6 Technical data

Installation manual

10

RRLQ011~016CA

Outdoor unit for air to water heat pump

4P385895-1A – 2016.03

6

Technical data

Latest information can be found in the technical engineering data.

6.1

Service space: Outdoor unit

Single unit (

) | Multiple units (

)

See figure 1 on the inside of the front cover.

A,B,C,D

Obstacles (walls/baffle plates)

E

Obstacle (roof)

a,b,c,d,e

Minimum service space between the unit and obstacles A, B, C, D and E

e

B

Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle B

e

D

Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle D

H

U

Height of the unit

H

B

,H

D

Height of obstacles B and D

1

Recommended to prevent exposure to wind and snow.
Not allowed

6.2

Wiring diagram

6.2.1

Wiring diagram: Outdoor unit

The wiring diagram is delivered with the unit, located at the inside of
the service cover.

Notes:

1

This wiring diagram applies only to the outdoor unit.

2

Symbols (see below).

3

Symbols (see below).

4

Refer to the option manual for connecting wiring to X6A and
X77A.

5

Refer to the wiring diagram sticker (on the back of the service
cover) for how to use the BS1~BS4 and DS1 switches.

6

When operating, do not short-circuit protective device S1PH.

7

Colours (see below).

8

Refer to the service manual for instructions on how to set the
selector switches (DS1). The factory setting of all switches is
OFF.

9

Symbols (see below).

Symbols:

L

Live

N

Neutral

Field wiring

Terminal strip

Connector

Connector

Connection

Protective earth (screw)

Noiseless earth

Terminal

Option

Wiring dependent on model

Colours:

BLK

Black

BLU

Blue

BRN

Brown

GRN

Green

ORG

Orange

RED

Red

WHT

White

YLW

Yellow

Legend:

A1P~A4P

Printed circuit board

BS1~BS4

Push button switch

C1~C4

Capacitor

DS1

DIP switch

E1H

Bottom plate heater

E1HC

Crankcase heater

F1U~F8U

(RRLQ_V3)

▪ F1U,  F3U,  F4U:  Fuse  (T  6.3  A  /

250 V)

▪ F6U: Fuse (T 5.0 A / 250 V)

▪ F7U, F8U: Fuse (F 1.0 A / 250 V)

F1U~F9U

(RRLQ_W1)

▪ F1U, F2U: Fuse (31.5 A / 500 V)

▪ F3U~F6U: Fuse (T 6.3 A / 250 V)

▪ F7U: Fuse (T 5.0 A / 250 V)

▪ F8U, F9U: Fuse (F 1.0 A / 250 V)

H1P~H7P (A2P)

(RRLQ_V3)

Light‑emitting diode (service monitor
orange)

H2P:

▪ Prepare, test: Flickering

▪ Malfunction detection: Light up

H1P~H7P (A1P)

(RRLQ_W1)

Light‑emitting diode (service monitor
orange)

HAP (A1P)

(RRLQ_V3)

Light‑emitting diode (service monitor
green)

HAP (A1P, A2P)

(RRLQ_W1)

Light‑emitting diode (service monitor
green)

K1M, K2M

(RRLQ_W1)

Magnetic contactor (main, upload)

K1R~K4R

Magnetic relay

K10R, K11R

(RRLQ_V3)

Magnetic relay

L1R~L4R

Reactor

M1C

Motor (compressor)

M1F

Motor (upper fan)

M2F

Motor (lower fan)

PS

Switching power supply

Содержание RRLQ011CAV3

Страница 1: ...Installation manual Outdoor unit for air to water heat pump English Installation manual Outdoor unit for air to water heat pump RRLQ011CAV3 RRLQ014CAV3 RRLQ016CAV3 RRLQ011CAW1 RRLQ014CAW1 RRLQ016CAW1...

Страница 2: ...D E HB HU HD B 200 A B C 200 200 200 B E 200 1000 500 A B C E 300 300 300 1000 500 D 500 D E 500 1000 500 B D 200 500 B D E HB HD HB HU 350 750 1000 500 HU HB HU 350 1000 1000 500 HB HU HB HD HD HU 20...

Страница 3: ...pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17...

Страница 4: ...rs Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing Format Paper in the b...

Страница 5: ...floor surface raise the unit to provide a free space of more than 150 mm under the outdoor unit 150 mm Drain holes Model Bottom view mm RRLQ 35 36 61 99 16 71 60 159 154 182 a b c d 4 a Discharge sid...

Страница 6: ...to the indoor unit NOTICE Any exposed piping might cause condensation 7 Reattach the service cover and the piping intake plate 8 Seal all gaps example a to prevent snow and small animals from entering...

Страница 7: ...FORMATION Piping length is the one way length of liquid piping 4 4 2 To charge refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluo...

Страница 8: ...m Ssc value RRLQ011CAV3 RRLQ014CAV3 RRLQ016CAV3 0 22 525 kVA RRLQ_W1 Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produ...

Страница 9: ...re b Bush c Nut d Frame e Hose 5 Reattach the service cover 6 Connect an earth leakage circuit breaker and fuse to the power supply line 4 5 4 To reposition the air thermistor on the outdoor unit Requ...

Страница 10: ...tches 6 When operating do not short circuit protective device S1PH 7 Colours see below 8 Refer to the service manual for instructions on how to set the selector switches DS1 The factory setting of all...

Страница 11: ...fin R10T RRLQ_V3 Thermistor fin RC RRLQ_V3 Signal receiver circuit S1NPH Pressure sensor S1PH High pressure switch TC RRLQ_V3 Signal transmission circuit V1R RRLQ_V3 Power module V1R V2R RRLQ_W1 Power...

Страница 12: ...fen Tel 33 0 3 89 21 74 70 Fax 33 0 3 89 21 74 74 e ma il in fo rote x fr www ro tex fr DAIKIN AIRCONDITIONING BELGIUM NV A v e n u e F r a n k l i n 1 B B 1 3 0 0 W a v r e Tel 32 0 10 23 72 23 Fax 3...

Отзывы: