PAX1 Motor Set Pressure Regulator 

User Manual

9. 

Specifications

Electrical Supply (DC)
Power Supply Voltage 

11-30 VDC

Power Consumption 

22 W max, <1.5 W standby

Electrical Supply (AC)
Power Supply Voltage 

95-250 VAC, 47-63 Hz

Power Consumption 

30 W max

Actuation Electrical, Analog
Actuation Control 

4-20 mA, 1500 V optically isolated 
from power supply, Switch for 
common power supply

Actuation Supply  

11-30 VDC (Loop Supply)

Min Current Span 

4 mA; the difference in the control 
current setting between the Lo 
Limit, and Hi Limit

Actuation Electrical, Pulse
Actuation Control 

Switch Closure Sinking, (1) increase,  
(1) decrease

Actuation Current 

10 mA sink, optically isolated  
1500 V, Switch for common  
power supply

Actuation Supply  

4 VDC minimum,  
30 VDC maximum

Monitor
Alarm Switches 

Customer use, (2) SPDT each 
switch, 1 A 250 VAC,  
(Mag latching relay)

Position Feedback 

Optional, Isolated 4-20 mA,  
11-30 VDC loop supply

Electrical Design Limits
Supply Voltage Limits (DC) 

11 VDC min, 30 VDC max

Supply Voltage Limits (AC) 

95 VAC min, 250 VAC max, 47-63 Hz

Analog input Limits 

3.5 mA min, 21 mA max,  
100 mA w/o damage

Analog Output Limits 

3.5 mA min, 21 mA max 

External loop supply 

4 VDC min, 

limits 

30 VDC max

Alarm Switches 

1 A 250 VAC SPDT

Customer interface
Electrical Connections 

Screw terminal block under cover,  
14-30 AWG

Actuator speed  

Multi-turn pot, 1.2 – 60 mm/min*

Limit adjustments 

Push button switch to accept 
current thrust rod position for (2) 
End of Travel limit, & (2) Alarm 
Switch, and Analog Feedback 
Calibration

Setup Switch  

8 position rotary switch.

Damping  

Single-turn pot, 8:1 turn down

Isolation Switch 

Pulse Control Loop – Isolated/
common to power supply 

Actuator Performance
Maximum Stroke 

25 mm

Maximum Force 

2000 N (450 lbf) Continuous Duty 
2890 N (650 lbf) for Low Duty Cycle 
Applications

Max Linear Speed 

60 mm/min

Actuator shaft 

M10 x 2 mm trapezoidal screw thd.

Power Up  

Analog Control: 2.1 sec.

Initialization Time 

Pulse Control: 0.9 sec. 
Feedback output: 0.9 sec.

EMC Ratings

FCC 47 CFR Part 15, Subpart B:2020
IC ICES-003:2016 Ed.6
CISPR 11:2009 Ed.5
IEC 61326-1:2012/07/10 Ed.2, Immunity - Equipment intended to  
be used in an industrial environment. Emissions per Section 7.2.

Environmental Ratings
Oper. Temp. Range 

-40 to +80 ºC, <50% Duty Cycle,  
<10 min cycle period  
(Motor Actuated)

 

-40 to +70ºC, Continuous Duty  
(Motor Actuated)

Ingress Protection 

IP66/68 

See agency specific 

approvals on p.2

NEMA 

Type 4X/6P 

See agency specific 

approvals on p.2

*Actuation speed may need to be limited to achieve rated thrust  
at lower supply voltages.

A4

US

US

A4

US

A4

US

A4

Содержание FAIRCHILD PAX1

Страница 1: ...PAX1 Motor Set Pressure Regulator User Manual...

Страница 2: ...sh buttons under the cover to facilitate commissioning and to permit local control of the pressure regulator s setpoint There is an 8 mm 5 16 female hex motor drive interface under the cover to allow...

Страница 3: ...Ex tb IIIC T85 C T100 C Db II 2 GD T6 T85 C Ta 40 C to 65 C T5 T100 C Ta 40 C to 70 C IP66 IP68 FM Hazardous Area Conditions of use Hazardous locations wiring must comply with ANSI NFPA 70 NEC Wiring...

Страница 4: ...eled on the regulator body under the ports Tighten connections securely NOTES Oil free air must be applied to the regulator Use a filter to remove dirt and entrained liquid in the air line ahead of th...

Страница 5: ...rimp ferrules for wires entering the terminal block at connection 11 12 Crimp ferrule onto wire then clamp it in the terminal block Figure 1 Grounding An internal ground lug is provided Use the ring t...

Страница 6: ...ol using an external loop supply DN UP RS 485 GND 1 2 3 4 5 6 7 8 9 10 11 12 SW2 Isolation Switch set to No FEEDBACK Switch set to PULSE Internal connection of NO ISOLATE switch Set to NO ANALOG CONTR...

Страница 7: ...P SUPPLY External loop supply for Isolated Feedback Loop Figure 6 Power and Feedback Connections 1 2 3 4 5 6 7 8 9 10 11 12 RS 485 GND FEEDBACK PULSE CONTROL ANALOG CONTROL mA B A mA DC POWER RS 485 D...

Страница 8: ...put control using an external loop supply 1 2 3 4 5 6 7 8 9 10 11 12 4 20 mA CONTROLLER Set switch to ANALOG DN UP RS 485 GND FEEDBACK PULSE CONTROL ANALOG CONTROL mA B A mA AC POWER RS 485 LOOP PWR S...

Страница 9: ...9 NO NC C ALARM SW LO C NO NC NO NO NC NC ALARM SW HI Alarm Indicator Power Supply Figure 11 Alarm Switch Connections 4 Electrical Connections AC Power continued...

Страница 10: ...eached thrust rod will move down only LIMIT LO Green Lo limit not reached thrust rod will move in both directions Red Lo Limit reached thrust rod will move up only ALARM HI Green Hi Alarm not reached...

Страница 11: ...will ignore the previous pressure limits so that new limits may be set beyond the previously set limits The LIMIT LO and LIMIT HI LEDs will continue to operate from the previously set limits until ne...

Страница 12: ...and DN RETRACT button and monitoring the Analog Feedback current on the milliammeter adjust the output current to the desired value 12 20 mA for this position 4 10 Press the SET button and wait for th...

Страница 13: ...00 348 1 13 71 FRONT M5 GROUND SCREW HOLE HARDWARE INCLUDED 68 3 2 69 256 3 10 09 27 1 1 07 2 3 4 14 NPTF CONDUIT PORTS 38 1 1 50 76 3 3 00 19 1 0 75 BACK 1 4 18 NPTF OR 1 4 19 BSPT EXHAUST 1 4 18 NPT...

Страница 14: ...T 78 0 3 07 TOP 175 9 6 93 152 4 6 00 FRONT M5 GROUND SCREW HOLE HARDWARE INCLUDED 133 4 5 25 27 1 1 07 275 3 10 84 86 7 3 41 38 1 1 50 BACK 1 4 18 NPTF OR 1 4 19 BSPT EXHAUST 14 18 NPTF OR 1 4 19 BSP...

Страница 15: ...6 1 2 14 NPTF 1 2 14 BSPT 1 2 14 BSPP 3 4 14 NPTF 3 4 14 BSPT 3 4 14 BSPP INLET OUTLET 117 3 4 62 225 3 8 87 215 9 8 50 152 4 6 00 1 4 18 NPTF OR 1 4 19 BSPT EXHAUST M5 GROUND SCREW HOLE HARDWARE INCL...

Страница 16: ...1 16 27 NPTF OR 1 16 28 BSPT ORIENTATION WILL VARY 65 2 5 B B B B INLETS OUTLETS 333 13 1 55 70 55 78 3 1 154 6 1 19 0 8 A A INLET OUTLET 2 3 4 14 NPTF CONDUIT PORTS A A M5 GROUNDING SCREW HARDWARE I...

Страница 17: ...BSPT CONDUIT PORTS 2 3 4 NPT GAGE PORT 1 4 18 NPTF OR 1 4 19 BSPT 31 1 2 19 8 38 1 5 260 10 2 37 1 5 INLET OUTLET 1 4 18 NPTF OR 1 4 19 BSPT 154 6 1 63 2 5 60 352 13 9 76 3 0 25 1 0 64 2 5 2 M8 X 1 2...

Страница 18: ...REW HOLE HARDWARE INCLUDED OUTLET 1 8 NPTF OPTION U 1 8 BSPT GAGE PORT 1 8 NPTF OPTION U 1 8 BSPT 35 1 4 OUTLET 1 4 OR 3 8 NPTF OPTION U 1 4 OR 3 8 BSPT 258 10 2 INLET 1 4 OR 3 8 NPTF OPTION U 1 4 OR...

Страница 19: ...T VACUUM PUMP 1 4 18 NPTF OR 1 4 19 BSPT 98 3 9 41 1 6 37 1 5 78 3 1 154 6 1 GAGE PORT 1 4 18 NPTF OR 1 4 19 BSPT 152 6 0 242 9 5 64 2 5 2 M8 X 1 25 MOUNTING HOLES 32 1 3 M5 GROUND SCREW HARDWARE INCL...

Страница 20: ...4 VDC min limits 30 VDC max Alarm Switches 1 A 250 VAC SPDT Customer interface Electrical Connections Screw terminal block under cover 14 30 AWG Actuator speed Multi turn pot 1 2 60 mm min Limit adju...

Страница 21: ...te Pulse mode and pressing the Jog DN button retract the thrust rod to its most retracted position Zero output pressure from the pressure regulator To expose the thrust rod remove the four bolts that...

Страница 22: ...e Regulator Assembly Actuator Thrust Rod O Ring Thrust Rod Cap O Ring Pressure Regulator Mounting Bolts Pressure Regulator Mounting Plate Actuator Mounting Bolts O Ring Pressure Regulator Figure 20 PA...

Страница 23: ...23 12 Notes...

Страница 24: ...tork reserves the right to amend and change specifications without prior notice Published data may be subject to change For the very latest version release visit our website at www rotork com The name...

Отзывы: