AC-225x-B Hardware Settings
28
AC-225x-B Series Hardware Installation and User Manual
5.2
Access Control Panel Baud Rate
The access control panel serial port baud rate, set in DIP switches one and two,
defines the communication speed for connecting with a PC in a network
connection. The default baud rate is set to 9600 bits per second.
Table 4 lists Switch 1 and 2 status and baud rate:
Table 4: Switch Baud Rates
Switch 1
Switch 2
Baud Rate
OFF
OFF
9600
OFF
ON
19200
ON
OFF
115200
ON
ON
57600
The access control panel baud rate must be identical to the AxTrax Network
configuration of baud rate.
5.3
Access Control Panel Type
The access control panel type is defined using the third DIP switch. There are two
panel types
–
a panel with one reader per each door or a panel with two readers
per each door. This DIP switch setting influences the number of doors in the panel.
The default access control panel setting is for two readers per each door.
▪
OFF
–
Defines using two readers for each door. Panel controls one door or
two doors when MD-D02B is installed.
▪
ON
–
Defines using one reader for each door. Panel controls two doors or four
doors when MD-D02B installed.
Select the appropriate DIP switch setting to operate the panel as either a single
door, a double door, or four doors (see Section 5.1).
Access control panels configured as either single door or double door controllers
have two readers, IN or OUT. Access control panels configured with the MD-D02B
expansion as either double door or four-door controllers have four readers.
Table 5 summarizes the possible hardware settings.
Table 5: Possible Hardware Settings
Single Door
Outputs
Door Lock output
(OUT 1)
General purpose output
(OUT 1A)
General purpose output
(OUT 2)
General purpose output
(OUT 2A)