background image

4 Installation

Installation manual

7

RRLQ011~016CA
Outdoor unit for air to water heat pump
4P385895-1A – 2016.03

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution
from  your  wholesaler.  Do  not  use  soap  water,  which  may
cause cracking of flare nuts (soap water may contain salt,
which  absorbs  moisture  that  will  freeze  when  the  piping
gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap
water  may  contain  ammonia  which  causes  a  corrosive
effect between the brass flare nut and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

4.3.2

To perform vacuum drying

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Increases

There is moisture in the
system. Go to the next step.

3

Evacuate  for  at  least  2  hours  to  a  pressure  on  the  manifold  of
−0.1 MPa (−1 bar).

4

After  turning  OFF  the  pump,  check  the  pressure  for  at  least
1 hour.

5

If you do NOT reach the target vacuum or cannot maintain the
vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

4.4

Charging refrigerant

4.4.1

To determine the additional refrigerant
amount

If the total liquid

piping length is…

Then…

≤10 m

Do NOT add additional refrigerant.

>10 m

R=(total length (m) of liquid
piping⁠–⁠10 m)×0.054

R=Additional charge (kg)(rounded in units
of 0.1 kg)

INFORMATION

Piping length is the one way length of liquid piping.

4.4.2

To charge refrigerant

WARNING

▪ Only use R410A as refrigerant. Other substances may

cause explosions and accidents.

▪ R410A  contains  fluorinated  greenhouse  gases.  Its

global  warming  potential  (GWP)  value  is  2087.5.  Do
NOT vent these gases into the atmosphere.

▪ When  charging  refrigerant,  always  use  protective

gloves and safety glasses.

Prerequisite: 

Before charging refrigerant, make sure the refrigerant

piping is connected and checked (leak test and vacuum drying).

1

Connect  the  refrigerant  cylinder  to  both  the  service  port  of  the
gas stop valve and the service port of the liquid stop valve.

2

Charge the additional refrigerant amount.

3

Open the stop valves.

4.4.3

To fix the fluorinated greenhouse gases
label

1

Fill in the label as follows:

b

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

GWP × kg

1000

=
=

+

kg

=

kg

=

GWP: XXX

RXXX

a

f

c

d
e

a

If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of 

a

.

b

Factory refrigerant charge: see unit name plate

c

Additional refrigerant amount charged

d

Total refrigerant charge

e

Greenhouse gas emissions

 of the total refrigerant charge

expressed as tonnes CO

2

-equivalent

f

GWP = Global warming potential

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant  charge  in  the  system  (expressed  as  tonnes
CO

2

-equivalent)  is  used  to  determine  the  maintenance

intervals. Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

2

Fix the label on the inside of the outdoor unit near the gas and
liquid stop valves.

4.5

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

NOTICE

For applications with preferential kWh rate power supply:

The  interruption  of  the  outdoor  unit  power  supply  may  not
be  more  than  2  hours  to  guarantee  optimised  startup
conditions for the compressor.

Содержание RRLQ011CAV3

Страница 1: ...Installation manual Outdoor unit for air to water heat pump English Installation manual Outdoor unit for air to water heat pump RRLQ011CAV3 RRLQ014CAV3 RRLQ016CAV3 RRLQ011CAW1 RRLQ014CAW1 RRLQ016CAW1...

Страница 2: ...D E HB HU HD B 200 A B C 200 200 200 B E 200 1000 500 A B C E 300 300 300 1000 500 D 500 D E 500 1000 500 B D 200 500 B D E HB HD HB HU 350 750 1000 500 HU HB HU 350 1000 1000 500 HB HU HB HD HD HU 20...

Страница 3: ...pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17...

Страница 4: ...rs Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions that you must read before installing Format Paper in the b...

Страница 5: ...floor surface raise the unit to provide a free space of more than 150 mm under the outdoor unit 150 mm Drain holes Model Bottom view mm RRLQ 35 36 61 99 16 71 60 159 154 182 a b c d 4 a Discharge sid...

Страница 6: ...to the indoor unit NOTICE Any exposed piping might cause condensation 7 Reattach the service cover and the piping intake plate 8 Seal all gaps example a to prevent snow and small animals from entering...

Страница 7: ...FORMATION Piping length is the one way length of liquid piping 4 4 2 To charge refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluo...

Страница 8: ...m Ssc value RRLQ011CAV3 RRLQ014CAV3 RRLQ016CAV3 0 22 525 kVA RRLQ_W1 Equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produ...

Страница 9: ...re b Bush c Nut d Frame e Hose 5 Reattach the service cover 6 Connect an earth leakage circuit breaker and fuse to the power supply line 4 5 4 To reposition the air thermistor on the outdoor unit Requ...

Страница 10: ...tches 6 When operating do not short circuit protective device S1PH 7 Colours see below 8 Refer to the service manual for instructions on how to set the selector switches DS1 The factory setting of all...

Страница 11: ...fin R10T RRLQ_V3 Thermistor fin RC RRLQ_V3 Signal receiver circuit S1NPH Pressure sensor S1PH High pressure switch TC RRLQ_V3 Signal transmission circuit V1R RRLQ_V3 Power module V1R V2R RRLQ_W1 Power...

Страница 12: ...fen Tel 33 0 3 89 21 74 70 Fax 33 0 3 89 21 74 74 e ma il in fo rote x fr www ro tex fr DAIKIN AIRCONDITIONING BELGIUM NV A v e n u e F r a n k l i n 1 B B 1 3 0 0 W a v r e Tel 32 0 10 23 72 23 Fax 3...

Отзывы: