Rotex Heating Systems GmbH
39
7.2
Parameter settings via the service code
The parameters of the boiler controller have been configured in the factory in accordance with the following
table.
These parameters can only be changed with the service code. Take the following actions to
activate the program memory:
1.
Press the and the button simultaneously, until a
0
appears on the service display and a
0
on the temperature display.
2.
Use the button to enter
15
(service code) on the temperature display.
3.
Use the button to set the parameter you wish to configure, on the service display.
4.
Use the and button to set the parameter to the required value (visible) on the temperature display.
5.
After all the required changes have been entered, press the button until
P
appears on the service display..
The boiler controller has now been reprogrammed.
Note
Pressing the button will take you out of the menu without saving the parameter changes.
Example: Change maximum CH power
1.
Press the and the button simultaneously.
2.
Use the button to go to
15
.
3.
Press the button 3 x. 60 and 3 will appear on the display.
4.
Use the button to change the 60 to 70.
5.
Press the button until
P
appears.
6.
The change has now been implemented. The maximum CH power has been increased from 60 to 70 %.
RKOMBG ** AAV1
Paramet
er
Description
22
28
33
Settings reach
0
Service code [15]
-
-
-
Access to installers settings, the service code must be
entered (=15)
1
Installation type
0
0
0
0= combi
1= Solo RKOMBG boiler
2= Tap (hot water only)
3= Solo
2
CH pump setting
0
0
0
0= pump post-running time active
1= pump continuously active
2= not applicable
3= not applicable
3
Set maximum CH power
60
60
60
Setting reach set value parameter c up to 100%
(100 % = 99 + 1x )
3.
Maximum capacity modulating CH pump
80
80
80
Setting reach set value parameter c. up to 100%
4
Set maximum hot water power
99
99
99
Setting reach set value parameter d up to 100%
5
Min. leaving water temperature of the fuel line
25
25
25
Setting reach 10°C to set value parameter 5
5.
Max setting value leaving water temperature
via operating panel
90
90
90
Setting reach 30°C to 90°C
6
Min. outdoor temperature of the fuel line
-7
-7
-7
Setting reach -9 to 10°C
7
Max. outdoor temperature of the fuel line
25
25
25
Setting reach 15°C to 30°C
8
CH pump post-running time after CH operation
1
1
1
Setting reach 0 to 15 minutes
9
CH pump post-running time after boiler
operation
1
1
1
Setting reach 0 to 15 minutes (n/a to Combi unit)
A
Setting three-way valve or electrical valve
0
0
0
0= powered during CH operation
1= powered during hot water operation and rest
2= powered during every heat request (CH, hot water
and continuous heating function)
3= group regulation
4= External DHW tank pump
Содержание RKOMBG22AAV1