background image

-11-

Characterization

 – This option provides for a 2 to 11 point

calibration of the unit in order to characterize its output.  This

calibration is performed under the VALVE POS menu via the

following steps:

1. Update the MAX POSITION parameter to reflect the

value of the maximum output position of the actuator.

(ex. 100 %)

2. Select the CAL POINT 1 parameter.  Use the 

 / 

 knob

to run the actuator to the desired ZERO position. Select

E

nter to save the current physical position of actuator as

its ZERO point.

3. Continue to the CAL PT 1 VAL parameter and select it for

update.  This is the numeric value that is to be associated

with the ZERO point (ex 0 %). Update and select 

E

nter to

save this value

4. Continue to the CAL POINT 2 parameter. Use the 

 / 

knob to run the actuator to the desired position. Select

E

nter to save the current physical position of actuator as

the second calibration point.

5. Continue to the CAL PT 2 VAL parameter and select it for

update. This is the numeric value that is associated with

the second calibration point (ex 10 %).

6. Continue to the CAL POINT 3 parameter. Use the 

 / 

knob to run the actuator to the desired position. Select

E

nter to save the current physical position of actuator as

the third calibration point.

7. Continue to the CAL PT 3 VAL parameter and select it for

update. This is the numeric value that is associated with

the third calibration point (ex 20 %).

8. Calibration points (up to 11) will be automatically

available until the CAL PT X VAL parameter is set equal to

the MAX POSITION parameter value set in step 1.  When

this occurs, calibration is considered complete; no

additional calibration points are provided.

ACTUATOR SETUP

5) Transmitter

The unit may be configured to use either an internally

powered transmitter (S4  slid to the right, in line with the

painted line) or as externally loop powered (S4 slid to the

left, not in line with the painted line)  The transmitter is

factory calibrated. User calibration is not required.

6) Loss of Command Action

The unit may be configured to perform one of four actions

when a loss of the command input signal occurs while

running under the automatic operation of the Open Loop

control mode:

LOCK – Locks the unit in place at its current position

DRIVE to ZERO - The unit will drive to the ZERO position

set in calibration

DRIVE to SPAN - The unit will drive to the SPAN position set

in calibration

DRIVE to POS - The unit will drive to a user position

specified by the CMD LOS POS parameter

7) Loss of Process Variable Input Action

The unit may be configured to perform one of four actions

when a loss of the process variable input signal occurs under

the automatic operation of the Closed Loop control mode:

LOCK - Lock the unit in place at its current position

DRIVE to ZERO - The unit will drive to the ZERO position

set in calibration

DRIVE to SPAN - The unit will drive to the SPAN position set

in calibration

DRIVE to POS - The unit will drive to a user position

specified by the PV LOS POS parameter

Содержание GPSA Series

Страница 1: ...Instruction Manual Established Leaders in Valve Actuation Publication P270E Issue 08 08 GPSA Series Electric Actuators and Control Systems...

Страница 2: ...1...

Страница 3: ...echanical Setup 8 DIP Switch Configuration 9 Typical Wiring Diagram 9 Actuator Setup 10 11 Menu Overview 12 Software Setup 13 19 Control Schemes 20 Troubleshooting Guide 21 Due to wide variations in t...

Страница 4: ...it is suitable for the intended application If you are unsure of the suitability of this equipment for your installation consult Rotork Process Controls prior to proceeding WARNING SHOCK HAZARD Insta...

Страница 5: ...uilt Sequential Number Month Built ABBREVIATIONS USED IN THIS MANUAL A or Amps Ampere ac Alternating Current C Degrees Celsius CW Clockwise CCW Counterclockwise dc Direct Current F Degrees Fahrenheit...

Страница 6: ...F to 150 F 20 C to 65 C Enclosure Explosion proof for Class I Division 1 Groups C and D Dust ignition proof for Class II Division 1 Groups E F and G Type 4 indoor or outdoor Duty Cycle Continuous unr...

Страница 7: ...dwheel Electronics Actuator Cover Actuator Base Magnetic Feedback Encoder Motor Screw Nut Screw Shaft Output Shaft Non Intrusive Momentary Switches for Setup and Diagnostics Vacuum Fluorescent Display...

Страница 8: ...7 MAJOR DIMENSIONS...

Страница 9: ...monitoring indication The relays may be configured to energize or de energize on the assigned condition The contacts are rated at 10mA to 5A 250V AC 30V DC The relays will de energize under loss of po...

Страница 10: ...he left Voltage input selected for INPUT 2 On slide to the right Current input selected for INPUT 3 Off slide to the left Voltage input selected for INPUT 3 On slide to the right Internally powered tr...

Страница 11: ...e settings If the parameter is numeric the knob selections will increment or decrement the parameter respectively When updating a numeric parameter value holding a knob selection or will increase the...

Страница 12: ...libration points up to 11 will be automatically available until the CAL PT X VAL parameter is set equal to the MAX POSITION parameter value set in step 1 When this occurs calibration is considered com...

Страница 13: ...2 4 8 PV MAX 6 2 4 9 PV MIN 6 2 4 10 PV DAMP 6 2 4 11 PV HI ALRM 6 2 4 12 PV LO ALRM 6 2 4 13 PV ALRM DB 6 2 4 14 PROPOR GAIN 6 2 4 15 INTEGRAL TIME 6 2 4 16 CMD CHNG TIME 6 2 4 17 CMD POS VARI 6 2 4...

Страница 14: ...btained locally when set to LOCAL or if it is obtained from the input signal on input pair number 3 when set to REMOTE SOFTWARE SETUP Configuration 6 1 Basic Parameters 6 1 1 DEADBAND This adjustment...

Страница 15: ...signal must fall below the Process Variable High Alarm level by this amount to clear a Process Variable High Alarm The parameter may be set from 0 3 to 25 of the Process Variable signal range 6 2 3 8...

Страница 16: ...le and it s associated parameters It is entirely configurable by the operator When selected for update the first of the four characters is highlighted The selections are used to scroll through the ava...

Страница 17: ...is changed by 25 and the CMD CHNG TIME parameter is set to 30 seconds incre mental changes will be made to the system each control cycle to incorporate the correction over time so that it is fully im...

Страница 18: ...or is equipped with two contact inputs that may be configured by the operator 6 4 1 INPUT SW ACTIVE Setting this parameter to YES enables input Switch 1 When active the INPUT CONFIG and INPUT SW SET p...

Страница 19: ...er 6 5 4 3 CAL PT 2 VAL This is the unit value associated with the second calibration point of the valve 6 5 4 4 CAL POINT 3 11 These are the actual positions of the output shaft at additional calibra...

Страница 20: ...or incompletely the changes will allow the actuator to run out of its expected range which could cause damage to the actuator and or to the devices to which it is connected This procedure should only...

Страница 21: ...iable Feedback Input 2 Controller Actuator Drive Valve Closed Loop GPSA Controller Process Control Mode Actuator Output Local or Remote PV Setpoint Input 3 PV Sensor Process Variable Process Variable...

Страница 22: ...r hunts in operation a Command signal is oscillating b Noise is present on command signal c Process variable is driving changing actuator position a Verify command signal is not oscillating Determine...

Страница 23: ...22...

Страница 24: ...rocess of on going product development Rotork reserves the right to amend and change specifications without prior notice Published data may be subject to change For the very latest version release vis...

Отзывы: