Suitably rated conduit seals must be used for the conditions of use such as dust tight seals for 
Class II & III, Groups E, F, G or water proof seals to prevent water ingress.  

 

To maintain Type 4X and IP66 rating when installing threaded conduit, use PTFE thread sealant 
tape according to instructions. 

 

CSA Specific Conditions of use: 

o

 

CAUTION

 

 

USE SUPPLY WIRES SUITABLE FOR AT LEAST 90°C” and “

ATTENTION

 

 

EMPLOYER DES FILS D’ALIMENTATION QUI CONVENNENT POUR AU MOINS 90°C”.

 

o

 

“TO BE CONNECTED TO A CLASS 2 CIRCUIT ONLY” and “RACCORDER UNIQUEMENT À UN 
CIRCUIT DE CLASSE 2”.

 

o

 

CAUTION

 

 

KEEP COVER TIGHT WHILE CIRCUITS ARE ALIVE” and “

ATTENTION

 

 

GARDER L

E COUVERCLE BIEN FERMÉ TANT QUE LE CIRCUITS SONT SOUS TENSION”.

 

o

 

WARNING

 

 POTENTIAL ELECTROSTATIC CHARGING HAZARD 

 

SEE INSTRUCTIONS” 

and “

AVERTISSEMENT

 

 DANGER POTENTIEL DE CHARGE ELECTROSTATIQUE 

 VOIR LES 

INSTRUCTIONS”.

 

o

 

“A SEAL SHALL BE INSTALLED WITHIN 18 in (45 cm) OF THE ENCLOSURE” and “UN 
SCELLEMENT DOIT ÊTRE INSTALLÉ À MOINS DE 45 cm (18 in) DU BOȊTER”.

 

Installation 

The PAX1 can be mounted in any position without affecting its operation.  It can be mounted to a flat 
surface using the mounting holes on the actuator.  An optional mounting bracket is also available.   For 

details, see “PAX1 Exterior Dimensions”.

 

Clean all pipelines to remove dirt and scale before installation.  Apply a minimum amount of pipe 
compound to the male threads of the fitting only.  Do not use Teflon tape as a sealant.  Start with the 
third thread back and work away from the end of the fitting to avoid the possibility of contaminating the 
regulator.  Install the regulator in the air line.  The inlet and outlet connections are labeled on the 
regulator body under the ports.   Tighten connections securely. 

NOTES:  Oil free air must be applied to the regulator.  Use a filter to remove dirt and entrained liquid in 
the air line ahead of the pressure regulator.  If an airline lubricator is used, it MUST be located 
downstream of the pressure regulator or performance will be affected. 

Installation below ground level 

Pressure Regulator Vent: For units that are installed below ground and in areas where the unit may be 
under water due to flooding, the pressure regulator vent should be piped to an area where the outlet of 
the pipe is located at an elevation above any possible flooding.  Water entering the bonnet vent will 
cause an increase in the outlet pressure in direct relation to the depth of the water above the vent.  This 
can cause a significant increase in outlet pressure especially in low pressure systems and may cause 
dangerous system overpressure conditions. 

Conduit Seal: The PAX1 is rated for limited submerged operation but the user is responsible for ensuring 
water cannot enter the PAX1 enclosure through the conduit connection and conduit port.  Ensure the 
conduit installation is water tight at elevations that may be submerged below water.  Where conduit is 
prone to collect internal condensation, appropriate conduit traps, drains and seals must be employed to 
prevent condensation from collecting inside the PAX1 enclosure. 

 

Содержание PAX1

Страница 1: ...well In analog control mode the unit is fail freeze upon loss of either control signals The actuator features UP and DOWN push buttons under the cover to facilitate commissioning and to permit local c...

Страница 2: ...uipment damage serious injury or death Hazardous Area Ratings Flameproof Factory Mutual CSA Class I Division 1 Groups ABCD T6 T5 Class I Division 1 Groups B C D T6 T5 Class II III Division 1 Groups EF...

Страница 3: ...tart with the third thread back and work away from the end of the fitting to avoid the possibility of contaminating the regulator Install the regulator in the air line The inlet and outlet connections...

Страница 4: ...elays require ferrules supplied to provide proper insulation for the high voltage AC connections Power Supply Sizing For 12 vdc operation the recommended power supply should have 2 amp capacity For 24...

Страница 5: ...p Rtn MTR ENAB DN V mA V mA 1 2 3 4 5 6 7 8 9 10 11 12 UP PWR LOOP SUPPLY Figure 1 SW2 Isolation Switch Set to Isolate FEEDBACK Switch set to PULSE Internal connection of NO ISOLATE switch Set to ISOL...

Страница 6: ...A 1 2 3 4 5 6 7 8 9 10 11 12 PWR Figure 3 FEEDBACK 4 20 mA CONTROLLER Set switch to ANALOG SW1 Set switch to 4 20 mA Lp Pwr DN UP MTR ENAB V mA V mA 1 2 3 4 5 6 7 8 9 10 11 12 PWR Figure 4 FEEDBACK 1...

Страница 7: ...3 4 5 6 7 8 9 10 11 12 PWR Figure 5 FEEDBACK POWER SUPPLY MILLIAMMETER LOOP SUPPLY CLOSED SWITCH DISABLES MOTOR Lp Pwr DN UP MTR ENAB V mA V mA 1 2 3 4 5 6 7 8 9 10 11 12 PWR Figure 6 FEEDBACK POWER...

Страница 8: ...parate external power source SW2 NO The Pulse control input circuit is connected to the DC power supply providing power to the unit Push button switches UP Moves the pressure regulator setpoint to a h...

Страница 9: ...through the hole in the top PCA cover near the SET button Turning the motor clockwise increases pressure counter clockwise decreases pressure Take care not to drive the actuator into its mechanical s...

Страница 10: ...rol current 2 7 Move the SETUP SWITCH to the TRAVEL LIMIT HI setting 2 8 Using the UP and DN buttons under the cover adjust the output pressure to the highest desired pressure 2 9 Apply the desired co...

Страница 11: ...o the ALARM SWITCH HI setting 4 5 Using the UP and DN buttons adjust the pressure regulator to its HI ALARM pressure 4 6 Press the SET button and wait for the ALARM HI LED to turn from Green then red...

Страница 12: ...d 6 2 Turn the adjustment clockwise to increase the output pressure and counter clockwise to decrease the output pressure 6 3 Take care when manually adjusting the actuator as you can damage the unit...

Страница 13: ...AUST 2X M8 MOUNTING HOLES 13 71 348 1 2 69 68 3 1 25 31 8 2 5 63 6 9 37 238 0 3 66 93 0 5 12 130 0 O 0 35 9 0 2X BRACKET MOUNTING HOLES 5 87 149 0 22595 1 MOUNTING BRACKET SOLD SEPARATELY 1 4 18 NPTF...

Страница 14: ...87 0 1 25 31 8 2 5 63 6 9 14 232 2 O 5 25 133 4 2X M5 MOUNTING HOLES 14 18 NPTF GAGE PORT 1 2 14 NPTF 1 2 14 BSPT 1 2 14 BSPP 3 4 14 NPTF 3 4 14 BSPT 3 4 14 BSPP INLET OUTLET 1 2 14 NPTF OR 3 4 14 NPT...

Страница 15: ...9 284 1 15 26 387 7 8 87 225 3 1 4 18 NPTF GAGE 1 4 18 NPTF OR 1 4 19 BSPT EXHAUST 3 75 95 2 BRACKET 1 2 14 NPTF OR 3 4 14 NPTF CONDUIT PORT M5 GROUND SCREW HOLE 1 18 30 0 1 2 14 NPTF 1 2 14 BSPT 1 2...

Страница 16: ...7 10 3 261 7 12 81 325 4 1 18 30 0 0 75 19 0 3 07 78 0 6 07 154 2 O 6 93 175 9 M5 SAFETY SCREW HOLE 1 25 31 8 2 5 63 6 2X M8 x 1 25 MOUNTING HOLES O 1 99 50 5 O 2 12 53 8 8 47 215 2 1 4 18 NPTF INLET...

Страница 17: ...07 78 0 1 00 25 3 3 61 91 6 6 157 156 4 11 4 288 4 1 18 30 0 13 86 352 0 6 07 154 2 O 6 93 175 9 2X M8 X 1 25 MOUNTING HOLES 1 4 NPTF OR BSPT INLET OUTLET 1 2 14 NPTF OR 3 4 14 NPTF CONDUIT PORT M5 SA...

Страница 18: ...3 6 2X M8 x 1 25 MOUNTING HOLES 3 07 78 0 0 53 13 5 1 4 OR 3 8 NPT OR BSPT INLET OUTLET 4 923 125 0 10 119 257 0 12 625 320 7 1 2 14 NPTF OR 3 4 14 NPTF CONDUIT PORT M5 SAFETY SCREW 1 18 30 0 6 07 154...

Страница 19: ...e 11 30VDC Power Consumption 22 watts max 1 watt standby Actuation Electrical Analog Actuation Control 4 20 mA 1500V optically isolated from power supply Switch for common power supply 1 5VDC non isol...

Страница 20: ...eed Multi turn pot 1 2 60 mm min Limit adjustments Push button switch to accept current thrust rod position for 2 End of Travel limit 2 Alarm Switch and Analog Feedback Calibration Setup Switch 8 posi...

Страница 21: ...Remove the pressure regulator and Thrust Rod Cap exposing the Thrust Rod With the setup knob to the Operate Pulse mode and pressing the Jog Up button extend the thrust rod to its most extended opposi...

Страница 22: ...tor Assembly Thrust Rod Thrust Rod Cap Pressure Regulator Mounting Bolts Pressure Regulator Mounting Plate Pressure Regulator Figure 16 OM 100PAX1R REV B 06 18 Actuator O Ring O Ring O Ring Contact Fa...

Отзывы: