Smart Positioner
YT-2700
Product Manual
Ver. 1.18
44
8.8.4
Tight Shut Open (TSHUT OP)
Tight shut open shows the current value in percentage (%). Input current of 4mA is 0%, 20mA is
100%. If temporary Tight shut open value (≤100%) is set and input current value is above the set %
value, the valve’s position is immediately moved to 100%. For example, if linear actuator is used and
the valve’s closing direction is 100% and input value of the current is above Tight shut open set value,
the set pressure from the regulator will be transferred to the actuator which will enhance the power to
close the valve and keep it from any leakage.
<
>
<
>
<UP>/<DOWN>
<
>
Press <UP> or
<DOWN> button
if the above is not
displayed.
<ESC>
3 times
8.8.5
Tight Shut Close (TSHUT CL)
Tight shut close shows the current value in percentage (%). Input current of 4mA is 0%, 20mA is
100%. If temporary Tight shut close value (≤100%) is set and input current value is below the set %
value, the valve’s position is immediately moved to 0%. For example, if rotary actuator is used and
the valve’s closing direction is 0% and input value of the current is above Tight shut open set value, it
will release all the remaining pressure from Out1 of the actuator which will have the return spring
power of the actuator or Out2 pressure to close the valve and keep it from any leakage.
<
>
<
>
<UP>/<DOWN>
<
>
Press <UP> or
<DOWN> button
if the above is not
displayed.
<ESC>
3 times
Содержание YT-2700
Страница 1: ...SMART POSITIONER PRODUCT MANUAL YT 2700 Rotork YTC Limited VERSION 1 18 ...
Страница 11: ...Smart Positioner YT 2700 Product Manual Ver 1 18 11 2 8 Product Dimension Fig 2 2 YT 2700L ...
Страница 12: ...Smart Positioner YT 2700 Product Manual Ver 1 18 12 Fig 2 3 YT 2700R Fork lever type ...
Страница 13: ...Smart Positioner YT 2700 Product Manual Ver 1 18 13 Fig 2 4 YT 2700R Namur Type ...
Страница 50: ...Smart Positioner YT 2700 Product Manual Ver 1 18 50 10 Main Software Map ...