Input and Output Connections
AC-225x-B Series Hardware Installation and User Manual
23
4.1.6
Normally Closed Supervised Double Resistor Input
Connection
Connect a 2.2 k
Ω
resistor in series to the input switch contacts.
Connect an 8.2 k
Ω
resistor parallel to the input switch contacts.
Normally Closed Supervised Input has 3 states:
▪
Switch Closed
–
Normal State:
Loop resistance = 2.2 k
Ω
▪
Switch Open
–
Abnormal State:
Loop resistance = 10.4 k
Ω
▪
Open circuit (Infinite loop resistance) or short circuit (0 resistance) across
input terminals
–
Trouble State
Figure 15: Normally Closed Supervised Input Connection (Double Resistor)
4.2
Inputs Description
4.2.1
Request-to-Exit (REX) Button Input
Use the REX input to open a door directly. Typically, the REX input is connected to
a Normally Open push button that is located inside the premises. The push button
is generally located in an easy-to-access position and opens a door without reading
a proximity card or PIN code.
Single door controller:
Door 1
–
IN1
Double door controller:
Door 1
–
IN 1
Door 2
–
IN 2
REX input functions when using MD-D02B:
Double door controller:
(each door has two readers)
Door 1
–
IN1
Door 2
–
IN5
Four door controller
(each door has one reader)
Door 1
–
IN1
Door 2
–
IN2
Door 3
–
IN5
Door 4
–
IN7
4.2.2
Door Monitor Input
The Door Monitor input typically connects to a Normally Closed door sensing
micro-switch for door status monitoring. Using Door Monitor enables many