background image

Limited Warranty 

AC-425 Hardware Installation and User Guide 

41 

E

XCLUSIONS AND 

L

IMITATIONS

 

ROSSLARE shall not be responsible or liable for any damage or loss resulting from the 
operation or performance of any Product or any systems in which a Product is incorporated. 
This warranty shall not extend to any ancillary equipment not furnished by ROSSLARE, 
which is attached to or used in conjunction with a Product, nor to any Product that is used 
with any ancillary equipment, which is not furnished by ROSSLARE. 
This warranty does not cover expenses incurred in the transportation, freight cost to the 
repair center, removal or reinstallation of the product, whether or not proven defective. 
Specifically excluded from this warranty are any failures resulting from Customer's 
improper testing, operation, installation, or damage resulting from use of the Product in 
other than its normal and customary manner, or any maintenance, modification, alteration, 
or adjustment or any type of abuse, neglect, accident, misuse, improper operation, normal 
wear, defects or damage due to lightning or other electrical discharge. This warranty does 
not cover repair or replacement where normal use has exhausted the life of a part or 
instrument, or any modification or abuse of, or tampering with, the Product if Product 
disassembled or repaired in such a manner as to adversely affect performance or prevent 
adequate inspection and testing to verify any warranty claim. 
ROSSLARE does not warrant the installation, maintenance, or service of the Product. 
Service life of the product is dependent upon the care it receives and the conditions under 
which it has to operate. 
In no event shall ROSSLARE be liable for incidental or consequential damages. 

L

IMITED 

W

ARRANTY 

T

ERMS

 

T

HIS WARRANTY SETS FORTH THE FULL EXTENT OF 

QORRLAQE’R

 WARRANTY

T

HE TERMS OF THIS WARRANTY MAY NOT BE VARIED BY ANY PERSON

,

 WHETHER OR NOT PURPORTING TO 

REPRESENT OR ACT ON BEHALF OF 

ROSSLARE. 

T

HIS LIMITED WARRANTY IS PROVIDED IN LIEU OF ALL OTHER WARRANTIES

.

 

A

LL OTHER WARRANTIES 

EXPRESSED OR IMPLIED

,

 INCLUDING WITHOUT LIMITATION

,

 IMPLIED WARRANTIES OF MERCHANTABILITY AND 

FITNESS FOR A PARTICULAR PURPOSE

,

 ARE SPECIFICALLY EXCLUDED

I

N NO EVENT SHALL 

ROSSLARE

 BE LIABLE FOR DAMAGES IN EXCESS OF THE PURCHASE PRICE OF THE 

PRODUCT

,

 OR FOR ANY OTHER INCIDENTAL

,

 CONSEQUENTIAL OR SPECIAL DAMAGES

,

 INCLUDING BUT NOT LIMITED 

TO LOSS OF USE

,

 LOSS OF TIME

,

 COMMERCIAL LOSS

,

 INCONVENIENCE

,

 AND LOSS OF PROFITS

,

 ARISING OUT OF 

THE INSTALLATION

,

 USE

,

 OR INABILITY TO USE SUCH PRODUCT

,

 TO THE FULLEST EXTENT THAT ANY SUCH LOSS OR 

DAMAGE MAY BE DISCLAIMED BY LAW

T

HIS WARRANTY SHALL BECOME NULL AND VOID IN THE EVENT OF A VIOLATION OF THE PROVISIONS OF THIS 

LIMITED WARRANTY

.

 

Содержание AC-425

Страница 1: ...1 Inputs Wiring Non Supervised Inputs 15 3 2 Inputs Wiring Supervised Inputs 15 3 3 Outputs Wiring 15 3 4 Power Supply 17 3 5 Readers 18 3 6 MD IO84 19 3 7 MD D04 19 4 Input and Output Connections 21...

Страница 2: ...e la ficha Inicio para aplicar TOA Heading al texto que desea que aparezca aqu iv AC 425 Hardware Installation and User Guide 6 2 TCP IP Network Connection 37 6 3 Modem Network Connection 38 A Limited...

Страница 3: ...pen Input Connection 22 Figure 10 Normally Closed Input Connection 22 Figure 11 Normally Open Supervised Input Single Resistor 23 Figure 12 Normally Open Supervised Input Double Resistor 24 Figure 13...

Страница 4: ...Error Utilice la ficha Inicio para aplicar TOA Heading al texto que desea que aparezca aqu vi AC 425 Hardware Installation and User Guide List of Tables No table of figures entries found...

Страница 5: ...is manual describes the maximum configuration of the system with the maximum number of functions including future options Therefore not all functions described in this manual may be available in the s...

Страница 6: ...flexible and easy to use AxSraxNG software the system provides an ideal modular and expandable solution for commercial and institutional needs It provides seamless integration with Rosslare s range o...

Страница 7: ...Error Utilice la ficha Inicio para aplicar Heading 1 al texto que desea que aparezca aqu AC 425 Hardware Installation and User Guide 9 Figure 1 AC 425 panel...

Страница 8: ...4 inputs selectable as supervised or non supervised Built in sounder generator for chime bell and siren signals Panel configuration DIP switch Up to 32 access control panels in every network 128 door...

Страница 9: ...ol features 1 2 2 Configurable Links The system s configurable links model makes it possible to trigger any chosen output automatically or report a configurable alarm based on a selected input This al...

Страница 10: ...y outputs 8 supervised outputs when using MD D04 or MD IO84 expansion boards 5A relay N O and N C options Reader Ports Standard 4 reader ports With MD D04 8 reader ports Output voltage 12 VDC Max curr...

Страница 11: ...ht 8 38 lbs 3 80 kg PS 33 Power Supply Specifications Input Voltage 16 5 VAC 3 A Backup Battery Charger Output 12 VDC 300 mA To Access control panel Output Voltage 1 13 8 VDC 1 5 A To Relay Outputs Ou...

Страница 12: ...2 or 4 doors up to 8 doors with MD D04 The panels connect together in a network and are controlled by a central server computer running the AxSraxNG software system The following diagram shows an exa...

Страница 13: ...ervised Inputs 3 2 Inputs Wiring Supervised Inputs When wiring the AC 425 for supervised inputs resistors should be placed on the input switch and not on the terminal block For more details refer to C...

Страница 14: ...Error Utilice la ficha Inicio para aplicar Heading 1 al texto que desea que aparezca aqu 16 AC 425 Hardware Installation and User Guide Figure 4 Door Lock Failed Close...

Страница 15: ...wiring between the PS 33 power supply and the AC 425 It is recommended to add a 12 VDC lead acid backup battery if the main power supply fails If the main output is 12 VDC wire it to the PS 33 whose...

Страница 16: ...PS 33 and AC 425 3 5 Readers Proximity keypad readers are supplied with a limited cable The color of the cable cover represents the cable s function according to Wiegand standards When extending the...

Страница 17: ...uts to the Access Control Panel Attach the MD IO84 to the AC 425 s expansion slot as marked in red in Figure 8 For more information see the MD IO84 Installation and User Guide 3 7 MD D04 The MD D04 is...

Страница 18: ...Error Utilice la ficha Inicio para aplicar Heading 1 al texto que desea que aparezca aqu 20 AC 425 Hardware Installation and User Guide Figure 8 Connector Location for MD IO84 or MD D04 Expansions...

Страница 19: ...supervised inputs Tse the AxSraxNG system to configure each input separately Non supervised inputs have two states Normal Abnormal Supervised inputs have three states Normal Abnormal Trouble The Troub...

Страница 20: ...short circuit Switch Open Abnormal State Loop resistance Infinite open circuit Figure 10 Normally Closed Input Connection 4 1 3 Normally Open Supervised Single EOL Resistor Input Connection Connect a...

Страница 21: ...5 Hardware Installation and User Guide 23 Figure 11 Normally Open Supervised Input Single Resistor 4 1 4 Normally Open Supervised Double EOL Resistor Input Connection Connect a 2 2 k resistor in serie...

Страница 22: ...sistance or short circuit 0 resistance across input terminals Trouble State Figure 12 Normally Open Supervised Input Double Resistor 4 1 5 Normally Closed Supervised Single EOL Resistor Input Connecti...

Страница 23: ...ut Connection Connect a 2 2 k resistor in series to the input switch contacts Connect an 8 2 k resistor parallel to the input switch contacts A Normally Closed Supervised Input has 3 states Switch Clo...

Страница 24: ...ader per door Door 1 IN 1 Door 2 IN 2 Door 3 IN 3 Door 4 IN 4 REX Inputs functions when using MD D04 Scenario Setting Two readers per door Door 1 IN1 Door 2 IN2 Door 5 IN5 Door 6 IN6 One reader per do...

Страница 25: ...no general purpose inputs available General purpose inputs are suitable for most uses For example they might be used to detect tampering to activate alarm sensors or to monitor a power supply failure...

Страница 26: ...nal Fire Protection Association regulations 4 4 Card Readers and Keypads Each access control panel can be connected to a maximum of four readers or 8 readers when using MD D04 There are three availabl...

Страница 27: ...OUT Door 5 Reader 5 IN OUT Door 6 Reader 6 IN OUT Door 7 Reader 7 IN OUT Door 8 Reader 8 IN OUT Use the AxSraxNG software to set the readers for IN or OUT use and to set the data transmission format...

Страница 28: ...ers Connectors Description Setup Two readers per door Outputs Door 1 Lock output OUT 1 Door 2 Lock output OUT 2 General purpose output OUT 3 General purpose output OUT 4 Inputs Door 1 Request to exit...

Страница 29: ...r1 IN OUT Reader2 Door2 OUT IN Reader3 Door1 IN OUT Reader4 Door2 OUT IN Reader5 Door3 IN OUT Reader6 Door4 OUT IN Reader7 Door3 IN OUT Reader8 Door4 OUT IN One reader per door with 8 readers MD D04 O...

Страница 30: ...ers and their functions DIP Switch Function 1 Panel s communication baud rate 2 3 Panel type Defines the number of readers for each door one or two readers per door This will also affect the number of...

Страница 31: ...switch There are two panel types a panel with one reader per each door or a panel with two readers per each door This DIP switch setting influences the number of readers per door in the panel The def...

Страница 32: ...6 Switch 7 Switch 8 1 Off Off Off Off Off 2 Off Off Off Off On 3 Off Off Off On Off 4 Off Off Off On On 5 Off Off On Off Off 6 Off Off On Off On 7 Off Off On On Off 8 Off Off On On On 9 Off On Off Of...

Страница 33: ...Installation and User Guide 35 Address Switch 4 Switch 5 Switch 6 Switch 7 Switch 8 28 On On Off On On 29 On On On Off Off 30 On On On Off On 31 On On On On Off 32 On On On On On The AC 425 panel add...

Страница 34: ...n to the computer When using an RS 232 connector only one AC 425 panel can be linked to each communication port on the computer Use an RS 485 if you wish to connect more than one panel on one communic...

Страница 35: ...serial line using a daisy chain formation The first panel is connected directly to the server using an MD 14 adaptor while the second panel connects to the first panel Additional panels are connected...

Страница 36: ...et port of the panel to the LAN WAN connection is 328 ft 99 97 m When the TCP IP connection is implemented over a Wide Area Network WAN it becomes possible to connect through the Internet This makes i...

Страница 37: ...e panel must be initialized from the computer running the AxSraxNG software 6 3 3 Computer Connections The MD N33 must connect to the computer via a serial port To connect to the PC 1 Connect a 9 VDC...

Страница 38: ...this warranty Unless otherwise requested by a ROSSLARE representative return of the failed product s is not immediately required If ROSSLARE has not contacted the Customer within a sixty 60 day holdi...

Страница 39: ...of or tampering with the Product if Product disassembled or repaired in such a manner as to adversely affect performance or prevent adequate inspection and testing to verify any warranty claim ROSSLA...

Отзывы: