushing <ENTER>
4.18
0Y 0d
Total used time duration. If a unit was used less than 1 minute, the
time will not accumulate.
1’st row→”4.18” means 4hours and 18minutes.
2’nd row→0Y: years, 0d: days
3.12
FULL OP
Time required (seconds) to fully open the current valve from the
closed state.
Saved after AUTO 2 or AUTO 3 Calibration.
2.97
FULL CL
Time required (seconds) to fully close the current valve from the
opened state.
Saved after AUTO 2 or AUTO 3 Calibration.
VM NOR /
VM dIZ /
VM REV
Display types of valve stroke on LCD.
VM NOR : View Mode Normal. 4mA
0%, 20mA
100% display.
VM dIZ : Raw data
VM REV : View Mode Reverse. 4mA
100%, 20mA
0% display.
※
You can change it, pushing <ENTER>
Erro
Error code(C, D) or warning code(B, F, G, H).
Refer to 9.1 or 9.2 sections
AbS
Absolute resistance value.
Содержание YT-2700
Страница 1: ...SMART POSITIONER PRODUCT MANUAL YT 2700 Rotork YTC Limited VERSION 1 18 ...
Страница 11: ...Smart Positioner YT 2700 Product Manual Ver 1 18 11 2 8 Product Dimension Fig 2 2 YT 2700L ...
Страница 12: ...Smart Positioner YT 2700 Product Manual Ver 1 18 12 Fig 2 3 YT 2700R Fork lever type ...
Страница 13: ...Smart Positioner YT 2700 Product Manual Ver 1 18 13 Fig 2 4 YT 2700R Namur Type ...
Страница 50: ...Smart Positioner YT 2700 Product Manual Ver 1 18 50 10 Main Software Map ...