¡Error! Utilice la ficha Inicio para aplicar Heading 1 al texto que desea que
aparezca aquí.
AC-425 Hardware Installation and User Guide
23
Figure 11: Normally Open Supervised Input (Single Resistor)
4.1.4
Normally Open Supervised Double EOL Resistor Input
Connection
Connect a 2.2 k
Ω
resistor in series to the input switch contacts.
Connect an 8.2 k
Ω
resistor parallel to the input switch contacts.