SOFTWARE SETUP

6.2.2.10 RATIO SET

This parameter is a Ratio Multiplier that is applied to the

input command signal. It ranges from .2 to 2.  A setting of 1

results in no change to the input command signal.

6.2.3 CLOSED LOOP CONTROL PARAMETERS

6.2.3.1 PV UNITS

This is a four character label that will be displayed with the

process variable and it’s associated parameters.  It is entirely

configurable by the operator.  When selected for update, the

first of the four characters is highlighted.  The 

 / 

 selections

are used to scroll through the available characters: A-Z, a-z,

space, -, % and /.  Selecting 

E

nter will set the displayed character

and continue to the next.  When all four characters have been

set, the label is saved.  At anytime prior to the final character

being set, 

C

ancel may be selected and no change to the label

will be made.

6.2.3.2 PV MAX

This is Process Variable reading that is to be associated with

the maximum input signal of 20ma or 5V, and local setpoint.

6.2.3.3 PV MIN

This is Process Variable reading that is to be associated with

the minimum input signal of 4ma or 1V, and local setpoint.

6.2.3.4 PV DAMP

Dampening is the amount of time over which the Process

Variable input signal is averaged.  The setting may range from

0 seconds (no dampening) to 25 seconds. This is used to

smooth out rapid fluctuations of the input signal.

6.2.3.5 PV HI ALRM

This is the Alarm level that signifies that the Process Variable

signal is too high.  When the process variable input rises

above this level an alarm is generated.

6.2.3.6 PV LO ALRM

This is the Alarm level that signifies a Process Variable signal

is too low.  When the Process Variable input falls below this

level an alarm is generated.

6.2.3.7 PV ALRM DB

This parameter determines when the Process Variable High

and Low Alarms are cleared.  The Process Variable signal

must rise above the Low Alarm level by the Deadband

amount in order to clear a Process Variable Low Alarm.  The

Process Variable signal must fall below the Process Variable

High Alarm level by this amount to clear a Process Variable

High Alarm.  The parameter may be set from 0.3% to 25% of

the Process Variable signal range.

6.2.3.8 PV LOS ACTION

This is the action taken when the Process Variable input

signal is lost.  It may be configured as

LOCK – actuator locks in place at its current position

DTZ – actuator drives to the Zero position

DTS – actuator drives to the Span position

DTP – actuator drives to a user selected position

6.2.3.9 PV LOS POS

This is the position to which the actuator will drive when the

PV LOS ACTION parameter is set to Drive To Position and

that signal is lost.

6.2.3.10 PROPOR GAIN

This is the gain applied in the PI control loop of the Closed

Loop control scheme.  It tells the actuator what percentage

of the difference between the Set Point and the Process

Variable signals to use as the step up or down. The

percentage is equal to 100 divided by the PROPOR GAIN

setting. It may be set from 0 to 255%. A gain setting of

100% results in the step up or down being equal to the

difference of the two signals.

6.2.3.11 INTEGRAL TIME

This is the time over which the correction of the PI control

loop is applied to the system.  It ranges from 0 to 60

minutes.  The correction to be made to the system is

calculated and it is applied incrementally over the Integral

time.  The correction and the size of its incremental

application is continually calculated and applied to the

system.  A setting of 0 minutes would apply any required

correction immediately rather than spread out over a period

of time.

6.2.3.12 LOC/RMT SP

This parameter configures whether the Process Variable set

point of the system is obtained locally (SP) when set to

LOCAL, or if it is obtained from the input signal (on input pair

number 3) when set to REMOTE.

6.2.3.13 SET POINT

When LOC/RMT SP is set to LOCAL, this is the Local Set

Point Parameter that the system uses.  It is only available

when REM SP is set to REMOTE.

6.2.3.14 SET POINT DEV ALRM

This is the percentage of the Process variable Signal by which

the Set Point and the Process Variable signal may differ

before an alarm is triggered.

Содержание GPSA Series

Страница 1: ...Instruction Manual Established Leaders in Valve Actuation Publication P270E Issue 08 08 GPSA Series Electric Actuators and Control Systems...

Страница 2: ...1...

Страница 3: ...echanical Setup 8 DIP Switch Configuration 9 Typical Wiring Diagram 9 Actuator Setup 10 11 Menu Overview 12 Software Setup 13 19 Control Schemes 20 Troubleshooting Guide 21 Due to wide variations in t...

Страница 4: ...it is suitable for the intended application If you are unsure of the suitability of this equipment for your installation consult Rotork Process Controls prior to proceeding WARNING SHOCK HAZARD Insta...

Страница 5: ...uilt Sequential Number Month Built ABBREVIATIONS USED IN THIS MANUAL A or Amps Ampere ac Alternating Current C Degrees Celsius CW Clockwise CCW Counterclockwise dc Direct Current F Degrees Fahrenheit...

Страница 6: ...F to 150 F 20 C to 65 C Enclosure Explosion proof for Class I Division 1 Groups C and D Dust ignition proof for Class II Division 1 Groups E F and G Type 4 indoor or outdoor Duty Cycle Continuous unr...

Страница 7: ...dwheel Electronics Actuator Cover Actuator Base Magnetic Feedback Encoder Motor Screw Nut Screw Shaft Output Shaft Non Intrusive Momentary Switches for Setup and Diagnostics Vacuum Fluorescent Display...

Страница 8: ...7 MAJOR DIMENSIONS...

Страница 9: ...monitoring indication The relays may be configured to energize or de energize on the assigned condition The contacts are rated at 10mA to 5A 250V AC 30V DC The relays will de energize under loss of po...

Страница 10: ...he left Voltage input selected for INPUT 2 On slide to the right Current input selected for INPUT 3 Off slide to the left Voltage input selected for INPUT 3 On slide to the right Internally powered tr...

Страница 11: ...e settings If the parameter is numeric the knob selections will increment or decrement the parameter respectively When updating a numeric parameter value holding a knob selection or will increase the...

Страница 12: ...libration points up to 11 will be automatically available until the CAL PT X VAL parameter is set equal to the MAX POSITION parameter value set in step 1 When this occurs calibration is considered com...

Страница 13: ...2 4 8 PV MAX 6 2 4 9 PV MIN 6 2 4 10 PV DAMP 6 2 4 11 PV HI ALRM 6 2 4 12 PV LO ALRM 6 2 4 13 PV ALRM DB 6 2 4 14 PROPOR GAIN 6 2 4 15 INTEGRAL TIME 6 2 4 16 CMD CHNG TIME 6 2 4 17 CMD POS VARI 6 2 4...

Страница 14: ...btained locally when set to LOCAL or if it is obtained from the input signal on input pair number 3 when set to REMOTE SOFTWARE SETUP Configuration 6 1 Basic Parameters 6 1 1 DEADBAND This adjustment...

Страница 15: ...signal must fall below the Process Variable High Alarm level by this amount to clear a Process Variable High Alarm The parameter may be set from 0 3 to 25 of the Process Variable signal range 6 2 3 8...

Страница 16: ...le and it s associated parameters It is entirely configurable by the operator When selected for update the first of the four characters is highlighted The selections are used to scroll through the ava...

Страница 17: ...is changed by 25 and the CMD CHNG TIME parameter is set to 30 seconds incre mental changes will be made to the system each control cycle to incorporate the correction over time so that it is fully im...

Страница 18: ...or is equipped with two contact inputs that may be configured by the operator 6 4 1 INPUT SW ACTIVE Setting this parameter to YES enables input Switch 1 When active the INPUT CONFIG and INPUT SW SET p...

Страница 19: ...er 6 5 4 3 CAL PT 2 VAL This is the unit value associated with the second calibration point of the valve 6 5 4 4 CAL POINT 3 11 These are the actual positions of the output shaft at additional calibra...

Страница 20: ...or incompletely the changes will allow the actuator to run out of its expected range which could cause damage to the actuator and or to the devices to which it is connected This procedure should only...

Страница 21: ...iable Feedback Input 2 Controller Actuator Drive Valve Closed Loop GPSA Controller Process Control Mode Actuator Output Local or Remote PV Setpoint Input 3 PV Sensor Process Variable Process Variable...

Страница 22: ...r hunts in operation a Command signal is oscillating b Noise is present on command signal c Process variable is driving changing actuator position a Verify command signal is not oscillating Determine...

Страница 23: ...22...

Страница 24: ...rocess of on going product development Rotork reserves the right to amend and change specifications without prior notice Published data may be subject to change For the very latest version release vis...

Отзывы: