background image

CLUTCH 

  

 

CLOSING PHOTOCELL

 

Photocell FAIL SAFE function. 

(Dip 1 leave ON) at each operating cycle the photocell is checked.

 

The photocell must be connected in Normally Closed (NC) mode, Connect the GND of the photocell's TX to the ''TX -'' terminal of the control unit.

 

Connection diagram WITHOUT the FS function

 

Connection mode compatible with previous control panels or with the Fail Safe function DISABLED (Dip 1 to OFF)

 

The photocell must be turned on in Normally Open (NO) mode

 

- It must be at the same height and in the same alignment, ideal height for installation in gates is 50cm. 

- Installation should be done as close as possible to the gate. 

- The certification is only valid with the use of ROSSI approved photocells: SIA 30 FS 

NOTE: 

In the route recognition process, the barrier sensor safety system is disabled.

 

For connection of the XP20WD FAAC model, check the product manual

 

 

Photocell connection - FAIL SAFE

 

 

SIA 30 FS.

 

 

     

 

 

- Connect the photocell TX GND on

 

 

     

Put the

 

 

   the TX- terminal of the control unit

 

 

 

 

 

 

 

   

 

DIP 1 to ON

 

 

 

   

   

 

 

 

 

 

Photocell FAIL SAFE function.

 

 

       

 

- The photocell must be connected to

 

 

     

 

 

Normally closed (NF) mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TX-12v

 

GND12v CM NF

 

 

 

 

 

 

 

 

 

1- F.SAFE

 

 

2- ENC/Ñ

 

3- LV/PS

 

4- CLOSE

 

5- PAUSE

 

6- Building

 

 

Connection diagram WITHOUT the FS function

 

 

 

 

 

 

 

 

 

 
 

GND 12v

 

GND12v CM NA 

 

 

RESOURCES

 

 

DIP

 

  

1- F.SAFE

 

 

2- ENC/Ñ

 

3- LV/PS

 

4- CLOSE

 

5- PAUSE

 

6- Building

 

 

Enable 

DIP

 functions - To enable, set the switch to 

ON

 position

 

 

1 - F.SAFE 

- To enable the FAIL SAFE function set the DIP to ON; To maintain compatibility with previous versions leave DIP 1 OFF (If this process is done with

 

 

the control panel turned on, it must remove the power from the control panel and turn it back on again)

 

 

2 - ENC - WITH ENCODER-If

 the dip switch is in

 ENC 

mode, the control unit will only work with a Rossi physical encoder. This function was developed to work with

 

LINE GHT 

operators, using an encoder and steering wheel system to control the soft stop of the gate (VIRTUAL INVERTER, patent pending);

 

 

Ñ

 

ENC - WITHOUT ENCODER 

- The control unit works according to models NKXH30, NKX30FS and KXHI1024FS. Moving DIP 2 between ON and OFF, the control panel performs a RESET in the functions.

 

 

The control panel must work without a physical encoder, in this mode it will use time counting to locate itself during the gate movement, not needing to program the route. This 

function can be used with all traditional operators without encoder, it cannot be used in the DZ GHT line.

 

 

3 - LV - LIGHT 

- For automators

 without encoder

, it works according to models KXH30 and KX30FS, For automators with encoder, it works with a

 short soft stop 

for

 

DZ GHT .

 

 

- PS - HEAVY - For automators without encoder, it works according to models KXH30 and KX30FS, For automators with encoder, it works with a 

long soft stop

 for DZ GHT.

 

 

4 - Lock 

- The lock programming, when enabled, causes the control panel, after receiving an opening command, to first send a pulse to open the lock and after 0.5 seconds it starts

 

to open the gate, the lock is 

kept activated for 3.5 seconds. With the function disabled, the lock activates simultaneously with the opening of the gate for a period of 0.5 seconds. Factory default is disabled.

 

 

5 -Automatic closing (pause) 

- Put the pause switch in the ON position and give the opening command. When reaching the open limit switch (FA ) the ST led will start blinking at 1 second intervals, let

 

the 

desired time for the pause value elapse and give the command again. Each blink indicates 1 second elapsed until 12hrs (Ex.: If the led blinks 20 times, it means that the pause time will be 20 seconds. After 

performing this operation, the pause will be programmed, every opening that occurs and takes place within the programmed time will automatically close the gate. To disable this feature, simply place the pause 

switch in the OFF position. In the next command the pause will be disabled. (For this type of configuration, it is extremely important, for user safety, to use 'SIA 30 FS' barrier sensors.)

 

 

6 - Building 

- Every command opens the gate, which only closes by automatic closing, which will only stop at the open limit switch; if there is another command during the opening, the control panel will ignore 

it. After the gate reaches the

 

open limit switch, the automatic closing time will start counting, the gate will only close after the programmed time has elapsed. If there is a command from the remote control or 

BOT

 

button, the time will be reset, starting the count again. If the gate is closing, any command the gate stops and opens again.

 

 

Using 

BOT F

 it is possible to close the gate before the break time after releasing the contact.

 

 

(

Note:

 In building mode the automatic closing is enabled automatically, just adjust the time in the 1st command) 

Residential - Accepts all 

BOT

 control and pushbutton commands (1st - command opens, 2nd - stops, 3rd - closes). 

Using 

BOT F

 it is possible to stop and close the gate after 

releasing

 the contact.

 

If you are using the photocell with the PASS 

AND CLOSE

 feature, a time greater than that programmed in the PASS 

AND CLOSE function must

 be set.

 

 

 

 

  

J9 - ENCODER CONNECTOR

 

 

 

Before powering the board, connect the encoder wire to connector 

J9

 and check that 

DIP 2

 is 

OFF

 

 

 

Check the position of the connector fitting

 

Note: Only required on the GHT line

 

 

 

 
 

RECORD REMOTE CONTROL

 

 

9

 

 

 

 

 

 

 

 

 

Removable Memory:

 

  

Access key recording:

 

 

 

Press and release the learn button on the control panel; 

 

With the 

ST

 led on, press one of the control buttons at the end of the recording, it will blink and go out indicating that the programming has been accepted. 

 

Repeat the process to record other buttons. 

 

Delete individual buttons:

 

 

This feature allows the coding to be erased from the control panel's memory, independently of the key code, without affecting the others. For this, the access key must be in 

hand to perform this procedure.

 

Hold down learn while pressing the button for the key you want to delete.

 

Note: 

This operation cannot pass the maximum time of 5 seconds

 

Erase memory

: Press the

 LEARN 

button and keep it pressed until the

 ST 

LED goes out, with this procedure you erase all the recorded codes.

 

 

This control unit has a removable memory where it can be replaced or removed if the control unit is damaged, inserting the memory IC in another control unit, the recording of the controls remains recorded.

 

NOTE: 

Check the memory Ci's fitting position with the serigraphy of the board.

 

 

 

 

 

          

CLUTCH TRIMPOT ADJUSTMENT 
CLUTCH - Adjustment of engine power that can vary between 20% to 100%. 
NOTE: The adjustment value is not changed during the gate movement, only after one complete opening and closing cycle

 

 

 

 

11 

 PASS AND CLOSE PHOTOCELL

 

With this function enabled, after the car leaves the route, the gate automatically closes after the programmed time, which can be 0 sec to 1 min; for this you must install a photocell and enable the function. To 

enable, the gate must be closed and 

the FF led on

, press the 

SET BUTTON 7 times

the ST led will flash quickly for 5sec

; to record a time greater than zero, the opening command must be carried out 

during the 

5 sec

 that the ST led is blinking quickly, the gate will open and then start counting the time, to finish the count, give a command to close. To record a minimum time 0 (zero) press the 

SET BUTTON 

7 times

the ST led will flash quickly for 5sec,

 after this time it records the minimum time.

 

 

 

Pg.05

 

10 

LEARN 