Rotex QTF 100 Скачать руководство пользователя страница 5

 

RTX-IOM-QTF-R01-0217 

Page 

5

 of 

26

 

 

www.rotexautomation.com 

 

 

3. 

Label description 

 
 
 
 
 
 
 
 
 
 
 
 

Label of the actuator defines the precise feature of that particular actuator. This 
description is written below the ROTEX logo and is as follow. 
 
 Model: QTF 

– Actuator series 

   50 

– Size of the actuator 

     E 

– Indicates spring return actuator 

     8 

– Spring set code 

Max. pr.: - 8 Bar 

– Actuator should not be operated above 8 bars. 

Seal: NBR 

– Seal material is NBR. 

Temp.: -20 °C to +80 °C 

– Operating temperature range for the actuator. 

4. 

Installation information 

Ensure that the actuator will not  be exposed to pressure in excess to the maximum rating as 
indicated on the actuator nameplate or technical documents. 

Ensure that throughout the installation there are no leaks of the supply medium. 

NOTE:

 

Depending  upon  control  unit,  actuators  may  exhaust  the  supply  media  to 

atmosphere  in  normal  operation;  this  may  not  be  permitted  in  some  applications.  In 
case of any doubt, please consult the Rotex technical team for clarifications. 

The maximum operating temperature for the actuator depends on  seals used in the actuator. 
Refer nameplate for operating temperature range. 

Ensure  that  the  maximum  operating  temperature  as  indicated  on  the  nameplate  is  not 
exceeded during operation, transportation or storage of the actuator

The  environment  and  surrounding  should  not  affect  or  limit  the  operational  safety  of  the 
product. 

Ensure  the  product  is  protected  against  impact,  vibration  or  any  kind  of  violent  movement 
during operation, transportation and storage. 

Содержание QTF 100

Страница 1: ...RTX IOM QTF R01 0217 Page 1 of 26 www rotexautomation com QTF RANGE PNEUMATIC RACK AND PINION ACTUATOR Installation Operation and Maintenance Manual...

Страница 2: ...5 Installation 9 5 1 Mounting 9 5 2 Setting 10 6 Operation 12 6 1 Operating Principle Standard Mode for double acting 12 6 2 Operating Principle Standard Mode for spring return Fail CW 13 7 Maintenan...

Страница 3: ...acturers Engineers Private Limited INDIA Manufacturer Warranty For the safety it is vital to follow instructions in the manual ROTEX will not be liable for any damages which are caused by users neglig...

Страница 4: ...ed condition are safe if the instructions contained within this manual are strictly adhered to and executed by well trained equipped prepared and competent personnel WARNING For the protection of pers...

Страница 5: ...l documents Ensure that throughout the installation there are no leaks of the supply medium NOTE Depending upon control unit actuators may exhaust the supply media to atmosphere in normal operation th...

Страница 6: ...However it is recommended to align the centreline of the pneumatic actuator module along the pipeline Ensure proper tightening of fasteners and mounting accessories to avoid loosening during operation...

Страница 7: ...ately for proper operation Operating actuators over temperature or pressure limits will result in damage to actuators 4 2 Technical Specifications Mounting is in accordance with ISO 5211 DIN 3337 VDI...

Страница 8: ...screwdriver with sharp corners rounded off Use a non hardening thread sealant on all pipe threads CAUTION Apply the thread sealant as per the manufacturer s instructions All parts should be thoroughl...

Страница 9: ...re than 30 kg 66 lb to avoid personal injury 5 1 Mounting Keep the valve on which the actuator is to be mounted in home position until the installation is complete Ensure that valve is secure Fix the...

Страница 10: ...lt in over travel or incomplete travel of the pinion Loose nut 13 rotate screw 5A in counter clock wise direction CCW to set over travel close Loose nut 13 rotate screw 5A in clock wise direction CW t...

Страница 11: ...TF 32 QTF32 E Half quarter turn 2 QTF 40 QTF 40 E Half quarter turn 3 QTF 50 QTF 50 E Half quarter turn 4 QTF 63 QTF 63 E Half quarter turn 5 QTF 80 QTF 80 E Quarter turn 6 QTF 90 QTF 90 E Quarter tur...

Страница 12: ...pply pressure is regulated to ensure maximum air supply is not exceeded Now the actuator is ready to perform 6 1 Operating Principle Standard Mode for double acting Both ports A and B are used as inle...

Страница 13: ...for spring return Fail CW Port A is used as inlet When air is supplied to Port A the pistons are moved away from each other the springs are compressed and the pinion is rotated CCW When the air is exh...

Страница 14: ...free from dust water Ensure that air supply has been disconnected Ensure proper lifting procedures are followed when moving or lifting actuators DO NOT use accessory mounting holes on top of actuator...

Страница 15: ...er spring tension Caution must be used while removing end cap bolts and end caps It is recommended to put actuator into a press during removal of end caps to ensure safe release of spring tension c Ro...

Страница 16: ...e top pinion seal 14 and the top pinion bearing 18 Remove the cam 08 g Pull the pinion the rest of the way out of the body Check the pinion bearing 5 for its condition If removal and replacement of th...

Страница 17: ...y recommended grease over the pinion bearing surface 15 and on the bottom pinion seal 11 Apply a thin coat all over the surface avoid excess grease Insert pinion carefully into the body 1 from the bot...

Страница 18: ...avoid excess grease g Rotate the pinion so that the dot on the pinion is positioned close to the two dots on the top pad of the actuator body for accurate pinion alignment For CCW assembly dot on the...

Страница 19: ...necessary to have the actuator body in the vertical position This is required to ensure that springs remain properly aligned and centered during assembly q Fix the seals 16 on the left and right end...

Страница 20: ...rn actuators release the air pressure for double acting actuators apply air to Port B This will bring the pistons back to the 0 degree position v Adjust the stroke adjustment screw 5A for the 0 degree...

Страница 21: ...an the chart specified below Actuator Model Operating Air pressure bar g Minimum operating time seconds Best recommended operating time by ROTEX Seconds QTF 32 6 0 02 0 3 QTF 40 6 0 02 0 3 QTF 50 6 0...

Страница 22: ...RTX IOM QTF R01 0217 Page 22 of 26 www rotexautomation com 10 Part list 10 1 Part list for QTF32...

Страница 23: ...RTX IOM QTF R01 0217 Page 23 of 26 www rotexautomation com 10 2 Part list for QTF40 QTF110...

Страница 24: ...RTX IOM QTF R01 0217 Page 24 of 26 www rotexautomation com 10 3 Part list for QTF125 QTF350...

Страница 25: ...MINUM LM6 2 5 STOPPER BOLT STEEL AISI304 2 6 O RING NBR 2 7 PISTON STRIP POLYACETAL 2 8 CAM CAST CARBON STEEL ASTM A216 GR WCB 1 9 COVER BOLT STEEL AISI304 8 10 WASHER POLYACETAL 1 11 O RING NBR 1 12...

Страница 26: ...re between 4 C and 49 C 40 F and 120 F Locate in an area to avoid damage by impact 12 Assistance For technical questions or assistance contact any authorized distributor of ROTEX or ROTEX MANUFACTURER...

Отзывы: