AC-215x Hardware Settings
5.1
DIP Switch Configuration
The DIP switches in the access control panel determine the baud rates for serial
communication, control panel type, and the device address, as summarized in
Table 3: DIP Switches and Their Functions
DIP
Switch
Function
1
The panel's communication baud rate
2
3
The panel type defines the number of readers for each
door – one or two readers per door. This also affects the
number of doors controlled by the panel.
4
The access control panel's RS-485 network address
5
6
7
8
Power down the access control panel before changing the DIP switch settings.
After changes have been made, restart the panel. The new settings are
automatically defined after power up.
In general, the up position is ON and the down position is OFF as
demonstrated in Figure 15.
Figure 15: DIP Switches
1 2 3 4 5 6 7 8
5.2
Access Control Panel Baud Rate
The access control panel serial port baud rate, set in DIP switches one and two,
defines the communication speed for connecting with a PC in a network
connection. The default baud rate is set to 9600 bits per second.